Control Panel D9412GV4/D7412GV4 v2.
Control Panel Table of Contents | en 3 Table of contents 1 Introduction 1.1 About documentation 4 1.2 Determine Bosch Security Systems, Inc. Product Manufacturing Dates 4 2 Installation 5 2.1 Installation Preparation 5 2.2 Enclosure Options 5 2.3 Mounting Enclosure 5 2.4 Installing the Control Panel 6 2.5 Connecting Earth Ground 7 2.5.1 Terminal 10 7 2.5.2 Ground Fault Detect Enable 7 2.5.3 Enabling Ground Fault Detection 7 2.5.
en | Introduction Control Panel 1 Introduction 1.1 About documentation Copyright This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved. Trademarks All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly. 1.2 Determine Bosch Security Systems, Inc.
Control Panel Installation | en 2 Installation 2.1 Installation Preparation 5 This section contains a general installation procedure and refers to other sections of the document for detailed instructions. Review this document and the D9412GV4/D7412GV4 Program Entry Guide (P/N: F01U265459) before beginning the installation to determine the hardware and wiring requirements for the features used. Have the following documentation available when reading through this guide: 2.
en | Installation i Control Panel Notice! Electromagnetic interference (EMI) can cause problems on long wire runs. Figure 2.1: Enclosure Mounting Callout - Description 1 - Point chart label 2 - Mounting skirt hooks (2) 3 - Module mounting holes (12) 4 - Tamper switch mounting holes (5) 5 - Skirt mounting hole (1) 6 - Enclosure mounting holes (5) 7 - Mounting skirt hook holes (2) 8 - Back of the control panel 9 - Lock down tab 2.4 Installing the Control Panel 1.
Control Panel Installation | en 2.5 Connecting Earth Ground 2.5.1 Terminal 10 7 To help prevent damage from electrostatic charges or other transient electrical surges, connect the system to earth ground at Terminal 10 before making other connections. Recommended earth ground references are a grounding rod or a cold water pipe. Warning! ! Do not use telephone or electrical ground for the earth ground connection. Use 14 AWG (1.8 mm) to 16 AWG (1.5 mm) wire when making the connection.
en | Installation Control Panel Figure 2.2: Ground Fault Detect (S4) Callout - Description 1 - S4 Locked (Closed). Control panels detects ground faults. 2 - S4 Unlocked (Open). Control panel does not detect ground faults. 2.5.4 Ground Fault Impedance Specifications The table below provides the impedance specifications for detecting ground faults when any terminal or field wiring is shorted to ground.
Control Panel Installation | en 9 Figure 2.3: Reset Pin Callout - Description 1 - Reset pin locked (closed) 2 - Reset pin normal (open) Bosch Security Systens, Inc. UL Installation Instructions 2012.12 | 02 | F.01U.265.
en | Diagrams Control Panel 3 Diagrams 3.1 Faceplates Figure 3.1: Faceplates Callout - Description Callout - Description 1 - Charging status LED (yellow) 8 - Ring 2 - Low battery LED (red) 9 - Operation monitor LED (green) 3 - Color-coded battery leads 10 - Accessory connector 4 - Ground fault detect enable 11 - Reset pin 5 - Phone LED (red) 12 - SDI interconnect wiring connector 6 - Tip 13 - SDI2 interconnect wiring connector 7 - Telephone cord connector 2012.12 | 02 | F.01U.265.
Control Panel Diagrams | en 11 3.2 Power Supply Side Wiring Diagrams 3.2.1 D9412GV4/D7412GV4 Power Supply Side System Wiring Diagram (Power and Phone) Figure 3.2: Side System Wiring Diagram Callout - Description Callout - Description 1 - If required by local AHJ, connect D113 8 - To Output A or Output B Battery Lead Supervision Module. 2 - Batteries 9 - Listed Audible Signaling Devices rated at 12.
en | Diagrams i i 3.3 Control Panel Notice! For UL Certified accounts, additional power can be obtained using only a UL Listed auxiliary 12.0 VDC regulated, power-limited power supply. Notice! All terminals accept for Outputs A, B, and C (Terminals 6, 7 and 8) are supervised. D9412GV4/D7412GV4 Input Points and Peripheral Devices System Wiring Diagram Figure 3.
Control Panel i Diagrams | en 13 Notice! For D129, use zero retard except for waterflow devices. All external connections except Terminal 5 (battery positive) are power limited. Bosch Security Systens, Inc. UL Installation Instructions 2012.12 | 02 | F.01U.265.
en | Diagrams Control Panel 3.4 SDI Devices Wiring Diagrams 3.4.1 D9412GV4 SDI and Zonex Devices System Wiring Diagram Figure 3.
