Installation Manual

6 720 644 930
32
Installation instructions
3.13 Measuring gas pressure
Confirm gas pressure upon installation.
Connecting manometer
B Shut off gas supply at installer supplied shutoff valve
for this water heater.
B Remove front cover and locate inlet gas pressure
measuring point (see Fig. 42).
B Loosen screw inside left test point fitting (do not
remove) and connect manometer tube to test point.
Remove screw completely if correct size tapping is
available.
Static Pressure Test
B Turn gas supply back on.
B Record static gas pressure reading in table 23.
Operating Pressure Test
B Press ON/OFF button to turn off the appliance.
B Press and hold "Program" (P) button and press ON/
OFF button to turn appliance ON.
Fig. 41
B As soon as '188' is displayed, release "Program"
, button and the display should read P2.
B Press or until P1 appears.
Note: While in this mode the appliance will run
constantly at maximum power and allow
maximum water flow.
For inlet gas pressure adjustment consider the
following table:
B Turn on high volume of hot water flow (at least 6
gpm) and heater will ignite. If heater display reverts to
P2, open more hot water fixtures to allow sufficient
flow. Press until P1 reappears on display.
B Operate all other gas appliances (except this heater)
on same gas piping system at maximum output.
B Record lowest operating gas pressure reading in
table 23.
Gas pressures lower than 3.5" W.C. for Natural Gas or
8" W.C. for LPG will result in insufficient degree rise to
the hot water being used, reduced hot water volume,
possible error code faults and must be corrected. See
Gas Connections, chapter 3.8, page 25.
P1 fan speed:
Factory default: NG: 48, LP: 46
Lowering P1 fan speed reduces the maximum BTU
input.
As a temporary measure if the gas pressure in P1 is
below specification, lower P1 fan speed incrementally
until minimum inlet gas pressure reaches specified
range (table 22). After upgrading gas line, reset
appliance to P1 factory default setting (NG: 48, LP: 46)
or setting from Section 3.3.7.
Fig. 42 Gas pressure test port (left tapping)
Gas type NG LPG
p
in
3.5” WC 8” WC
Table 22 Minimum inlet gas pressure under full operation
Static Gas Pressure Reading (see Chapter 3.13)
enter here: ___________________ Date: ___________
Operating Gas Pressure Reading (see Chapter 3.13)
enter here: ___________________ Date: ___________
Table 23