INSTRUCTION MANUAL INSTALLATION, COMMISSIONING AND SERVICING INSTRUCTIONS WORCESTER GREENSTORE LECP GROUND SOURCE HEAT PUMP IN EITHER SYSTEM OR COMBI VARIANTS 6 720 802 172-01.
LIST OF CONTENTS LIST OF CONTENTS 1 Key to symbols and safety instructions . . . . . . . . . . . . . . . . . . . 3 1.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 Benchmark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Pre - installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3.
KEY TO SYMBOLS AND SAFETY INSTRUCTIONS 20.8 20.9 20.10 20.11 20.12 20.13 Additional heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Access level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Return to factory settings . .
PRE - INSTALLATION 3 PRE - INSTALLATION 3.1 GROUND SOURCE HEAT PUMP OPERATION As the outside temperature gets colder, the heat demand of a house increases and the output of an ground source heat pump will decrease. Eventually it becomes so cold outside that the output of the heat pump alone is not able to heat the building effectively. The Greestore range of ground source heat pumps therefore allows for monoenergetic and bivalent operation.
STANDARD DELIVERY and components used as part of the secondary domestic water system must be approved for use with potable water supplies. This is to certify that the above ranges of products manufactured by Bosch Thermotechnology have been tested and found to comply with: • the requirements of the (Water Fittings) Regulations 1999 for England and Wales, the Water Byelaws 2000, Scotland and the Water Regulations Northern Ireland.
GENERAL 7 ▶ Heat pump installation, energy drilling and collector installation must follow applicable regulations. GENERAL Only a competent person may carry out the installation. The installer must follow applicable rules and regulations and recommendations from the supplier. 7.1 6-11 System are heat pumps designed to be supplemented with an external hot water cylinder e.g. our 280 litre solar compatible.
HEATING, GENERAL 7.10 CAN-BUS TERMINATION 1 Term No Term A method for good ESD protection is a ground-connected bracelet when handling electronics. This bracelet must be put on before opening the screened metal bag/packaging or before exposing an installed board. The bracelet must be worn until the circuit board is enclosed in its screen packaging or closed electric box. Replaced, returned circuit boards must be handled in the same way. 2 6 720 644 816-03.1I Fig.
ENERGY METERING the heat pump and provide the control unit with information about the current room temperature. The signal affects the flow temperature. For example, it falls when the room controller indicates a higher temperature than the one set. Room controllers are used when factors other than the outdoor temperature influence the indoor temperature of the house.
DIMENSIONS AND CLEARANCE 10 DIMENSIONS AND CLEARANCE 20 600 ≥100 81 119 100 173 67 46 52 ≥100 ≥300 10.1 6-11KW COMBI 2 3 645 6 4 800 1800 5 211 7 190 1 6 720 647 043-32.3I Fig. 6 6 720 617 200-02.1I Fig. 5 6 720 806 768 (2013/02) All dimensions are stated in mm.
DIMENSIONS AND CLEARANCE 20 600 213 189 1 E A 4 D 5 B 3 800 1520 7 645 C 6 F 2 48 105 168 88 ≥100 47 ≥100 ≥400 10.2 6-11KW SYSTEM 6 720 647 043-33.1I Fig. 8 6 720 617 200-03.2I Fig. 7 10 All dimensions are stated in mm.
TECHNICAL INFORMATION 11 TECHNICAL INFORMATION 11.1 COMPONENT PARTS 11.1.1 6-11KW COMBI 11.1.2 6-11KW SYSTEM 1 1 16 17 2 16 2 15 3 3 4 18 5 4 5 15 14 13 19 6 12 7 14 13 6 12 7 11 11 8 8 10 9 6720802416-27.1I 10 9 6720802416-26.1I Fig. 9 [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] Fig.
TECHNICAL INFORMATION 11.2 SYSTEM SOLUTIONS Detailed system solutions can be found in the product's planning documentation. 11.2.1 SYSTEM SOLUTION EXPLANATIONS E10 E10.T2 Outdoor sensor Table 3 E10 E11 E11.C101 E11.C111 E11.F101 E11.G1 E11.P101 E11.T1 E11.TT Expansion vessel Buffer tank Safety valve Circulation pump, heating system Pressure gauge Flow sensor Room controller (accessory) E22 E22.G2 E22.G3 E22.Q22 E22.R101 E22.T6 E22.T8 E22.T9 E22.T10 E22.T11 E22.
