Installation Guide

16
|
Bosch Climate 5000 Series Wall Mounted Ductless Single Split Air Conditioner / Heat Pump Installation Manual
03.2019 | Bosch Thermotechnology Corp.
Data subject to change
6 Outdoor Unit Installation
Step 1: Select installation location
Before installing the outdoor unit, you must choose an appropriate location. The
following are standards that will help you choose an appropriate location for the
unit.
Proper installation locations meet the following standards:
Meets all spatial minimum requirements shown in Installation Space
Requirements ( Figure 17)
Figure 17
evoba )ni42
(
mc
0
6
60cm (24in)
on right
30cm (12in)
on left
200cm (79in)
in front
30cm (12in)
fr
om b
a
ck wall
Good air circulation and ventilation
Firm and solid—the location can support the unit and will not vibrate
Noise from the unit will not disturb others
Protected from prolonged periods of direct sunlight or rain
DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets
Near a public street, crowded areas, or where noise from the unit
will disturb others
Near animals or plants that will be harmed by hot air discharge
Near any source of combustible gas
In a location that is exposed to large amounts of dust
In a location exposed to excessive amounts of salty air
NOTICE
If the unit is exposed to heavy wind: Install unit so that air
outlet fan is at a 90° angle to the direction of the wind. If
needed, build a barrier in front of the unit to protect it from
extremely heavy winds. See Figures 18 and 19.
Figure 18
Strong wind
Strong wind
Figure 19
Strong
wind
Wind Baffle
NOTICE
If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit it to protect it from the
rain or snow. Be careful not to obstruct air flow around
the unit.
This unit is not designed for application in areas frequently
exposed to salty air (seaside) conditions..