Control Panel i 3.4.2 Diagrams | en 15 Notice! Terminals 24 through 36 are power limited, supervised. Fire and Intrusion devices must be on separate circuits. Refer to ICP-SDI-9114 Installation Instructions (P/N: F01U030068) D7412GV4 SDI and Zonex Devices System Wiring Diagram Figure 3.
en | Diagrams Control Panel Notice! i 3.5 Terminals 24 through 36 are power limited, supervised. Fire and Intrusion devices must be on separate circuits. Refer to ICP-SDI-9114 Installation Instructions (P/N: F01U030068). D9412GV4/D7412GV4 SDI2 Devices System Wiring Figure 3.
Control Panel Diagrams | en Module D9412GV4 BB810/B820 SDI2 Inovonics 4 17 D7412GV4 1 1 16 16 16 16 8 8 Interface Modules B920 Two-line Alphanumeric Keypad5 B930 ATM Style Alphanumeric Keypad (SDI2) 5 B520 Auxiliary Power Supply Module For the D7412GV4, only 5 inputs are available on the Octo-input at address 7. 1 For the D7412GV4, only 4 outputs are available on the Octo-output at address 6. 2 For the B426/B420, only two devices can be installed at one time.
en | Diagrams Control Panel SDI2 Bus Wiring Recommendations 3.5.1 Use the following SDI2 bus wiring recommendations for SDI2 installation. The SDI2 bus is used by the GV4 Control Panel and corresponding modules to communicate with one another. Modules can be connected via home run, daisy chain, or single level T-tapped anywhere on the SDI2 bus. Please reference Figure 2.7 below. Figure 3.
Control Panel Diagrams | en Cable Overall Cable Overall Cable Overall Cable Overall capacitance cable capacitance cable capacitance cable capacitance cable length length length 19 length pF/ft ft pF/ft ft pF/ft ft pFf/ft ft < 17 7500 22 6363 27 5185 32 4400 18 7500 23 6086 28 5000 33 4242 19 7350 24 5800 29 4828 34 4100 20 7000 25 5600 30 4700 35 4000 21 6666 26 5385 31 4516 36 3800 Table 3.1: Maximum cable length i i 3.
en | Power Supply and Power Outputs Control Panel 4 Power Supply and Power Outputs 4.1 Power Supply - Primary 4.1.1 Primary (AC) Power Circuit The primary source is a 16.5 VAC, 40 VA, internally-fused transformer (Bosch Security Systems, Inc. Model D1640). The control panel draws 225 mA when idle and 300 mA when in an alarm state. The total available auxiliary current is 1.4 A. Transient suppressors and spark gaps protect the circuit from power surges.
Control Panel Power Supply and Power Outputs | en 21 D8004 Transformer Enclosure Required for Fire Systems Use the D8004 Transformer Enclosure for the D1640 Transformer in fire and combined fire and burglary applications. i Notice! Check with the Authority Having Jurisdiction (AHJ) about mounting transformers on specific circuits. Power Terminals - Secondary 4.2 Secondary (DC) Power 4.2.
en | Power Supply and Power Outputs Control Panel Warning! High current arcs are possible. The positive (red) battery lead and Terminal 5 can create high ! current arcs if shorted to other terminals or the enclosure. Use caution when working with the positive lead and Terminal 5. Always disconnect the positive (red) lead from the battery before removing it from Terminal 5. Warning! The battery terminals and wire are not power limited. A 0.250 in (6.
Control Panel Power Supply and Power Outputs | en 23 Figure 4.2: Non-PowerLimited Wiring Callout ᅳ Description 1 ᅳ Conduit required for use with external batteries. 2 ᅳ Battery wires 3 ᅳ 0.25 in (6.4 mm) minimum. To ensure proper spacing, use tie-wraps or similar devices to secure wires. 4 ᅳ Relay output wires 5 ᅳ Input or Zone wires 6 ᅳ Standby battery 4.3 Power Outputs - Circuit Protection 5 PTC’s protect the control panel from short circuits on the continuous and programmable power outputs.
en | Power Supply and Power Outputs – Control Panel Terminal 8: Output C (Switched Auxiliary Power) PTC CB5 protects Terminal 24: Zonex Power. PTC CB1 protects Terminal 32: SDI Power +. PTC CB3 protects Terminal 36: SDI2 Power +. Required by UL: – All devices powered from a power output are to be supervised. – Power outputs are not shared between fire and non-fire devices unless all devices are in conduit within 20 ft, and in the same room. 4.
