Installation Manual

Table Of Contents
7. Press [ENTER] while viewing the desired format to select it and save the programming.
8. When the keypad shows Parameter Saved, escape from the menu.
B93x/B94x keypads configuration of Phone Format
1. Enter the installer passcode, and then open the [1] Installer menu.
2. Go to [1] Program > [1] Reporting > [1] Phone menu. The keypad shows the phone
number for the phone destination.
3. Use
/[PREV] or /[NEXT] to go to the destination you want to edit.
4. Press [Format] to view and edit the phone format, and then press [Edit] to edit the
phone format.
5. Press the icon or softkey for the desired format.
6. Press [Save] to save the programming.
7. When the keypad shows Parameter Saved, escape from the menu.
[1] Reporting > [2] Network menu parameters
Enhanced communications is the ability to communicate by some means other than a standard
digital dialer. The control panel can include four separate enhanced communication
destinations to which the control panel can route events. In this menu, you can enable
enhanced communication and edit the network address, network address, poll rate, and port
number for each destination (D1, D2, D3, and D4).
D1 Network address __________________________ Poll rate ___________ Port number _______
D2 Network address __________________________ Poll rate ___________ Port number _______
D3 Network address __________________________ Poll rate ___________ Port number _______
D4 Network address __________________________ Poll rate ___________ Port number _______
Enhanced Comm
B91x/B92x keypads configuration of Enhanced Comm
1. Enter the installer passcode, and then open the [1] Installer menu.
2. Go to [1] Program > [1] Reporting > [2] Network > [1] Enhanced Comm. The keypad
shows the Enhanced Comm option as well as the current default value.
3. Press [ENTER] to view and change the enhanced comm options.
4. Use [PREV] or [NEXT] to toggle between the Yes and No options.
5. Press [ENTER] while viewing the desired option to save the programming.
6. When the keypad shows Parameter Saved, escape from the menu.
B93x/B94x keypads configuration of Enhanced Comm
1. Enter the installer passcode, and then open the [1] Installer menu.
2. Go to [1] Program > [1] Reporting > [2] Network > [1] Enhanced Comm menu. The
keypad shows the Enhanced Comm option as well as the current default value.
3. Press [Enhanced Comm] to view and change the enhanced comm options, and then press
[Edit] to edit the enhanced communication option.
4. Press the icon or softkey for the desired option.
5. Press [Save] to save the programming.
6. When the keypad shows Parameter Saved, escape from the menu.
Network Address
20.1.2
110 en | Keypad Installer menu Control Panel
2016.05 | 14 | F.01U.287.180 Installation and System Reference Guide Bosch Security Systems, Inc.