TECHNICAL INFORMATION 11.2.2 6-11KW COMBI 6 720 802 421-04.1I Fig. 11 Unmixed heating circuit with buffer tank When installing to underfloor heating systems with individual room control, a system solution with a buffer tank (E11.C111) is required to guarantee the flow over the heat pump. For explanations to the system solutions ( 11.2.1). The particle filter [E21.
TECHNICAL INFORMATION 11.2.3 6-11KW COMBI 6 720 802 421-05.1I Fig. 12 Unmixed and mixed heating circuit An absolute prerequisite for the connection is that a minimum flow of at least 70% of the heating system volume can be maintained throughout the year. The particle filter [E21.
TECHNICAL INFORMATION 11.2.4 6-11KW SYSTEM 6 720 802 421-06.1I Fig. 13 Unmixed heating circuit with buffer tank and external hot water heating When installing to underfloor heating systems with individual room control, a system solution with a buffer tank (E11.C111) is required to guarantee the flow over the heat pump. For explanations to the system solutions ( 11.2.1). The particle filter [E21.
TECHNICAL INFORMATION 11.2.5 COMBINED OPERATION OF TWO HEAT PUMPS (CASCADE CONNECTION) 6 720 802 421-07.1I Fig. 14 Two heat pumps (cascade connection) with unmixed and mixed heating circuits, buffer tank and external hot water heater. For explanations to the system solutions ( 11.2.1). The particle filter [E21.
TECHNICAL INFORMATION 11.3 TECHNICAL INFORMATION 11.3.1 6-11KW COMBI Mode fluid/water Heating output (B0/W35)1) Heating output (B0/W45)1) COP (B0/W35)1) COP (B0/W45)1) Heat transfer fluid Nominal flow (delta_T = 3K2)) Permitted external pressure drop2) Max. pressure Contents (internal) Operating temperature Connection (Cu) Compressor Type Weight cooling agent R407c3) Max. pressure Compressor oil Heating system Nominal flow (delta_T = 7K) Min./max. flow temperature Max.
TECHNICAL INFORMATION 11.3.2 DIAGRAM CIRCULATION PUMPS 6-11KW COMBI Heat transfer fluid (coll.) pump 6-7kW Combi H[kPa] 80 Heat transfer fluid pump 9kW Combi H[m] 8 7 60 6 50 5 40 4 30 3 20 2 10 1 0 0 H [kPa] H [m] 120 110 100 90 80 70 60 50 40 30 20 10 0 -c ∆p 70 . ax m 12 11 10 9 8 7 6 5 4 3 2 1 0 0 1 2 3 4 5 V [m³/h] 0 0 1 0 0.2 2 0.4 3 0.6 4 0.8 1.0 0,2 0,4 0,6 0,8 1,0 1,2 V [l/s] Q[m³/h] 1,2 6 720 641 855-36. 2il Q[l/s] 6 720 641 855-35.
TECHNICAL INFORMATION 11.3.3 6-11KW SYSTEM Mode fluid/water Heat output (B0/W35)1) Heating output (B0/W45)1) COP (B0/W35) 1) COP (B0/W45)1) Heat transfer fluid Nominal flow (delta_T = 3K2)) Permitted external pressure drop2) Max. pressure Contents (internal) Operating temperature Connection (Cu) Compressor Type Weight cooling agent R407c3) Max. pressure Compressor oil Heating system Nominal flow (delta_T = 7K) Min. flow temperature Max. flow temperature Max.
