Installation Guide

Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 11
Bosch Thermotechnology Corp. | 05.2019
Data subject to change
Split type outdoor unit mounting dimensions
Outdoor Model
Outdoor Unit
Dimensions mm (in.)
W x H x D
Mounting Dimensions
mm (in.)
Distance A Distance B
BMS500-AAM018-1CSXRA
845x702x363
(33.27x27.6x14.3)
540
(21.26)
350
(13.8)
BMS500-AAM027-1CSXRA,
BMS500-AAM027-1CSXHB,
BMS500-AAM036-1CSXRA,
BMS500-AAM036-1CSXHB
946x810x410
(37.24x31.9x16.14)
673
(26.5)
403
(15.87)
BMS500-AAM036-1CSXHB,
BMS500-AAM048-1CSXRA
952x1333x415
(37.5x52.5x16.34)
634
(24.96)
404
(15.9)
Table 5
Figure 7
Split Type Outdoor Unit
H
W
W
H
A
B
D
Series installation
The relations between H, A and L are as follows:
LA
L ≤ H
L ≤ 1/2H
9.8in / 25 cm or more
1/2H < L ≤ H 11.8in / 30 cm or more
L > H Can not be installed
Table 6
Figure 8
L
H
A
59in /
150 cm
or more
9.8in /
25cm
or more
9.8in /
25cm
or more
23.6in /
60 cm
or more
118in / 300cm or more
The minimum distance between the outdoor unit and walls described
in the installation guide does not apply to airtight rooms. Be sure to keep
the unit unobstructed in at least two of the three directions (M, N, P)
(See Fig. 9)
Figure 9
M
N
P
11.8 in / 30 cm
from back wall
23.6 in / 60 cm
on right
11.8 in / 30 cm
on left
78 in / 200 cm
in front
23.6 in / 60 cm above