Bosch CRC200 Room Controller Installation Manual

6 720 821 651 (2017/05)CRC200
Service menu | 19
8.2 Heating zone menu
Settings for the heating zone are made in this menu. With
automatic configuration, important data are preset.
Afterwards, only the relevant menu items appear in this menu.
Example: In case of outdoor reset control, the menu item for
room temperature-dependent control is not displayed.
NOTICE: Risk of damaging or destroying the
screed!
If radiant floor heating (Low Temp.) is
installed, observe the maximum supply
temperature recommended by the
manufacturer.
Menu item default setting Control range Functional description
Design Temp
()
113 °F (45 °C) 86...140 °F (30...60 °C)
(with Low Temp.
heating) | 86...185 °F
(30...85 °C) (only High
Temp)
Only visible if Control type = External opt. (Optimized outdoor
reset control) is selected:
This is the supply temperature requested at the outdoor design
temperature (see setting Min.outs.temp). The control range
depends on the heating system selected.
Base point
()
77 °F (25 °C) 68 °F (20 °C) ... End
point (with Low Temp.
heating)
Only visible if Control type = External simple (simple outdoor
reset control) is selected:
This is the supply temperature at fixed outside temperature of
68 °F (20 °C). The range is limited by the setting of the End
point.
End point ( ) 113 °F (45 °C)
(with Low Temp.
heating)
Base point ... 140 °F
(60 °C) (with Low Temp.
heating)
Only visible if Control type = External simple (simple outdoor
reset control) is selected:
This is the supply temperature requested at the outdoor design
temperature (see setting Min.outs.temp). The range is limited
by the setting of the Base point.
167 °F (75 °C)
(with High Temp
heating)
Base point ... 185 °F
(85 °C) (with High Temp
heating)
Max. Suppl.T. 118 °F (48 °C)
(Low Temp.
heating) | 167 °F
(75 °C) (only High
Temp)
86...140 °F (30...60 °C)
(with Low Temp.
heating) | 86...185 °F
(30...85 °C) (only High
Temp)
Maximum supply temperature; the control range depends on
the heating system selected.
PID charact. Medium Fast | Medium | Slow Control characteristics (only visible when room temperature-
dependent control is selected):
Fast: Fast (2k P range), older home, loose construction, limited
insulation
Medium: Average (3k P range), Minimum building
requirements, medium construction
Slow: Slow (4k P range), newer home, tight construction, well
insulated
Opt. pump run NO NO | YES YES: Optimized pump operation active: The heating pump runs
as little as possible on the basis of the supply temperature
(available only with supply temperature control). This saves
energy but may also reduce comfort.
NO: If the system has more than one heat source installed (e. g.
a hybrid system) or a buffer storage tank is installed, this
function must be deactivated.
Table 7 Settings in the heating zone menu