Operating instructions
08/06    13
4.4  Baud rate setting/line length 
  The setting of the baud rate must be identical in all subscribers on the system bus. 
T
he maximum possible baud rate is based on the necessary overall line len
g
th of the
system bus. The baud rate is set via the parameter 
Baud-Rate 903 and thus defines 
the possible line length. 
  Operation mode  Function  max. line length 
  3 -  50 kBaud  Transmission rate 50 kBaud  1000 meters 
  4 -  100 kBaud  Transmission rate 100 kBaud  800 meters 
  5 -  125 kBaud  Transmission rate 125 kBaud  500 meters 
  6 -  250 kBaud  Transmission rate 250 kBaud  250 meters 
  7 -  500 kBaud  Transmission rate 500 kBaud  100 meters 
  8 -  1000 kBaud  Transmission rate 1000 kBaud  25 meters 
  A baud rate under 50 kBaud, as defined accordin
g
 to CANopen, is not sensible for the
system bus as the data throughput is too low. 
  The maximum line lengths stated are guidelines. If they are made complete use of, 
the admissible len
g
th is to be calculated on the basis of the line parameters and the
bus driver (PCA82C250T) 
4.5  Setting node address 
  A maximum of 63 slaves or frequency inverters with system bus can be operated on
the system bus. Each frequency inverter is 
g
iven a node ID, which may only exist
once in the system, for its unambi
g
uous identification. The settin
g
 of the system bus
node ID is done via the parameter 
Node-ID 900. 
  Parameter  Setting 
  No. Description  Min. Max. Factory setting 
 900 Node-ID  -1 63 -1 
T
hus, the system bus possesses a maximum number of 63 subscribers (Networ
k
nodes), plus one frequency inverter as a master. 
  Note: 
With the factory setting of parameter 
Node-ID 900 = -1, the system bus 
is deactivated for this frequency inverter. 
If the 
Node-ID 900 = 0 is set, the frequency inverter is defined as a mas-
ter. Only one frequency inverter on the system bus may be defined as a
master. 