Bosch IDS BVA Product Specifi cations
12.2016 | Bosch Thermotechnology Corp.Data subject to change
5 Blower Data
Air ow performance
Airfl ow performance data is based on cooling performance with a coil and no fi lter
in place. Check the performance table for appropriate unit size selection. External
static pressure should stay within the minimum and maximum limits shown in the
table below in order to ensure proper operation of both cooling,
heating, and electric heating operation.
Air Handler Model Size Motor Speed
SCFM
External Static Pressure-Inches W.C.[kPa]
0.1[.02] 0.2[. 05]
0.3[.07] 0.4[.10] 0.5[.12] 0.6[.15] 0.7[.17] 0.8[.20]
24
Tap(5)
SCFM
1016 955 914
870 827 790 741 691 657
Watts
139
146 157
165 174 185 195 202 209
Tap(4)
SCFM
955
892 853
804 768 729 671 630 ---
Watts 118 125 135 142 152 162
169
178 ---
Tap(3)
-Default Setting
SCFM 927 829 789 739 701 643
597
--- ---
Watts
109
105 113 121
131 137
147
--- ---
Tap(2)
SCFM
887
766 671 631
567 522
465
--- ---
Watts 97 87
83 93
99 108 112 --- ---
Tap(1)
SCFM 829 698
547 366
347 277 234 --- ---
Watts
81 71 60 54 60 64 72
--- ---
36
Tap(5)
SCFM
1452 1403 1343 1287 1214 1144 1085
1022 968
Watts
253 264
271 284 296 303
313 324 329
Tap(4)
-Default Setting
SCFM
1255 1203
1150 1062 995 920
854 797 719
Watts 170 182 193
201 212 221
229 239 244
Tap(3)
SCFM 1109 1050 985
897 841 841
766 702 617
Watts 126 136
147
154 164 170 180 187 195
Tap(2)
SCFM 1020 907
818
733 673 586 520 --- ---
Watts 103
98
109 114 124 129 139 --- ---
Tap(1)
SCFM 962
807
627 551 450 380 296 --- ---
Watts
90
80 71 79 83 93
96 --- ---
48
Tap(5)
SCFM
2072
2013 1935 1923 1878 1830
1783 1736 1688
Watts
447 464 489 497 514 530
545 558 570
Tap(4)
SCFM
1860 1816 1735 1679 1640 1591
1542 1504 1481
Watts 348 364 383 395 408 418 429 451 463
Tap(3)
-Default Setting
SCFM 1702 1651 1560 1547 1497 1438 1385 1331 1280
Watts 268 281
304 312 325 337 349 361 375
Tap(2)
SCFM 1393 1358
1179 1155 1139 1074 1020 964 896
Watts 227 234 258 269 270 283 296 313 325
Tap(1)
SCFM 1365 1239 1078 1050 965 904 886 831 797
Watts 220 226
243 264 269 281 293 301 317
60
Tap(5)
SCFM 2054 2015
1947 1928 1886 1846 1804 1742 1654
Watts 470 495 518 528 542 553 569 567 548
Tap(4)
-Default Setting
SCFM 1883 1840 1783 1754 1712 1670 1622 1579 1541
Watts 367 388 411 420 422
445 454 466 479
Tap(3)
SCFM 1721 1674 1582 1566 1528
1484 1443 1401 1345
Watts 289
305 327 330 341
353 365 378 387
Tap(2)
SCFM 1515
1463 1386 1358 1308
1262 1215 1153 1073
Watts
205
218 235 239 251 263 276 285 301
Tap(1)
SCFM
1337
1265 1156 1148 1095 984 955 963 789
Watts
145 157 173 178 186 197 212 225 235
Table 3
- Bold outlined areas represent airfl ow outside of the required 300-450 cfm/ton range.
SCFM means Standard Cubic Foot per Minute.
Airfl ow based upon Air Handler Unit operating at 230V with no electric
heater kit and no fi lter. Airfl ow at 208V is approximately the same as
230V.