Installation Instructions

Wiring label
This equipment should be installed in accordance with the NFPA 70 (National Electrical Code), the NFPA 72
(National Fire Alarm Code), and the local authority having jurisdiction. Depending on the application, the installation
is to be in accordance with one or more of the following UL standards:
UL681 Installation and Classification of Mercantile and Bank Burglar Alarm Systems;
UL1076 Proprietary Burglar Alarm Systems and Units; UL1641 Installation and
Classification of Residential Burglar Alarm Systems. Printed information describing proper installation,
operation, testing, maintenance, repair service and response to an alarm is to be provided with this equipment.
Warning: Owner's Instruction Notice (P/N: F01U287181): Not to be removed by anyone except occupant.
Avertissement : guide de l'utilisateur (réf. : F01U287181) : seul l'occupant est autorisé à le retirer.
B5512/B4512/B3512
Bosch Security Systems, Inc. recommends testing the entire system
at least once a week, and having a qualified technician check
the system at a minimum of once every 3 years.
Suitable for the following applications: 1) Household Burglar Alarm System Units. 2) Household Fire Warning System Units. 3) Police Station connect, Mercantile Premise alarm system,
Mercantile Safe and Vault alarm system. For all Police Station applications, Model D8108A Attack Resistant Enclosure with a UL Listed local sounding device
is required. 4) Local, Mercantile Premise alarm system and Mercantile Safe and Vault alarm system. 5) Central Station, suitable as a dual signal line transmission system.
6) Proprietary Burg. 7) Holdup Alarm Units and System.
This equipment has been type tested and found to comply with the specifications in Part 15 of FCC rules for Class B Computing Devices. Operation is subject to the two following
conditions (1) this device may not cause any interference, and (2) this device must accept any interference received including interference that may cause undesired operation.
POWER SUPPLY REQUIREMENTS
The Power Supply provides a maximum of 800 mA for the Control Panel
and all Accessory Devices.
All external connections are inherently power limited, Class 2.
Requirements for battery standby time might reduce allowable output.
THIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS.
THE TOTAL DELAY (CONTROL PANEL PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60 SECONDS.
NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
WARNING
Circuit (point)
Control panel
delay, seconds
Smoke detector
Include detector data or the following or equivalent statement: “Use the delay (power-up/start-up) time marked
on the installation wiring diagram of the smoke detector or on the installed smoke detector(s).
Model
Delay, seconds
This equipment should be installed in accordance with the
CSA C22.1, Canadian Electrical Code, Part 1, Safety Standard
for Electrical Installations.
B5512_B4512_B3512_ULLD-04
Communication:
Standard Line Security: Cellular or IP
A4: Cellular or IP
P3: DACT
CAUTION! AVERTISSMENT!
Avoid damage to Panel.
Do not connect 24 V to terminals.
Pout éviter d’emdommager la centrale :
Ne pas raccorder l’alimentation électrique
de volts aux bornes.
Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2010
UL Listed and Classified control unit Model B5512, B4512 or B3512;
UL Listed and Classified keypad Model B915, B920, B921C, B930, B942, or B942W
UL Listed Local Bell
Model number B430 complies with Part 68, FCC Rules. FCC Registration Number: ESVAL00BB430 Ringer Eq 0.0B
Model number B430 complies with CS-03, IC Rules, IC: 1249A-B430
REN 0.0
Optional B440/B441/B442/B443 - Or - Optional B430
GND OUT
Interconnect Connector
P1
P1
P1
OUTPUT A (C terminal) = AUX PWR
GND OUT
OUTPUT A (C terminal) = COM
OUTPUT A (C terminal) = dry contact
GND OUT
P1
BATTERY POSITIVE ONLY
BATTERY NEGATIVE ONLY
Do not connect to a
receptacle controlled by
a switch. Do not share
with other equipment.
B5512/B4512/B3512
uses a CX4010 UL Listed
Class 2 Transformer
18 VAC 22 VA 60 HZ,
or in Canada, an
ICP-TR1822-CAN
Plug-in Transformer
120 VAC primary,
18 VAC 22 VA secondary.
Incorrect wiring
might damage
this equipment.
Maximum charging current is 1 A auxiliary power at 12 VDC.
BATTERY: Replace every 3 to 5 years with one or two
D126 or one D1218 12 V Lead Acid Batteries for Burglary or
Combination Fire and Burglary Systems.
WARNING! ATTENTION!
Multi-Battery installation requires Model D122
or D122L Dual Battery Harness.
Improper installation can be a fire hazard.
Le installations à plusieurs batteries nécessitent un
faisceau de câbles de Batterie double de modèle
D122 ou D122L. Toute installation inadéquate peut
causer un risque d’incedie.
For UL Listed fire alarm
applications, use a
D192G Notification
Appliance Circuit module.
SDI2 keypads,
input and
output
modules,
communicators,
and wireless
receivers.
Supervised Loops
Open 3.7 to 5.0 VDC
Normal 2.0 to 3.0 VDC
Short 0.0 to 1.3 VDC
1 k
EOL Resistor
(P/N:15093130-004)
Required at End of Line. Typical Initiating Devices
are are Door Contacts NO/NC, Floor Mats, Motion
Detectors, Glass Break Detectors, etc.
EOL
D134 Dual
Relay Module
N/O 1
N/C 1
X1 +
X1 -
N/O 2
N/C 2
X2 +
X2 -
COMM 1
COMM 2
ICP-EZTS
Tamper
Switch
For a list of 2-wire smoke
detectors compatible with
the D125B Dual Class B
Initiating Module, refer to
the D125B Installation
Instructions
(P/N: F01U036340).
For a list of 2-wire smoke
detectors compatible with
the B201, refer to
the B201 Installation
Guide
(P/N: F01U296412).
GND OUT
An EOL power supervision module might be required
for use with 4-wire smoke detectors.
(Optional)
Auxilliary Powered Devices 11.5 to 12.4 VDC. Below 10.2 VDC,
the B5512/B4512/B3512 stops processing Loop inputs.
ATTENTION!
CETTE UNITÉ COMPREND UNE FONCTIONNALITÉ DE VÉRIFICATION DES ALARMES QUI CONDUIT À UN RETARD DU SIGNAL D'ALARME DU SYSTÈME PROVENANT DES CIRCUITS
INDIQUÉS. LA RETARD TOTAL (CENTRALE + DÉTECTEURS DE FUMÉE) NE DOIT PAS DÉPASSER 60 SECONDES. NE CONNECTER AUCUN AUTRE DÉTECTEUR DE FUMÉE À CES
CIRCUITS, SAUF SI CELA EST PERMIS PAR LES RÉGLEMENTATIONS LOCALES EN VIGUEUR
F01U287186-09
7.9
Control Panels System wiring diagrams | en 45