TECHNICAL INFORMATION 11.3.4 DIAGRAM CIRCULATION PUMPS 6-11KW SYSTEM Collector circuit pump 6-7kW System H[kPa] 80 Collector circuit pump 9kW System H[m] 8 7 60 6 50 5 40 4 30 3 20 2 10 1 0 0 H [kPa] H [m] 120 110 100 90 80 70 60 50 40 30 20 10 0 -c ∆p 70 . ax m 12 11 10 9 8 7 6 5 4 3 2 1 0 0 1 2 3 4 5 V [m³/h] 0 0 1 0 0.2 2 0.4 3 0.6 4 0.8 1.0 0,2 0,4 0,6 0,8 1,0 1,2 V [l/s] Q[m³/h] 1,2 6 720 641 855-36. 2il Q[l/s] 6 720 641 855-35.
REGULATIONS OUTLINE DRAWINGS FOR THE COLLECTOR HOSE IN THE GROUND AND THROUGH A WALL REGULATIONS The following regulations and requirements must be observed: • The responsible power supply company's local regulations and requirements, including any corresponding special rules • National building regulations • EN 60335 (Electrical appliances and similar utilities - Safety) part 1 (General demands) part 2-40 (Special demands on electrical heat pumps, air conditioners and air dehumidifiers) • EN 12828 (Heati
INSTALLATION After the manifolds and the flow control valves, the coils are connected to a collecting pipe. A filling link, filter and the plastic expansion vessel supplied with the heat pump are connected to the collecting pipe. A pressure relief valve is connected to the outgoing pipe. One circuit at a time is filled with heat transfer fluid. Keep the valves closed in the other loops during the process.
INSTALLATION FILLING UNIT A filling unit is included in the delivery and should be installed close to the collector circuit inlet. COLLECTOR CIRCUIT PUMP Factory setting for the collector circuit pump is max ( Figure 20). The setting may need to be adjusted to achieve the correct delta value ( Chapter 17.4). The value must lie within the grey area. To adjust the value, turn the dial. At cascade connection, make sure that the setting on the collector circuit pump is max.
INSTALLATION 13.4 HEATING SYSTEM 13.7 FLUSHING THE HEATING SYSTEM PARTICLE FILTER (INTEGRATED IN 6-11 SYSTEM) FOLLOW THE GUIDANCE OF BS7593: Treatment of water in domestic hot water central heating and also the flushing guidelines below. A particle filter for the heating system is included in the delivery of 6-11 Combi and should be installed on the connection for the heating system's return line. The particle filter is installed in the return heating pipe to the heat pump ( [E21.V101], chapter 11.2.
INSTALLATION 13.10 REMOVING THE FRONT PANEL 13.11.4 ROOM TEMPERATURE CONTROLLER (ACCESSORY) ▶ Loosen the screws, tilt the front panel outwards and take it off. 1. 2. The room controller will only operate and control the relevant heating circuit. 1. When the room temperature controller is connected and integrated in the system, this is automatically acknowledged during the initial configuration. Requirements for installation location: • If possible, interior wall without draughts or heat radiation.
INSTALLATION ▶ Refill to the correct pressure. Normal pressure is 1.0 – 2.5 bar, but depends on the expansion vessel's pre-pressure and the height of the building. ▶ Shut the heating water filling valve when the correct pressure is reached. ▶ Check all connections for leaks. ▶ Turn the valves on the filling unit so that they are in filling position ( Figure 27). 13.
ELECTRICAL CONNECTIONS ▶ The circuit must be pressurized when venting is complete. Turn the valves on the filling unit to pressure increase position and pressurize the circuit to 2.5 to 3 bar ( Figure 30). Make sure the expansion vessel has an air pocket corresponding to approximately 1/3 of the total volume, by using the de-airing valve on top of the expansion vessel 6 720 641 570-07 .1I Fig.
ELECTRICAL CONNECTIONS 14.1 CONNECTING THE HEAT PUMP CAUTION: Never touch a circuit board without wearing a ground-connected bracelet ( Chapter 7.11). ▶ Remove the front panel ( page 25). ▶ Remove the electric box cover. ▶ Route the connection cables to the electric box through the cable gland in the roof plate of the heat pump. ▶ Connect the cables according to the wiring diagram. ▶ Reinstall the electric box cover and the front panel of the heat pump. 14.2 ELECTRICAL CONNECTION WIRING DIAGRAM 14.2.