Control Panel Power Supply and Power Outputs | en 25 F01U265459) contains complete instructions for programming outputs. Refer to Terminals 6 and 7, page 25, Fire System Power Formula, page 25, and Terminal 8, page 26 for descriptions of the functions of each terminal. Refer to the Bell Parameters section of the program to set the Fire Bell, Alarm Bell, and Gas Bell output responses for outputs.
en | Power Supply and Power Outputs 4.6.4 Control Panel Terminal 8 Terminal 8 provides continuous positive (+) 12.0 VDC Nominal power. Output C interrupts the power at Terminal 8 when activated. Use Terminal 8 to power smoke detectors or other devices that are reset by interrupting power. One self-resetting circuit breaker protects Terminals 6, 7, and 8 against shorts. Verification/Reset Output The default program sets Output C (Terminal 8) as a verification and reset output.
Control Panel 5 Specifications | en 27 Specifications Voltage Input Primary: Terminals 1 and 2 16.5 VAC 40 VA class 2 plug-in (Power Supply)1 transformer (D1640) Secondary: Terminals 4 and 5 Sealed lead-acid rechargeable battery (12.0 VDC, 7 Ah or 12.0 VDC, 17.2 or 18 Ah). The control panel supports up to two 12.0 VDC, 7 Ah batteries using the D122/ D122L Dual Battery Harness or two D1218 (12.0 VDC, 17.2 or 18 Ah) batteries using a D122/D122L.
en | Specifications Control Panel SDI2 Bus Telephone Connections SDI Bus B-: 9 VDC 15000 (4572 m) maximum SDI2 Bus A+; 12 VDC nominal 7500 ft (2286 m) maximum3 SDI2 Bus B-: 12 VDC nominal (7500 ft) (2286 m) maximum3 Connection: RJ31X or RJ38X jack can connect the control panels. Two telco Bosch Security Systems, Inc. D928 Dual Phone Line lines: Module required for two phone line service. Supervision supplied by the control panel.
Control Panel 5.1 Specifications | en 29 B520 Specifications Voltage Input (Power Primary: 18 VAC terminal Supply) 18.0 VAC, 50 VA class 2 plug-in transformer -TR1850 (18.0 VAC, 50 VA class 2 plug-in transformer – TR1850-CA for Canada) Secondary: Batt 1, Batt 2 The B520 Auxiliary Power Supply terminals Module supports the connection of two independantly monitored sealed lead-acid rechargeable batteries (12.0 VDC, 7 Ah through 12.0 VDC, 36 Ah).
en | Specifications Control Panel Recharge Cycle AC ON – Load shed relay resets, battery charging begins, Battery Trouble and AC Restoral Reports sent. 12.6 VDC – Battery Restoral Report sent, Low Battery LED off.
Control Panel Terminal Terminal No Description 16 POINT 4 Specifications | en 31 Requirements Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop resistance less than 100 Ω. 17 POINT 5 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop resistance less than 100 Ω. 18 19 POINT 5/6 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop COMMON resistance less than 100 Ω.
en | Specifications Terminal Terminal Control Panel Requirements No Description 36 SDI2 POWER Terminal accommodates 14 to 22 AWG, use appropriate wire size based on peripheral device current. *D9412GV4 only. Terminals 25 and 26 are NOT USED on the D7412GV4 Control Panel. Compatibilities 5.3 i Model Notice! Where the fire alarm transmitter is sharing on-premise communications equipment, the shared equipment must be UL Listed (ITE or fire protective signaling).
Control Panel Model Specifications | en Title UL 864 UL Intrusion 985 D1218 33 cUL Intrusion 12 V, 17.2 Ah Rechargeable Battery D1255/D1255B Keypads (General Purpose) X X X D1255W Text Keypad (white) X X X D1260/ Keypads X X X X X D1260B2 D1640 16.5 VAC 40 VA Transformer X D1640-CA 16.
en | Specifications Model Control Panel Title UL 864 UL Intrusion 985 RADION repeater RFPR-12-A RADION PIR X RFPR-C12_A RADION PIR C X RFUN RADION universal transmitter X 3 3 3 X Intrusion RFRP-A 3 cUL X Where the fire alarm transmitter is sharing on-premise communications equipment, the shared equipment must 1 be UL Listed (ITE or fire potective signaling). Version 1.04 or above. 2 Compatible with version 2.xx or higher 3 Table 5.2: Compatible Accessories1 5.
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450 USA www.boschsecurity.com © Bosch Security Systems, Inc.