Specifications
7 
Connect load positive (+) and negative (-) to the TRACER load output as shown 
in figure 3-2. 
An in-line fuse holder should be wired in series in the load positive (+) or 
negative (-) wire as shown. DO NOT INSERT A FUSE AT THIS TIME. 
If wiring the load connection to a load distribution panel, each load circuit should 
be fused separately. The total load draw should not exceed the 10A load rating. 
Step 2: Battery Wiring 
WARNING: Risk of explosion or fire! Never short circuit battery positive (+) 
and negative (-) or cables 
Figure 3-3 Battery wiring 
Before connecting the battery, measure the battery voltage. It must be over 9 V to 
power the controller. For 24V, the voltage must be greater than 18V to properly detect 
a 24V battery. The 12/24V battery detection is automatic and the check is only 
performed at start-up. 
Wire an in-line fuse holder no more than 150mm from the battery positive 
terminal. DO NOT INSERT FUSE AT THIS TIME. 