Installation Manual

6 720 608 542
26
Installation instructions
B Operate all other gas appliances on the same gas
piping system at maximum output.
B Record lowest operating gas pressure reading in
table 14.
Gas pressures lower than 3.5" W.C. for Natural Gas or
8" W.C. for LPG will result in insufficient degree rise to
the hot water being used, reduced hot water volume,
possible error code faults and must be corrected. See
Gas Connections, chapter 3.8, page 21.
Fig. 35 Gas pressure test port (left tapping)
Static Gas Pressure Reading (see Chapter 3.12)
enter here: ___________________ Date: ___________
Operating Gas Pressure Reading (see Chapter 3.12)
enter here: ___________________ Date: ___________
Table 14