Control Panels B5512/B4512 en UL Installation Instructions
Control Panels Table of Contents | en 3 Table of contents 1 Introduction 4 1.1 About documentation 4 1.1.1 Related documentation 4 1.2 Bosch Security Systems, Inc. product manufacturing dates 5 2 System overview 6 3 Control panel installation 7 3.1 Install the enclosure and wiring label 7 3.2 Install the control panel 7 3.2.1 Mount the control panel 7 3.2.2 Connect earth ground 9 3.2.3 Configure OUTPUT A using the jumper 3.
en | Introduction Control Panels 1 Introduction 1.1 About documentation This document contains instructions for a trained installer to properly install, configure, and operate this control panel, and all optional peripheral devices. Review this document before beginning the installation to determine the hardware and wiring requirements for the features used. Throughout this document, the words “control panel” refer to both control panels (B5512 and B4512).
Control Panels Introduction | en 7. 5 Under Search Results, click the desired product. The product page opens with the Documents tab selected. 8. Click en to the right of the desired document. Call Bosch Security Systems, Inc., Technical Support (1-800-289-0096) if you need additional assistance.
2 en | Introduction Control Panels System overview B920/B930 Use Two-line Alphanumeric and ATM Style Alphanumeric keypads to operate the control panel by area. B5512 control panels support up to 4 areas. B4512 control panels support up to 2 areas. Each area can have its own account number or you can group together areas with a common account number. B208 Octo-input modules allow the addition of up to 8 input devices. B810 RADION receiver SDs connect RADION wireless devices to the control panel.
Control Panels Introduction | en 3 Control panel installation 3.1 Install the enclosure and wiring label 7 Refer to Enclosures to determine if the application requires a specific enclosure. To install the enclosure: 1. Remove any knockouts prior to installing the control panel. 2. Mount the enclosure in the desired location. Use all enclosure mounting holes. Refer to the mounting instructions supplied with the selected enclosure. 3. i Pull the wires into the enclosure.
en | Introduction Control Panels Figure 3.2: B10 and B11 control panel placement locations 1 ᅳ B10 Medium Control Panel Enclosure 2 ᅳ B11 Small Control Panel Enclosure 3 ᅳ Mounting clip locations for the B5512/B4512 2. Snap the four supplied plastic standoffs onto four enclosure support posts. If using the B12 Mounting Plate for D8103 Enclosure, attach the standoffs to the plate support posts. Do not attach the standoffs with screws at this time. Figure 3.3: Standoff attachment 3.
Control Panels 3.2.2 Introduction | en 9 Connect earth ground To help prevent damage from electrostatic discharges or other transient electrical surges, connect the system to earth ground at the earth ground terminal before making other connections. The icon indicates the earth ground terminal. Use a recommended earth ground reference, such as a grounding rod or a cold water pipe. Notice! i Do not use telephone or electrical ground for the earth ground connection. Use 14 AWG (1.8 mm) to 16 AWG (1.
en | Introduction Control Panels OUTPUT A (C terminal) = AUX PWR P1 COM AUX OUTPUT A (C terminal) = COM P1 COM AUX OUTPUT A (C terminal) = DRY P1 COM AUX COMMUNICATION MODULE 1 ETHERNET ETHERNET 100BASE-T LINK USB RESET P1 ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.
Control Panels Introduction | en 11 Using interconnect wiring Interconnect wiring connectors parallel the SDI2 PWR, A, B, and COM terminals on the terminal strip. In installations with multiple SDI2 modules, using interconnect wiring makes the installation quicker and easier than using terminal strip wiring. You use any combination of terminal and interconnect wiring to wire multiple modules in parallel, but do not wire a single module to the control panel using both terminal and interconnect wiring.
en | Introduction Control Panels Install the transformer 4.1.1 Caution! ! Do not short-circuit the terminals of the transformer: Shorting the terminals opens the internal fuse, causing permanent failure. Connect the transformer to the 18 VAC terminals of the control panel before plugging it into the power source. Notice! i Plan ahead Route telephone, SDI2 bus wiring, and sensor loop wiring away from any AC conductors, including the transformer wire.
