Operating instructions
08/06    47
4.14.3  Capacity planning of the system bus 
  Each PDO tele
g
ram possesses a constant useful data content of 8 Bytes. Accordin
g
 to
worst case, this results in a maximum telegram length of 140 bits. The maximum tele-
gram run time of the PDO’s is thus stipulated via the set baud rate. 
  Capacity planning   
  Baud rate / 
kBaud 
Telegram run time / μs
  1000  140  
  500  280  
  250  560  
  125  1120  
  100  1400  
  50  2800  
  As a function of the set baud rate and the transmission interval of the TxPDO’s se-
lected, the following bus loads results: 
  Capacity of the system bus 
  Bus load as a function of the transmission for one TxPDO in % 
Baud rate / 
kBaud 
1ms 2ms 3ms 4ms 5ms 6ms 7ms 8ms 9ms 10ms
 1.000 14  7  4.7 3.5 2.8 2.3 2 1.8 1.6 1.4 
 500 28 14 9.3 7 5.6 4.7 4 3.5 3.1 2.8 
 250 56  28 18.7 14 11.2 9.3  8  7  6.2 5.6 
 125 112 56 37.3 28 22.4 18.7 16  14 12.4 11.2 
 100 140 70 46.7 35  28 23.3 20 17.5 15.6 14 
 50 280 140 93.3 70  56 46.7 40  35 31.1 28 
  Attention!  A bus load >100% means that a telegram cannot be dispatched com-
pletely between two transmission times. 
Such a setting is not admissible! 
T
his observation must be done for each TxPDO. The sum of all the TxPDO’s decides on
the entire bus load. The bus load must be desi
g
ned in such a way that any tele
g
ram
repetitions for transmission errors are possible without exceeding the bus capacity. 
  Note: 
T
o facilitate capacity plannin
g
, an Microsoft Excel file with the name
"Load_Systembus.xls” is available. 










