F01U029847-01.book Page 2 Thursday, March 1, 2007 9:27 AM 2 en | Legal F220 Series Detectors with F220-B6RS Bases 1 Legal 1.1 Trademarks CleanMe® is a registered trademark of GE Interlogix in the United States and/or other countries. Chamber Check® is a registered trademark of Bosch Security Systems, Inc. in the United States. Chambermaid™ is a trademark of Bosch Security Systems, Inc. in the United States. ENVI-RO-TECH™ is a trademark of Tech Spray L.P.
F01U029847-01.book Page 3 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases General Information | en 3 use a can of clean, dry compressed air (such as TECHSPRAY ENVI-RO-TECH Duster) which is available at office and alarm supply stores. Shorten the plastic tube that comes with the compressed air to about 2 in. (5 cm). Place the tube or needle valve through the Chambermaid valve in the bottom of the detector (refer to Figure 2.2 on page 6). i 2 NOTE! Do not paint the detectors.
F01U029847-01.book Page 4 Thursday, March 1, 2007 9:27 AM 4 en | General Information F220 Series Detectors with F220-B6RS Bases manufacturer’s installation instructions for proper end-of-line (EOL) resistor selection. 2.1.2 Base Features 13 12 11 10 14 12 15 8 13 9 7 13 3 4 2 5 12 O N 1 D I 2 P 3 4 1 6 12 13 1. Terminal 1 9. 2. Terminal 2 10. Tamper Tab (Locking Bar) 3. Terminal 3 11. Tamper Tab (Locking Bar 4. Terminal 4 5. Terminal 5 12. Alignment Key (4 places) 6.
F01U029847-01.book Page 5 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases 2.2 General Information | en 5 F220 Series Detectors 2.2.1 About F220 Series Detector Heads The F220 Series Detector Heads listed inTable 2.1 each require an F220-B6 Series Base. ! WARNING! The F220-PTHC detects carbon monoxide (CO) as a component of a fire. Do not use the F220-PTHC as a stand-alone CO detector.
F01U029847-01.book Page 6 Thursday, March 1, 2007 9:27 AM 6 en | General Information 2.2.2 F220 Series Detectors with F220-B6RS Bases F220 Series Detector Features 1 5 2 6 4 3 1. Front of detector 2. Light-emitting diode (LED) 5. Back of detector Thermistor Chambermaid location 3. 4. 6. Unlocking port (heat detectors only) Fig. 2.2 2.2.3 Detector Features F220 Series Heat Detector Heads The F220 Heat Detector Heads can be identified by color coding (refer to Table 2.2).
F01U029847-01.book Page 7 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases 2.2.4 General Information | en 7 F220 Series Smoke Detector Heads The F220 Series Smoke Detector Heads are UL Listed, openarea photoelectric smoke detectors that work with commercial fire protective signaling systems and household fire warning systems. Select the appropriate mounting base to configure the detectors for two-wire or four-wire versions (refer to Section 2.
F01U029847-01.book Page 8 Thursday, March 1, 2007 9:27 AM 8 en | Install the Bases 2.3.2 F220 Series Detectors with F220-B6RS Bases Base Specifications Alarm Current (only base current, detector current excluded) F220-B6RS (with 45 mA at 24 VDC steady sounder and 50 mA maximum at 30 VDC relay): F220-B6RS (with 30 mA at 24 VDC separately powered 35 mA maximum at 30 VDC sounder only): NAC Current 30 mA at 24 VDC Standby Current 10 mA maximum at 30 VDC Voltage 10.0 VDC to 30.0 VDC Table 2.4 2.3.
F01U029847-01.book Page 9 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases Install the Bases | en 9 Power Supervision Base can be used as the last base on a loop in four-wire systems to provide power supervision. i NOTE! Follow NFPA 72 guidelines for mounting locations. For commercial and industrial installations, 30 ft (9 m) spacing between smoke detectors is recommended. 1. Release the mounting skirt from the mounting base.
