Operating instructions
28  08/06
4.10.2  Communication via field bus connection (SDO1) 
  If an frequency inverter has been defined as the system bus master and equipped
with a field bus interface, access to the parameterization of all the subscribers in exis-
tence on the system bus is possible by means of this field bus interface via the first
SDO channel (SDO1). An extension has been created in the protocol frame of the field
buses for this purpose. 
  Attention!  The prerequisite for this mechanism is that the identifier settin
g
 for the 
first SDO channel (SDO1) corresponds to the Predefined Connection Set.
The parameter addressed must also be existent in the system bus mas-
ter. 
4.10.2.1  Profibus-DP 
  If an object with communication channel (PKW) is used in Profibus-DP, access to all 
the other subscribers on the system bus can be done via it. The structure of the com-
munication channel permits an additional addressin
g
 of a system bus subscriber. This
is done by the use of an unused byte in the communication channel. 
  Communication channel PKW 
 0 1 2 3 4 5 6 7 
  PKE Index -  Data 
 AK/SPM Parameter 
number 
Data set  Node-ID 
system bus 
  Byte 3 is used to transmit the node ID of the required subscriber on the system bus. I
f
byte 3 = 0, the master inverter of the system bus is addressed. The display is binar
y
(0...63). 
4.10.2.2  RS232/RS485 with VECTRON bus protocol 
  In the VECTRON bus protocol, there is a byte in the tele
g
ram header that is always
transmitted with 0 as a standard feature. 
  ENQUIRY 
  0 1 2 3 4 5 6  
 Address 0 p n n n ENQ  
 Node-ID 
system bus
Data set Parameter number     
  SELECT 
  0 1 2 3 4    
  Address STX 0  p n n n ... 
   Node-ID 
System bus
Data set Parameter number   
  Byte 1 in the enquiry and byte 2 in the select telegram are not defined and are used to 
transmit the node ID of the required subscriber on the system bus. If this byte = 0,
the master inverter of the system bus is addressed. The display is ASCII correspondin
g
to the conventions for the display of the address in the VECTRON bus protocol. 
  Note:  If there is an NAK fault messa
g
e, the error is to be read out from the
system bus master with node ID = 0 via parameter 11. 