36 | Installation
Greenstar6 720 806 992 (2013/07)
Roof terminals Material Supplier Part number
Ø 3" / Ø 5" (Ø 76/125 mm) concentric PVC IPEX System 636 196006
Ø 3" / Ø 5" (Ø 76/125 mm) concentric CPVC IPEX System 636 197009
Ø 3" / Ø 5" (Ø 80/125 mm) concentric PP Duravent 3PPS-VK
Table 18 Roof terminals
Wall terminals Flue System / Materials Supplier Part number
Ø 3" (Ø 76 mm) parallel stainless steel Flex-L 46546901
90 °-elbow with
inlet screen
PVC (elbow)
stainless steel (screen)
IPEX (elbow)
Langly Wire (screen)
UL-S636 approval (elbow)
L2594 (screen)
Ø 3" (Ø 76 mm) twin pipe termination PP Duravent 3PPS-HTP
Ø 3" (Ø 76 mm) single pipe termination PP Duravent 3PPS-HST
Ø 3" / Ø 5" (Ø 80/125 mm) Bosch Greenstar
Horizontal Telescopic Terminal Kit
M&G Dura Vent Poly Pro Green Vent System Bosch 7738003218
Table 19 Wall terminals
NOTICE:
DO NOT use cellular core pipe.
DO NOT use PVC when using anti-freeze in the
primary circuit of the boiler. Use CPVC or stainless
steel only!
NOTICE:
Vent terminations must keep the following minimum
clearances from electric meters, gas meters,
regulators and relief equipment: 4 feet (1220 mm)
[Canada 6 feet (1830 mm)] horizontally and in no
case above and below, unless a horizontal distance of
4 feet (1220 mm) [Canada 6 feet (1830 mm)] is
maintained.