ELECTRICAL CONNECTIONS 14.2.2 CAN-BUS OVERVIEW Fig. 33 CAN-BUS overview 14.2.3 CIRCUIT BOARD WIRING 6 720 648 043-10.1I Fig. 34 Circuit board wiring 14.2.4 POWER SUPPLY The terminal blocks are attached at the factory to a common power supply. Connect to L1, 1N and PE. 1 6 720 802 416-18.1I Fig.
ELECTRICAL CONNECTIONS 14.2.5 INTERNAL WIRING DIAGRAM 6 720 802 416-10.2I Fig.
ELECTRICAL CONNECTIONS 14.2.6 COMPLETE WIRING DIAGRAM CONNECTIONS 6 720 802 416-12.2I Fig. 37 Complete wiring diagram connections (230V) Solid line = factory set connection Dotted line = connect during installation: [RHP] High pressure switch [F11/Q1] Motor cut-out compressor/soft starter [F1/F21] Fuse/overheat protection electric additional heat [K2] Contactor electric additional heat stage 1 [K3] Contactor electric additional heat stage 2 [E11.
ELECTRICAL CONNECTIONS 14.2.7 COMPLETE WIRING DIAGRAM CONNECTIONS 6 720 802 416-13.1I Fig. 38 Complete wiring diagram connections (low current) Solid line = factory set connection Dotted line = connect during installation: [B11] External input 1 [E41.F31] Alarm protective anode [E11.T1] Flow [E10.T2] Outdoor sensor [E41.T3x] Hot water System-model [E12.T1] Flow circuit 2 [G2] Heat carrier pump [E12.B11] External input, circuit 2 [B12] External input 2 [E41.
ELECTRICAL CONNECTIONS 14.3 EXTERNAL CONNECTIONS All external connections are made on terminal board PEL (low current) and connection terminal blocks. ▶ High and low current cables should be routed separately in order to avoid interference on the sensors (minimum distance of 100 mm). ▶ Use the following cable area when extending the temperature sensor cable: – Up to 20 m long cable: 0.75 till 1.50 mm2 – Up to 30 m long cable: 1.0 till 1.50 mm2 6 720 802 416-14.1I Fig.
ELECTRICAL CONNECTIONS 14.4 COMBINED OPERATION OF TWO HEAT PUMPS (CASCADE CONNECTION) 1 2 6 720 802 416-19.1I Fig. 40 CAN-BUS overview with two heat pumps 7 CAUTION: Do not mix up the 12V and CAN-BUS connections! The processors are destroyed if 12V is connected to the CAN-BUS. 1 ▶ Check that the four cables are connected to the contacts with the corresponding marking on the circuit board. In cascade connection both heat pumps must have the same output.
CONTROL PANEL 15 CONTROL PANEL Settings for the control of the heat pump are made with the control unit's control panel, which also provides information about current status. 15.1 PANEL OVERVIEW – Turn the dial to see more menus on the same level or change a set value. – Press the dial to change to a lower menu level or save a change. 15.6 RETURN BUTTON Use to: • Go back to the previous menu level. • Leave a setting display without changing the set value. 15.
FUNCTION CHECK ▶ Set Hot water production for each heat pump (compressor) ( Chapter 20.2). ▶ Set the heat pump output for each heat pump in Heat pump x capacity ( Chapter 20.7). See the type plate. ▶ Output limitation electric heater in compressor mode. Set the permitted output at the same time as the compressor is operating ( Chapter 20.8). ▶ Output limitation electric heater when additional heat only. Set the permitted output when the compressor is not operating ( Chapter 20.8).
INSTALLER MENUS tHV - tHR T1 E11.T1 Flow, circuit 1 T2 E10.T2 Out T3 E41.T3 Hot water (if hot water production) T5 E11.TT.T5 Room, circuit 1 (option, CAN-BUS sensor) T6 E21.T6 Hot gas Heat transfer fluid out P3 T8 E21.T8 P3 T9 E21.T9 Heat transfer fluid in T10 E21.T10 Collector circuit in T11 E21.T11 Collector circuit out T1 E12.T1 Flow, circuit 2 (if circuit 2 is used) T5 E12.TT.
