Installation Manual
6 720 644 930
16
Installation instructions
Fig. 17 Vertical venting installation (single pipe pene-
tration)
Warning: Single pipe penetration should be used
in non-freezing climates only!
Fig. 18 Vertical venting installation (twin pipe penetra-
tion)
Fig. 19 Vertical venting installation - Masonry Chim-
ney (combustion air piping not shown)
3.3.4 Vent connections
B Attach the flue gas exhaust accessory (8 705 504
151) to the top of the unit (position 1) using the 4
screws and gasket provided. Fully insert stainless
steel vent pipe 1.5” minimum into the accessory and
tighten the clamp (position 2).
FIRESTOP SUPPORT
ELBOW
APPLIANCE
HOSE
CLAMP
RAINCAP
STORMCOLLAR
FLASHING
FIRESTOP SUPPORT
4"MIN.
AIRSPACE
6720608158-91.2Av
CONDENSATE
DRAIN
2'MIN.
10'MIN.
3'MIN.
i
If using the 4” vent, a 3” to 4” increaser is
required immediately off the top of the
heater.
i
NOTE: Vent pipe must be completely ver-
tical when inserting or gasket inside ex-
haust accessory can become displaced.
Exhaust accessory can be removed with
vent pipe attached to check gasket posi-
tion.
CHIMNEY
MORTAR
HANGERSTRAP
HORIZONTAL RUN
1/4"RISE/FT
ELBOW
APPLIANCE
MAY BEINSULATED
IFNECESSARY
6720608158-14.2AL
HOSE
CLAMP
ELBOW
RAINCAP
STORMCOLLAR
SILICONESEAL
FLASHING
CONDENSATE
DRAIN
2'MIN.
10'MIN.
3'MIN.