8.3 Adding Refrigerant
In North America, the standard pipe length is 7.5m (25’). The additional refrigerant
to be charged can be calculated using the following formula:
Additional refrigerant per pipe length
Connective Pipe Air Purging Additional Refrigerant
< Standard pipe length Vacuum Pump N/A
> Standard pipe length Vacuum Pump
Liquid Side: Ø 6.35 (ø 0.25”)
Inverter R410A:
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oZ/ft
Liquid Side: Ø 9.52 (ø 0.375”)
Inverter R410A:
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
Table 8
CAUTION: CONTAINS REFRIGERANT
NEVER mix refrigerant types.