Installation Manual

Table Of Contents
2-wire smoke wiring (D125B)
CCD 0x
-
0xxxx -
000
© RADIONICS INC.
D125B
1992
1
SWITCH
POWER
10
EARTH
GND
2
ZONE
B
4 5
PANEL
COMMON
3
ZONE
A
6
B-
LOOP
7
A-
LOOP
8
B+
LOOP
9
A+
LOOP
R21
R9
R10
R14
R11
R12
R22
RV2
RV3
RV4
R8
RV1
TB1/J1
R3
C1
R7
C3
C2
R13
R4
R5
R6
U1
PTC2
PTC1
R1
R2
D125B
1
2
3
4, 5
7, 9
6, 8
or
5
UX PWR
11
10
10
Figure 18.4: D125B to control panel wiring (B5512 shown)
Callout Description Callout Description
1 Switched auxiliary power from the control panel’s
Output A (NC)
1
7 Supervised smoke detector to A LOOP negative
2 Connection from an on-board point on the control
panel to Zone B
8 Supervised smoke detector to B LOOP positive
3 Connection from an on-board point on the control
panel to Zone A
9 Supervised smoke detector to A LOOP positive
4/5 Connection to the control panel’s common (one
connection only)
10 Earth ground
6 Supervised smoke detector to B LOOP negative 11 Output A jumper (under cover) set to AUX PWR
1
You can also use Output B or C in conjunction with a D133 or D134 relay module.
Notification appliance circuit wiring
The control panel does not have an onboard NAC. Use a D192G Notification Appliance Circuit
Module for systems requiring a NAC.
Programming determines the output format and the conditions that activate the output. One
self-resetting circuit breaker protects against shorts. When using the output to activate
notification appliance circuits in UL Listed fire alarm applications, install a D192G Notification
Appliance Circuit module.
Refer to the D192G Notification Appliance Circuit Module Installation Guide (P/N: 4998122260)
for detailed wiring information and specifications.
18.4
18.5
86 en | System wiring diagrams Control Panel
2016.05 | 14 | F.01U.287.180 Installation and System Reference Guide Bosch Security Systems, Inc.