Control Panels Introduction | en 3. 13 Connect the black battery lead to the BAT- terminal, and then to the negative (-) side of the battery. 4. Connect the red battery lead to the BAT+ terminal, and then to the positive (+) side of the battery. Warning! High current arcs are possible. The positive (red) battery lead and the BAT+ terminal can create high current arcs if shorted to other terminals or the enclosure. Use caution when working with the positive lead and BAT+.
en | Introduction Control Panels Callout ᅳ Description 6 ᅳ 12 V sealed lead-acid rechargeable battery (D126/D1218) 7 ᅳ Sensor loop wires Charge the battery Connect the battery and then the transformer to allow the control panel to charge the battery while you complete the installation. Battery maintenance 4.2.2 Use sealed lead-acid rechargeable battery (12.0 VDC, 7 Ah or 12.0 VDC, 18 Ah). The control panel supports up to 18 Ah of battery. If you use two D126 (12.
Control Panels Introduction | en 15 Recharge cycle AC ON - Battery charging begins and AC Restoral Reports sent. 13.4 V - Battery Restoral Report sent. Battery float charged. Further information Refer to Powered outputs, page 18. B520 Auxiliary Power Supply 4.3 The optional B520 Auxiliary Power Supply Module provides up to 2 A of 12 VDC standby power for Fire and Burglar applications.
en | Introduction 4.3.4 Control Panels Installation and control panel wiring (B520) The power supply draws approximately 15 mA (+/- 1 mA) from the control panel. Ensure that there is enough power for the module and other powered devices you want connected to the system. Refer to On-board outputs, page 18. Caution! ! Always power down the control panel and B520 when connecting modules, relays, or other wiring.
Control Panels Introduction | en 17 Wire to the control panel When wiring a module to a control panel, use the terminal strip labeled with PWR, A, B, and COM for SDI2 IN to wire to terminals labeled PWR, A, B, and COM on the control panel. Use 12 AWG to 22 AWG (2 mm to 0.65 mm) wire.
en | Introduction Control Panels Callout ᅳ Description 1 ᅳ B520 Auxiliary Power Supply Module 2 ᅳ Powered device (SDI2 module) 3 ᅳ Terminal strip wiring 4 ᅳ Interconnect wiring (P/N: F01U079745) Wire to batteries Wiring the B520 to BATT 1 is required for proper operation of standby power for the B520 module. Wiring the second battery (BATT 2) is optional. If a control panel is configured for two batteries as the standby power source, then BATT 2 is also required for proper operation.
Control Panels i 5.1.2 Introduction | en 19 Notice! UL requires any device powered from a power output to be supervised. Total available power The control panel produces up to 800 mA of combined power at 12.0 VDC nominal to power peripheral devices. The outputs listed below and OUTPUT A share the available power. AUX terminal (auxiliary power) AUX Powers devices requiring continuous power (for example, motion detectors).
en | Introduction Control Panels 1 COMMUNICATION MODULE 1 ETHERNET 100BASE-T ETHERNET 20 LINK OUTPUT A Jumper Under Cover USB 1k AUX OUTPUT A - 12 V + BATTERY C OUTPUT B End of Line Resistors 1 COM 2 3 COM 4 5 COM 6 7 COM 8 C B OUTPUT ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.
Control Panels Introduction | en Callout ᅳ Description Callout ᅳ Description 6 ᅳ Yellow LINK LED 16 ᅳ SDI2 terminals (power and data) 7 ᅳ Plug-in module retention clip 17 ᅳ Auxiliary power terminals 8 ᅳ On-board Ethernet connector 18 ᅳ Terminals for Output A 9 ᅳ USB connector 19 ᅳ Battery terminals 10 ᅳ Heartbeat LED (blue) 20 ᅳ 18 VAC power input terminals 7 System wiring diagrams 7.
en | Introduction Control Panels MODULE 1 Y X MODULE RELEASE COMMUNICATION MODULE 1 ETHERNET ETHERNET 100BASE-T 1 14 LINK OUTPUT A Jumper Under Cover ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.
