Operating instructions
08/06    41
4.12  Control parameters 
  For the monitoring of the system bus and the display of the internal states, two con-
trol parameters are provided. There is a report of the system bus state and a report o
f
the CAN state via two actual value parameters. 
The parameter 
Node-State 978 gives information about the Pre-Operational, Opera-
tional, Stopped state. A PDO transfer is only possible in the Operational state. The
state is controlled by the system bus master (PLC / PC / frequency inverter) via NM
T
telegrams. 
The parameter 
CAN-State 979 gives information about the state of the physical layer.
If there are transmission errors, the state chan
g
es from OKAY to WARNING until the
cancellation of the communication with BUS-OFF. After BUS-OFF, the CAN controller is
automatically re-initialized and the system bus started again. 
  Note:  If the BUS-OFF state occurs, the frequency inverter breaks down with
"F2210 BUS-OFF". 
  After Bus-OFF, the system bus in the frequency inverter is completely reinitialized.
There is a new boot-up messa
g
e from the subscriber and an emer
g
ency tele
g
ram with
the Bus-OFF message is transmitted. The change of state of the subscriber to Opera-
tional is done by the Start-Remote-Node tele
g
ram cyclically sent by the system bus
master. 
  Actual values of the system bus 
  No. Description  Display 
  978 Node-State  1 - Pre-Operational 
2 - Operational 
3 - Stopped 
  979 CAN-State  1 - OKAY 
2 - WARNING 
3 - BUS-OFF 