Operating instructions
48  08/06
T
he capacity plannin
g
 are planned and documented with the help of the table. The
work sheet is available as a Microsoft Excel document "Load_Systembus.xls" on the
BONFIGLIOLI VECTRON product CD or by request. 
  Load system bus   
  Baud rate [kBaud]: 
50, 100, 125, 250, 500, 1000 
1000 
 Frequency 
inverter 
TxPDO 
Number 
Ta 
[ms] 
Workload 
[%] 
  1 0 0  
  2 0 0  
1 
3 0 0  
  1 0 0  
  2 0 0  
2 
3 0 0  
  1 0 0  
  2 0 0  
3 
3 0 0  
  1 0 0  
  2 0 0  
4 
3 0 0  
  1 0 0  
  2 0 0  
5 
3 0 0  
  1 0 0  
  2 0 0  
6 
3 0 0  
  1 0 0  
  2 0 0  
7 
3 0 0  
  1 1 14  
  2 1 14  
8 
3 1 14  
  1 1 14  
  2 1 14  
9 
3 0 0  
  1 0 0  
  2 0 0  
10 
3 0 0  
  Total workload [%]  70 
In the table, the set baud rate is entered from the parameter 
Baud-Rate 903 in
kBaud. For each frequency inverter, the set time for the transmission interval (e. 
g
.
TxPDO1 Time 931) in ms is entered for the TxPDO bein
g
 used at the time. In the
column Load the bus load caused by the individual TxPDO appears, under 
T
otal
Load the entire bus load. 
  For the bus load (Total load) the following limits have been defined: 
≤ 80 % 
Î OKAY 
 80 ... 90 % 
Î CRITICAL 
> 90 % 
Î NOT POSSIBLE 