MENU OVERVIEW 19 • • • • • • • MENU OVERVIEW The top menu level for installers is: • • • • • • • Room temperature Hot water Holiday Energy measurements Timers External control Installer Additional heat Safety functions General Alarms Access level Return to factory settings Program version Access level 0 = Customer Access level 1 = Installer HP x = Heat pump 1 or 2 / Compressor 1 or 2 Room temperature Circuit 1 Heating Access level Type of heating system 1 Highest permitted flow temperature T1 1
MENU OVERVIEW Hot water Access level Hot water peak Day of the week Interval in weeks Start time Maximum time Time for warm-keeping 0 0 0 1 1 Hot water program Active program View/edit active program 0 0 Hot water mode 0 Hot water settings heat pump x Hot water production 1 Block heating during hot water demand 1 Maximum operating time for hot water at heating demand Hot water circulation 1 Hot water circulation pump active Time settings Protective anode installed 1 1 1 Table 26 Hot wate
MENU OVERVIEW External control Heat pump x Access level External input 1, 2 External input circuit 2, 3...
MENU OVERVIEW Additional heat Additional heat general Access level Start delay 1 Allow additional heat timer during energy supply cut-off 1 Additional heat only 1 Block additional heat 1 1 Maximum outdoor temperature for additional heat Electric additional heat Hot water electric heater Additional heat program Electric heater connection Connected output Output limitation in compressor mode Output limitation when additional heat only Output limitation in hot water mode 1 1 1 1 Regulator settin
SETTINGS 20 ▶ Check also that the highest temperature T1 with Underfloor does not exceed the permitted value for the type of floor used. SETTINGS The heat curve forms the basis for set point value calculation of the flow temperature. Most other temperatures for heating that are set refer to room temperature. These values are transformed by the control unit into flow temperature values. 20.1 ROOM TEMPERATURE Press the button in the standard display to open the main menu.
SETTINGS Setting of heat curve If the heat curve has been set too high, the display will show the message Too high heat curve setting. ▶ Change the heat curve setting. A heat curve is set for each circuit. If the room temperature is perceived to be too high or too low in the circuit, it is preferable to adjust the curve. The curve can be changed in different ways.
SETTINGS >> Heat curve hysteresis heat pump x Program 1 and 2 >>> Maximum These selections provide an opportunity to define user programs for time control by adjusting the start and stop times, as well as a normal and an programmed temperature. F value Lowest value Highest value 25.0K The value in Minimum 30.0K Table 43 Maximum hysteresis Program Program 1, 2 Day Mon - Sun Start 5:30 Stop 22:00 Table 49 Program 1 and 2 ▶ Set how big the maximum hysteresis for the flow temperature can be.
SETTINGS >>> Room temperature during time program Factory setting Lowest value Highest value 17.0 °C 10.0 °C 30.0 °C Table 51 Room temperature, exception ▶ Set the temperature that should apply as exceptional temperature in the program. The menu is displayed only if Program 1or Program 2has been selected. >>> Copy to all heating circuits Factory setting Alternative No No/Yes Table 52 All circuits ▶ Select Yes to have the same control for all installed circuits.
SETTINGS At a temperature higher than 20 °C, the same curve value applies as for 20 °C. The right point of the curve (-35 °C) can be changed in Minimum outdoor temperature ( Chapter 20.1). Set value applies for all heat curves. A change of the right point affects the flow temperature for all outdoor temperatures that are lower than the set temperature. >> Highest permitted flow temperature T1 Factory setting Lowest value Highest value 80.0 °C 1) 100.
SETTINGS 20.1.1 SET POINT VALUE The heating circuit's set point value is the temperature of the flow that the heat pump attempts to maintain. Sometimes, the measured actual value fluctuates a bit upward and downward depending on changes in the outdoor temperature or a large hot water demand. The set point value specified by the customer/installer is most often the room temperature, which is recalculated by the control unit into a corresponding flow temperature set point value.
SETTINGS 20.
SETTINGS ▶ Select hot water mode. Economy means that the hot water is permitted to cool slightly before hot water production starts compared to Comfort. The hot water cylinder temperature is held at approximately 50 °C. ▶ Change to Comfort if more or hotter hot water is desired. The hot water cylinder temperature is held at approximately 58 °C.
