Installation Guide
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 9
Bosch Thermotechnology Corp. | 05.2019
Data subject to change
5 Specifi cations
Number of units that can be used together Connected units 2-5 units
Compressor stop/start frequency Stop time 3 min or more
Power source voltage
Voltage fl uctuation within ±10% of rated voltage
Voltage drop during start within ±15% of rated voltage
Interval unbalance within ±3% of rated voltage
Table 3
2 Zone System 3 Zone System 4 Zone System 5 Zone System
Model
BMS500-AAM018-1CSXRA
BMS500-AAM018-1CSXHB
BMS500-AAM027-1CSXRA
BMS500-AAM027-1CSXHB
BMS500-AAM036-1CSXRA
BMS500-AAM036-1CSXHB
BMS500-AAM048-1CSXRA
Max. equivalent length for all indoor units 131ft / 40m 197ft / 60m 262ft / 80m 262ft / 80m
Max. length to farthest indoor unit 82ft / 25m 98ft / 30m 115ft / 35m 115ft / 35m
Max. height diff erence between indoor and
outdoor unit
49ft / 15m 49ft / 15m 49ft / 15m 49ft / 15m
Max. height diff erence between indoor units 33ft / 10m 33ft / 10m 33ft / 10m 33ft / 10m
Refrigerant precharge (total pipe length) 49ft / 15m 74ft / 23m 98ft / 30m 123ft / 37m
Additional refrigerant charge
Liquid side: 1/4in - 0.16oz/ft Liquid side: 1/4in - 0.16oz/ft
Liquid side: 1/4in - 0.16oz/ft
Liquid side: 3/8in - 0.32oz/ft
Liquid side: 1/4in - 0.16oz/ft
Liquid side: 3/8in - 0.32oz/ft
Table 4 Refrigerant pipe requirements
When installing multiple indoor units with a single outdoor unit, ensure that the
length of the refrigerant pipe and the drop height between the indoor and outdoor
units meet the requirements illustrated in the following diagram (indoor units
may be located above or below the outdoor unit as long as they meet these height
diff erence requirements):
Figure 3
33 ft (10 m)
or less
Indoor unit
Indoor unit
Outdoor unit
49 ft (15m)
or less
Max.Height difference