Installation Manual

Table Of Contents
Point Source selections
Unassigned Output
Octo-input Keypad
Wireless IP Camera*
On-board
*The B426, B3512, and the ā€œEā€ variants do not support IP cameras.
Point Index selections
Assign a Point Index to a point by selecting the Point Index number. The tables below show the Point Index
number and default configuration for each Point Index. You must use RPS to configure the Point Index
parameters..
Point Indexes (point profiles) 1 through 8
Point Index Text defaults (the second language text defaults are blank):
Point Index Number Default Text (first language)
Point Index 1 24-hr Instant on Open/Short
Point Index 2 24-hr Invisible/Sil on Short
Point Index 3 Pull Station
Point Index 4 Smoke Detector
Point Index 5 Smoke Detector w/Verification
Point Index 6 Bell Supervision - D192G
Point Index 7 Part On: Instant
Point Index 8 Part On: Delay
Point Index Number 1 2 3 4 5 6 7 8
Point Index Text
(1st language)
24-hr
Instant
24-hr
Invisible/
Pull
Station
Smoke
Detector
Smoke
Detector
Bell
Supervisi
Part On:
Instant
Part On:
Delay
Point Index Text
(2nd language)
(blank) (blank) (blank) (blank) (blank) (blank) (blank) (blank)
Point Type / Response /
Circuit Style
24 Hour 24 Hour Fire
Point
Fire
Point
Fire
Point
24 Hour Part On Part On
Entry Delay _(30)_ _(30)_ _(30)_ _(30)_ _(30)_ _(30)_ _(30)_ _(30)_
Entry Tone Off Y/N Y/N Y/N Y/N Y/N Y/N Y/N Y/N
Silent Bell Y/N Y/N Y/N Y/N Y/N Y/N Y/N Y/N
Ring Until Restored Y/N Y/N Y/N Y/N Y/N Y/N Y/N Y/N
Audible After Two Fails Y/N Y/N Y/N Y/N Y/N Y/N Y/N Y/N
Invisible Point Y/N Y/N Y/N Y/N Y/N Y/N Y/N Y/N
Buzz on Fault __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ __(0)__
Control Panel Keypad Installer menu | en 127
Bosch Security Systems, Inc. Installation and System Reference Guide 2016.05 | 14 | F.01U.287.180