F01U029847-01.book Page 10 Thursday, March 1, 2007 9:27 AM 10 en | Install the Bases 3.2 F220 Series Detectors with F220-B6RS Bases Wire the Bases CAUTION! When wiring bases, all terminal screws ! 3.2.1 including those not wired must be tightened to prevent loose screw heads from making intermitent electrical contact with the detector head. Terminal Connections WARNING! Do not twist or loop the wires around the terminals.
F01U029847-01.book Page 11 Thursday, March 1, 2007 9:27 AM Install the Bases | en 11 F220 Series Detectors with F220-B6RS Bases 3.2.4 Four-wire Loop Termination One D275 End-of-Line Module (refer to Figure 3.5 on page 19) or F220-B6E Power Supervision Base (refer to Figure 3.4 on page 18) is required for each loop when using four-wire bases. 3.
F01U029847-01.book Page 12 Thursday, March 1, 2007 9:27 AM 12 en | Install the Bases 3.4.1 F220 Series Detectors with F220-B6RS Bases NAC Configurations In these configurations, the sounders are controlled and powered from the control panel’s NAC power circuit or a remote NAC power circuit. The positive (+) wire from the NAC or D132B Multi-use Reversing Relay Module connects to Terminal 5 and the negative (-) wire connects to Terminal 4 (refer to Figure 3.2, Item 3 on page 14).
F01U029847-01.book Page 13 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases 3.4.2 Install the Bases | en 13 Local Configurations In these configurations, the sounders are controlled and powered from the control panel’s power circuit (refer to Figure 3.2, Items 1 and 2 on page 14). The initiating device circuit (IDC) wires connect to Terminals 1 and 2 (refer to Figure 3.2, Items 3 and 4 on page 14).
F01U029847-01.book Page 14 Thursday, March 1, 2007 9:27 AM 14 en | Install the Bases F220 Series Detectors with F220-B6RS Bases 1 _ _ + + 1 F220-B6RS b2 b1 4 4 4 5 1. 3 + _ 2 + _ C 3 2 + _ 3 + _ 2 powers the sounders from and negative (-) resetta- the control panel so that ble auxiliary power input all sounders follow the from the control panel or control panel’s NAC set- base. 3. 5 NO Base Power: positive (+) from a previous four-wire 2. 1 a1/a2 c ting. 4.
F01U029847-01.book Page 15 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases Install the Bases | en 15 Position 1 and 2 on; Sounder output configured for steady 3 and 4 either both on signal (continuous tone) or both off. O N 1 D I P 2 3 4 Position 1, 2, and 3 on; Sounder output configured for 4 off. Temporal Code 3 signal O N 1 D I P 2 3 4 Position 1, 2, and 4 on; Sounder output configured for March 3 off. Time signal O N 1 D I P 2 3 4 Table 3.
F.01U.029.847 | -01 | 2007.
F01U029847-01.book Page 17 Thursday, March 1, 2007 9:27 AM Install the Bases | en 17 F220 Series Detectors with F220-B6RS Bases 1. 2. Positive (+) and negative Supervision Base or a (-) resettable auxiliary D275 Power Supervision power either in parallel Module. originating from the same 4. When connecting a D275, power supply or run from connect the positive (+) separate power supplies.
F01U029847-01.book Page 18 Thursday, March 1, 2007 9:27 AM 18 en | Install the Bases F220 Series Detectors with F220-B6RS Bases _ 1 + 4 b2 b1 F220-B6E* C 4 5 NO 3 5 2 1. 2. a1/a2 c C 2 NO 1 6 3 + _ Power input (positive [+] previous four-wire base. in on terminal b2; negative 3. Jumper connecting [-] in on terminal a1/a2) terminals 2 and 3. from the control panel or 4. Place an appropriate EOL from a previous four-wire resistor (refer to the base.
