Submittal Sheet

Bosch Thermotechnology Corp. reserves the right to make changes without notice due
to continuing engineering and technological advances |
BTC 741008301 E | 10.2014
Tel: 1-866-642-3198 Fax: 1-603-965-7581 www.bosch-climate.us
Engineering Submittal Sheet
C1210ESC
Tankless Water Heater
Bosch Thermotechnology Corp.
Londonderry, NH • Ft. Lauderdale, FL
Engineering Speci cations
remote communications if the wireless module is installed.
The controls shall include extensive self-diagnostic capabilities
that incorporate a minimum of 18 separate fault codes and 8
programmable system categories.
The water heater comes equipped with power cord and shall
operate on 120V/1/60Hz electrical service.
INSTALLATION
All aspects of installation of Water Heater Plant shall be in strict
accordance with manufacturer’s instructions. Materials shall
conform to all manufacturer’s recommendations including a
manufacturer listed vent system.
Water heater plant piping shall be eld constructed of materials
as speci ed. Water heater shall be installed with individually
isolating shutoff valves for service and maintenance, and a hot
water hose connection for eld testing. Unit shall have an ASME
approved temperature/pressure relief valve with a setting of 150
psig. Water heater shall require a minimum gas pressure of 3.5"
W.C. (Natural Gas) at 1,000 scfh (full load rated capacity).
MODE OF OPERATION
Heater shall include integral factory wired operating controls
to control all operation and energy input. Control of discharge
water temperature shall be set through an internal setpoint with
a eld adjustment of 100°F to 180°F. Heater shall be capable of
maintaining the outlet temperature within an accuracy of ±2°F*.
This shall be accomplished by modulation of ring rate from
100% to 11% of rated input. Unit shall operate with an Inverse
Ef ciency Curve, with maximum ef ciency achieved at minimum
ring input.
* based on static stability test
CONTROLS INTEROPERABILITY
The control board may be linked to other Bosch tankless water
heaters through the use of a cascading kit. This accessory shall
cause the unit to perform as described above while activating
or deactivating other units in the system. Additional Bosch
tankless water heaters shall be plumbed in parallel and located
near the main unit.
WARRANTY
The heat exchangers shall carry a 5-year limited warranty
against leakage due to defects in materials or workmanship
or corrosion in a commercial installation, subject to the
manufacturer’s water quality requirements. All other parts
and components shall carry a 5 year limited warranty against
defects in materials or workmanship.
2 of 7