Engineering Speci cations
Water heater shall be a Model Therm 830 ES. Plant shall consist
of ___Model Therm 830 ES NG/LP tankless water heaters as
manufactured by Bosch Thermotechnology Corp. Heater shall
be CSA/ANSI Z21.10.3 listed. Heater shall have an input of 175
MBH with a gross output of 147 MBH when red with natural gas.
Unit shall operate with a minimum of 82% ANSI Z-21 ef ciency.
Tankless water heater shall have a recovery of 225 gallons per
hour at a 77°F temperature rise. Tankless water heater shall have
Low NOx emissions and is 2012 SCAQMD NOx certi ed to rule
1146.2.
CONSTRUCTION
Water heater shall be gas red, tankless design with a modulating
power burner and negative pressure gas valve. Burner shall be
capable of 9:1 turndown of ring, without loss of combustion
ef ciency. Primary heat exchanger/combustion chamber shall
incorporate a multi pass copper tube and n design with internal
turbulators. Heat exchanger shall be rated for maximum working
pressure not less than 150 psig. Water heater shall be equipped
with a modulating water valve to improve temperature stability.
Exhaust outlet connector shall be of corrosion resistant metal,
with a 3” diameter ue connection.
The water heater control system shall be a single printed circuit
board in water-resistant plastic enclosure. The entire system
shall be Underwriters Laboratories approved.
The control system shall contain: embedded control board
incorporating LCD display to read temperature, and tactile
buttons for output power, temperature, and programming
control; CPU board which houses all control functions; power
transformer; ignition spark module; and unique connections
for each sensor or component. The control board shall be
eld replaceable. The combustion safeguard/ ame monitoring
system shall utilize spark ignition and a recti cation type ame
sensor. The control panel hardware shall support wireless
remote communications if the wireless module is installed.
The controls shall include extensive self-diagnostic capabilities
that incorporate a minimum of 18 separate fault codes and 8
programmable system categories.