SETTINGS 20.4 ENERGY MEASUREMENTS Energy is measured per compressor; the calculated results are added prior to being displayed. > Generated energy This displays Generated energy in kWh divided into Heating and Hot water. > Consumption electric additional heat This displays Consumption electric additional heat in kWh divided into Heating and Hot water. 20.5 TIMERS The control unit shows the timers that are in operation. There are a number of timers for, e.g.
SETTINGS 20.6 EXTERNAL CONTROL >>> Start collector circuit pump When an external input is connected, the control unit performs functions which are set to Yes or is separated from 0 (Room temperature). When the external input is no longer connected, the control unit returns to normal mode. Only installed functions are displayed.
SETTINGS 20.
SETTINGS > Compressor working area (Compressor operating) This defines a number of functions that make the compressor stop temporarily or change operating mode to avoid more serious alarms.
SETTINGS >>>> Pump speed at no demand >>> Mixing valve signal >>> Mixing valve open >> Alarm buzzer Factory setting Lowest value Highest value >> General alarm Table 129 Pump speed at no demand >>> Mixing valve close > Circulation pumps 10% 1% 100% >> Heating circuit pump G1 ▶ Set pump speed when there is no demand. A low speed is used to keep the system operating when there is no demand for heat.
SETTINGS 20.8 ADDITIONAL HEAT >> Heat source Factory setting Alternative Additional heat Both/Compressor/Additional heat The additional heat works together with the heat pump to maintain the right heating in the circuits. The additional heat can be selected to work alone. Table 134 Heat source drying See manual for the multi-module for the mixed additional heat operating mode. >> Program settings >>> Flow temperature increase per heating step Factory setting Lowest value Highest value 5.0K 1.0K 10.
SETTINGS > Hot water electric heater >>> Output limitation in compressor mode Factory setting Lowest value Highest value 6.0kW 0.0kW 9.0kW Table 145 Output limitation ▶ Set the output permitted during compressor operation. Under Additional heat, there are also settings for additional electric heat in hot water heaters. >> Acknowledge hot water additional heat Factory setting Alternative No Yes/No Table 153 Additional electric heat, hot water A low value can result in hot water peak failure.
SETTINGS 20.11 ALARMS >> Hysteresis alarm reset Factory setting Lowest value Highest value 1.0K 1.0K 10.0K Table 157 Hysteresis >> Number of warnings before alarm Factory setting Lowest value Highest value 1 1 4 The different alarms that can occur are described in (Chapter 21). Under Alarms there is: • • • • • • Information log Delete information log Alarm log Delete alarm log Alarm history Alarm indication > Information log The number of warnings is calculated during a time period of 180 min.
ALARMS >> Alarm indication room sensor (room controller) If the same alarm is repeated even after manual restart, the unit should be replaced (refers to 4 and 5 flashing alarms). >>> Block alarm indicator lamp Factory setting Alternative Yes No/Yes 21.2 ALARMS Table 167 Block indicator lamp This section includes: ▶ Set if the indicator lamp should be off or not. The setting applies to all room controllers.
ALARMS 21.8 ALARM CATEGORIES The alarms are divided into different categories depending on the type and level of the fault. Alarm category is displayed in the alarm window, alarm log and alarm history. CATEGORIES A-H ARE ALARMS, CATEGORIES I-J ARE WARNINGS/INFORMATION, CATEGORIES K-M ARE WARNINGS, CATEGORY Z IS INFORMATION.
ALARMS Alarm lamp/buzzer: Yes. Alarm lamp/buzzer: Yes. Restart: Acknowledgement is required in category A. Restart: Automatic once the alarm cause has disappeared. 21.10.6 LOW TEMPERATURE COLLECTOR CIRCUIT OUT E2X.T11 21.10.11 HIGH FLOW TEMPERATURE E1X.T1 Function: Warning/alarm is given if the temperature of the collector circuit out is too low. First, a warning is given. If the warning appears several times during a certain time period, the warning transforms into a category A alarm.