F01U029847-01.book Page 19 Thursday, March 1, 2007 9:27 AM Install the Bases | en 19 F220 Series Detectors with F220-B6RS Bases The alarm loop relay (Form A, Terminals 1 and 2) and the power supervision relay (Terminal 3 and 4) are rated for 0.5 A at 120 VAC/DC for resistive loads. ! 3.5.2 CAUTION! Do not connect relays to inductive or capacitive loads. Use with resistive loads only.
F01U029847-01.book Page 20 Thursday, March 1, 2007 9:27 AM 20 en | Install the Detector Heads F220 Series Detectors with F220-B6RS Bases 4 Install the Detector Heads 4.1 Mount the Detector Heads CAUTION! Before mounting detector heads, all terminal i ! i 4.1.1 screws in the base including those not wired must be tightened to prevent loose screw heads from making intermitent electrical contact with the detector head.
F01U029847-01.book Page 21 Thursday, March 1, 2007 9:27 AM Install the Detector Heads | en 21 F220 Series Detectors with F220-B6RS Bases CAUTION! When using the locking bar, before installing ! 4.1.2 the detector head, open the unlocking port (refer to Figure 4.2, Item 4) by poking through the plastic with a screwdriver. Mounting Skirt (Figure 4.2, Item 2) Align the four alignment keys (refer to Figure 2.2, Item 12 on page 6 and to Figure 4.
F01U029847-01.book Page 22 Thursday, March 1, 2007 9:27 AM 22 en | Install the Detector Heads 4.1.3 ! F220 Series Detectors with F220-B6RS Bases Detector Head CAUTION! The mounting skirts and detector heads are keyed. Do not force them onto the mounting bases. Install: Install the detector head by lining up the LED on the detector head (refer to Figure 4.2, Item 6 on page 21) with the bar on the mounting skirt (refer to Figure 4.2, Item 7).
F01U029847-01.book Page 23 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases 4.2 Install the Detector Heads | en 23 Set Detector Modes The F220 Series Smoke Detectors feature a unique magnet-operated sensitivity mode and detector test mode. 4.2.1 Test Mode Test the detector by placing the magnet next to the T mark on the mounting skirt for three consecutive flashes to cause an alarm. 4.2.
F01U029847-01.book Page 24 Thursday, March 1, 2007 9:27 AM 24 en | Install the Detector Heads 4.3 F220 Series Detectors with F220-B6RS Bases Set CleanMe Feature The Clean Me feature monitors the smoke chamber’s sensitivity and sends a trouble signal to the control panel when the sensitivity degrades to a preset level. i NOTE! When a CleanMe signal is sent to a control panel that is not CleanMe compatible, the signal may be misinterprted as an alarm. To activate the CleanMe feature: 1.
F01U029847-01.book Page 25 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases Test the Installation | en 25 be met by visually inspecting the detector and checking the flash rate of the LED. NOTE! Perform the visual check before resetting power. i After a reset the trouble indicators clear for 70 seconds. After 70 seconds, if the detector is in a trouble condition, trouble indications begin again.
F01U029847-01.book Page 26 Thursday, March 1, 2007 9:27 AM 26 en | Test the Installation 9. F220 Series Detectors with F220-B6RS Bases When the system is alarm free, check each detector to ensure that the green LED indicator flashes approximately every eight seconds. This verifies the detector is receiving power and operating properly. NOTE! If a heat detector LED flashes at a rate of i 4 flashes/sec, the detector is either cold (below +32°F [0°C]), out of sensitivity range, or defective.
F01U029847-01.book Page 27 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases 5.3 Test the Installation | en 27 Test the Alarm Loop Checkthe voltage across the EOL resistor of each alarm loop to verify wiring losses do not exceed control panel manufacturer’s specifications. 5.4 Test any CO Sensors Removing the detector head or resetting the detector’s power places the detector in a special test mode for 15 minutes.
F01U029847-01.book Page 28 Thursday, March 1, 2007 9:27 AM Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450-9199 USA Customer Service: (800) 289-0096 Technical Support: (888) 886-6189 www.boschsecurity.us © Bosch Security Systems, Inc.