installation manual

Table Of Contents
Inspection and maintenance | 65
6 720 806 992 (2013/07)Greenstar
14.1.5 Burner servicing
Remove burner lid (steps 1 - 4).
Fig. 86 Removing the burner cover
Remove burner and clean its components.
Fig. 87 Burner
Reinstall burner in reverse order, including a new gasket if necessary.
Adjust the gas-air ratio ( page 60).
14.1.6 Heat exchanger block inspection and cleaning
Remove the inspection cover ( page 10) and any sheet metal insert
below, if installed.
Determine degree of soiling of the heat exchanger through visual
inspection.
If mechanical cleaning is required:
For cleaning the heat exchanger, Bosch offers the service accessory kit
which includes main heat exchanger gaskets, the heat exchanger brush
and heat exchanger cleaning blade (part-# 7719001998).
Remove the condensate trap (steps 1 and 2) and place a suitable
container underneath.
Fig. 88 Removing the condensate trap
DANGER: Fire danger!
Only operate the burner while installed in a boiler.
1
2
4
6 720 641 933-95.1o
3
7 181 465 330-08.2R
NOTICE: Damage to the coating of the heat exchanger.
Cleaning of the heat exchanger should not be
necessary until five years after the initial
commissioning.
Only use a Bosch cleaning blade and Bosch cleaning
brush ( page 92).
Only clean heat exchanger in case if soiling is clearly
visible.
6 720 641 933-93.1o
1
2