Operating instructions
08/06    49
5  Control inputs and outputs 
5.1  Analog input EM-S1INA 
5.1.1  General 
  The analog input of the EM-RES-01 expansion module can optionally be configured as 
a voltage or a current input. Parameterization of the input signal is done by the defini-
tion of a linear characteristic and assignment as a 
−  reference value source 
(can be selected via the parameter 
Reference frequency source 475), 
−  reference percentage source 
(can be selected via the parameter 
Reference percentage source 476), 
−  actual percentage source 
(can be selected via the parameter 
Actual percentage source 478, in configura-
tion x11) or 
−  limit value sources 
(can be selected via the parameters 734…737). 
5.1.2  Configuration voltage/current input 
  The analog input of the EM-RES-01 expansion module has been confi
g
ured in the
factory setting for a voltage signal of +/- 10 V. Switch S3 enables a switch-over of the
operation mode for an analog current signal of +/-20 mA. 
X410A
X
410B
S3
  Operation mode – switch S3  Function 
OFF -Voltage input 
OFF (downward) – 
analog input EM-S1INA is configured for a 
voltage signal. 
ON -Current input 
ON (upward) – 
analog input EM-S1INA is configured for a 
current signal. 