Control Panels Introduction | en 7.2 23 Battery lead supervision wiring COMMUNICATION MODULE 1 4 ETHERNET ETHERNET 100BASE-T LINK OUTPUT A Jumper Under Cover OUTPUT A BAT 2- CHGR- BAT 2+ VAUX+ BAT 1- SUPV BAT 1+ CHGR+ ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.
en | Introduction Control Panels 1 2 COMMUNICATION MODULE 1 ETHERNET ETHERNET 100BASE-T LINK USB SDI2 Device Bus R Y G B ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.0 - 13 VDC 1k AUX OUTPUT A - 12 V + 18 VAC 18VAC + BAT - NO C NC COM AUX R Y PWR A OUTPUT A G B B COM C OUTPUT B End of Line Resistors 1 COM 2 3 COM 4 5 COM 6 7 COM 8 1 5 7 COM 2 3 COM 4 COM 6 COM 4 AUX PWR ALARM TRIG 3 COM SUPV IN ALARM CKT Figure 7.
Control Panels 7.4 Introduction | en 25 Keyswitch wiring 2 1 6 7 3 3 5 5 4 4 Figure 7.4: Keyswitch wiring Callout ᅳ Description 1 ᅳ Maintained keyswitch 2 ᅳ Momentary keyswitch 3 ᅳ Common 4 ᅳ Point input 5 ᅳ 1 kΩ resistor (P/N: 4998143839) 6 ᅳ Open on a circuit arms the area 7 ᅳ Short on a circuit toggles the arming state Keyswitches are not intended for use in UL listed systems. UL Installation Instructions 2013.
en | Introduction 7.5 Control Panels SDI2 devices general system wiring COMMUNICATION MODULE 1 ETHERNET ETHERNET 100BASE-T LINK OUTPUT A Jumper Under Cover ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.
Control Panels Introduction | en 27 You can configure modules via home run, daisy chain, or single level T-tap anywhere on the SDI2 bus. 1 COMMUNICATION MODULE 1 ETHERNET ETHERNET 100BASE-T LINK OUTPUT A Jumper Under Cover ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.
en | Introduction Control Panels Maximum cable lengths The following rules must be followed when wiring the SDI2 bus. – The SDI2 bus requires the use of un-shielded cable from 12 AWG to 22 AWG. – SDI2 devices or keypads must be within 2000 ft (610 m) of the control panel.
Control Panels AWG Introduction | en MFG/PN 16 Belden Capacitance Resistance pF/ft Ω/1000 ft Max Run 19.9 4.0 7000 23.5 4.2 5800 32 1.56 4400 NEC Type 29 Definition HC2758 Belden 5202 12 Belden 5002 Table 7.2: Maximum cable length i Notice! Fire alarm applications require NEC cable type FPLR, FPLP, or FPL or the equivalent power limited fire alarm cables (refer to article 760 of the NFPA 70 code). UL Installation Instructions 2013.
7.6 en | Introduction Control Panels Wiring label 2013.
Control Panels 8 Introduction | en 31 Specifications Control panel power supply specifications Voltage Input (Power Primary 18 VAC Supply) terminals 18 VAC 22 VA Class 2 transformer (CX4010) Secondary BAT terminals 12 Volt Sealed Lead Acid Rechargeable Battery (D126 or D1218) Current Control Panel: Idle 125 mA; Alarm 155 mA Requirements Refer to the Standby battery requirements and calculations section in the Control Panels (B5512/B4512) Installation and System Reference Guide (P/N: F01U26544
en | Introduction Control Panels Point Thresholds On-board points Open - 3.7 to 5.0 VDC 1 to 8 Normal - 2.0 to 3.0 VDC Short - 0.0 to 1.3 VDC Short circuit current - 5 mA Compatible B10 Medium Control Panel Enclosure, B11 Small Control Panel Enclosure, D2203 Enclosures Enclosure, D8103 Universal Enclosure, D8108A Attack Resistant Enclosure, and D8109 Fire Enclosure 8.
Control Panels Introduction | en OUTPUT B Output B OUTPUT C Output C 33 22 AWG min (up to 12 AWG max) UL Installation Instructions 2013.
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450 USA www.boschsecurity.com © Bosch Security Systems, Inc.