Outdoor Kit Installation Manual
6 720 645 551
Measuring carbon dioxide (CO2)
13
8 Measuring carbon dioxide (CO
2
)
Note: After installation of the outdoor vent cap,
measuring CO
2
for proper levels is recommended
before operating the appliance. See water heater
installation manual for details.
B To measure CO
2
on this appliance, a test port is
available under the louvered grill on the front of the
outdoor vent cap.
B To access test port, remove two screws on either
side of the louvered grill.
B Pull louvered grill free from vent cap.
B Insert combustion gas analyzer probe approximately
4 inches straight into test port. Do not slope probe
up or down.
B Confirm CO
2
is within proper range specified in the
water heater installation manual. Refer to water
heater installation manual if any adjustment is
necessary.
B When measuring is complete, replace louvered grill
with screws.
Fig. 23
1 Test port
Warning: Outdoor vent cap will get
very hot during operation.
B Ensure the vent cap is cool before
performing the procedure below.