ALARMS 21.10.16 SHORT CIRCUIT ON SENSOR E11.T1 FLOW 21.10.22 SHORT CIRCUIT ON SENSOR T3 HOT WATER Function: The alarm is activated when the sensor's value indicates a temperature higher than 110 °C. The flow temperature T1 becomes identical to T8. If there are several heat pumps installed, T1 = T8 for the heat pump that does not produce hot water and has the highest value on T8. Additional heat mixing valve shut.
ALARMS Category: H. Alarm lamp/buzzer: Yes. the highest temperature permitted for T8. The warning is blocked during hot water peaks or extra hot water. Restart: Automatic once the alarm cause has disappeared. Reset condition: The warning is deactivated when the sensor temperature falls sufficiently. 21.10.28 SHORT CIRCUIT ON SENSOR E2X.T9 HEAT TRANSFER FLUID IN Category: K. Function: Activated when the sensor's value indicates a temperature higher than 110 °C.
ALARMS Alarm lamp/buzzer: No. Information Comment/Value Restart: Automatic once the alarm cause has disappeared. T2 Out Current outdoor temperature Hot water Calculated hot water temperature 21.10.39 CHECK CONNECTION TO I/O BOARD X Hot water set point value Function: Depends on the board. T5 Room Current value if room controller exists Reset condition: Communication with the board is re-established.
FACTORY SETTINGS 21.13.8 TEMPORARY HOT WATER STOP DUE TO WORKING AREA LIMITS 21.13.5 LOW TEMPERATURE COLLECTOR CIRCUIT OUT E2X.T11 Function: The information is given if the temperature of the collector circuit out is too low. First, a information is given. If the information appears several times during a certain time period, the warning transforms into a category A alarm. For settings of T11: (Chapter 20.9).
FACTORY SETTINGS Room temperature Circuit 2, 3...
FACTORY SETTINGS Installer General Anti-seizure mode Day of the week Start time Highest permitted flow temperature T1 Radiator/Underfloor F value Access level Wednesday 12:00 1 1 80/45 °C 1 1 Operating mode No 15s 1 1 Display light switch off delay 5 min 1 Time for reset of access level 20 min 1 (Start-up) 1 Groundwater Groundwater Compressor start delay groundwater Heat pump x capacity Connected I/O boards Shows which circuit boards are connected and their program version 1 Compre
ENVIRONMENTAL PROTECTION Safety functions Setting collector circuit in T10 F value Access level Lowest permitted temperature E21.T10 -6,0 °C 4,0 °CGroundwater 1 Lowest permitted temperature E22.T10 -6,0 °C 4,0 °CGroundwater 1 1.0K 1 1 1 Lowest permitted temperature E21.T11 -8,0 °C 2,0 °CGroundwater 1 Lowest permitted temperature E22.
MAINTENANCE 24 MAINTENANCE 25 DANGER: Risk of electric shock! ▶ Switch off the main power supply before starting work on the electrical part. We recommend that a function check be performed regularly by a competent person. ▶ Only use genuine spare parts! ▶ Refer to the spare parts list when ordering spare parts. ▶ Always renew seals and O-rings removed during servicing or repair work.
COMMISSIONING PROCEDURE GREENSTORE 26 COMMISSIONING PROCEDURE GREENSTORE Customer/responsible for installation: Installer of installation: Heat pump type: Serial number: Commissioning date: Date of manufacture: Type of collector: Total length of collector: Other components in the installation: Additional heat Room controller T5 Water heater Exhaust air collector 3-way valve Hot water sensor T3 Flow line sensor heating circuit 2 E12.
BENCHMARK LOG BOOK 27 BENCHMARK LOG BOOK GROUND SOURCE HEAT PUMP COMMISSIONING CHECKLIST This Commissioning Checklist is to be completed in full by the competent person who commissioned the heat pump and associated equipment as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
BENCHMARK LOG BOOK Service Record It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed. Service Provider Before completing the appropriate Service Interval Record below, please ensure you have carried out the service as described in the manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing controls.
WORCESTER, BOSCH GROUP: Worcester, Bosch Group Cotswold Way, Warndon, Worcester WR4 9SW. Tel. 0844 892 9900 Worcester, Bosch Group is a brand name of Bosch Thermotechnology Ltd. worcester-bosch.co.