Operating instructions
08/06    27
  Reading parameters: 
Client Î Server 
SDO Upload (expedited) 
 0 1 2 3 4 5 6 7 
  Ctrl. byte  Parameter number  Data set  Data 
 0x40 LSB MSB 0xnn  0 
Server Î Client  Upload Response Î Reading process free of errors 
 0 1 2 3 4 5 6 7 
  Ctrl. byte  Parameter number  Data set  Data 
 0x42 LSB MSB 0xnn LSB    MSB 
  uint/int LSB MSB 0x00 0x00 
  long LSB ... ... MSB 
Server Î Client  Abort SDO Transfer Î Reading process faulty 
 0 1 2 3 4 5 6 7 
  Ctrl. byte  Parameter number  Data set  Data 
 0x80 LSB MSB 0xnn Code 0 0 0 
  The error code is stated in byte 4 in a faulty reading process. 
(see Table, failure codes). 
  failure codes   
 Code Description  
    1  inadmissible parameter figure   
 2 inadmissible data set   
    3  parameter not readable   
    4  parameter not writable   
 5 reading error EEPROM   
 6 writing error EEPROM   
    7  checksum error EEPROM   
    8  parameter cannot be written during running drive   
    9  values of the data sets differ   
    10  parameter of wrong type   
 11 unknown parameter   
 12  BCC error in VECTRON bus protocol   
 15 unknown error   
 20  system bus subscriber not available only in access via field 
bus connection 
 21  string parameter not admissible only in access via 
VECTRON bus protocol 
  Errors marked in the table
are 
g
enerated by the field bus side, not in the Abort SDO
Transfer of the system bus. 