Installation Guide

EN
20
Installation
www.bora.com
INFO  If the gas flame goes out, is excessively affected 
by the extractor and/or the flame is not as it 
should be (e.g. soot production, flame blowback, 
etc.), the return flow aperture must be enlarged.
4.4.4  Special assembly instructions for gas 
cooktop CKG
 Please note the local regulations and connection 
requirements applicable to gas cooktops.
 Before connecting the appliance, check that the 
appliance settings comply with local connection 
requirements (gas type and pressure).
INFO  Minimum requirement for operating gas cooktop 
CKG: System software 03.00 (or higher) 
 If necessary, retrieve the installed software version 
(see operating instructions, Menu chapter, Retrieving 
the software version).
 Update the system software if necessary (see 
operating instructions, Menu chapter, Updating the 
system software).
INFO  Minimum clearance of 650 mm between the 
worktop and wall unit in the case of gas devices.
INFO  On recirculation systems, a return flow aperture 
of at least 1,000 cm² must be provided for each 
air cleaning unit.
INFO  Ensure sufficient ventilation.
INFO  Taking into account the applicable valid 
regulations, the cooktop must be connected to 
the gas line with an upstream stopcock.
INFO  The gas supply pipe can be connected after the 
ga
s cooktop has been installed.
INFO  The hose connection must be laid in such a way 
that it is not subject to deformation, buckling or 
abrasion.
INFO  The stopcock and gas supply pipe connections 
must be accessible.
INFO  It must be possible to inspect the entire length of 
the hose line once installed.
INFO  Only compatible connection pieces are to be used 
for the hose line.
INFO  The pressure regulator must correspond to the 
set gas type and set gas pressure and must meet 
local and legal requirements.
INFO  The gas connection hose line must not come into 
contact with smoke or the flue outlet of an oven.
4.4.3  Recirculation when using the cooktop 
extractor as a recirculation system
In the case of recirculation systems there must be a 
return flow aperture in the kitchen units:
> 500 cm² (per air cleaning box) in combination with 
cooktops CKFI, CKI, CKIW, CKCH, CKCB and CKT
> 1000 cm² (per air cleaning box) in combination with 
gas cooktop CKG
INFO  If several extractor systems are operated in 
recirculation mode, the return flow aperture 
for each air cleaning box must be calculated 
correspondingly. 
Example: 
2 recirculation systems = 2 x (> 500 cm²) or 
2 x (> 1,000 cm²) in the case of gas appliances
For recirculation, the necessary return flow aperture can 
be created using a shortened plinth. A slatted plinth with 
at least the minimum opening cross-section can also be 
used.
 Ensure that the return flow aperture is large enough.
45
1 32
Fig. 4.4  Recirculation design example (kitchen is
land + 
cooktop + CKA2 + air cleaning unit)
[1]  Cooktop
[2]  Cooktop extractor CKA2 (recirculation)
[3]  Air cleaning unit (ULB1, ULB3, ULBF)
[4]  BORA plinth fan EC (ULS)
[5]  Recirculation return flow aperture 
 (Totalopeningcrosssectionperaircleaningunit≥500 cm² 
or≥1000 cm² in the case of gas cooktop CKG)










