Access Control Interface Module D9210B Operation and Installation Guide
D9210B D9210B Operation and Installation Guide 32206G Page 2 © 2002 Bosch Security Systems
D9210B Contents 1.0 1.1 1.2 1.3 1.3.1 1.3.2 1.4 1.5 2.0 2.1 2.1.1 2.1.1.1 2.1.1.2 2.1.1.3 2.1.1.4 2.2 2.3 2.3.1 2.3.2 2.4 2.5 2.6 2.6.1 2.6.2 3.0 3.1 3.2 3.2.1 3.2.2 3.2.3 3.2.3.1 3.2.3.2 3.2.3.3 3.2.4 3.2.5 3.2.6 3.2.7 3.2.8 3.2.9 3.2.10 3.2.11 3.2.12 3.2.13 4.0 4.1 5.0 Introduction........................................................................................................................................................................................... 5 Manual Organization .................
D9210B Contents 5.1 LED Troubleshooting .......................................................................................................................................................25 Appendix A: D9210B Terminal Quick Reference and Electrical Specifications .............................................................. 27 Figures Figure 1: D9210B Access Control Interface Module................................................................................................................
D9210B Introduction 1.0 Introduction This document assumes that you have basic security system installation skills such as measuring voltages, stripping wire, making proper wire connections, and checking phone lines. It also assumes you are familiar with the proper installation of Bosch Security Systems Control/Communicator panels and the related programming tasks. The material and instructions in this document have been carefully checked for accuracy and are presumed to be reliable.
D9210B Introduction 1.3.2 Tips, Important Notes, Cautions and Warnings Throughout this document, helpful tips, important notes, cautions and warnings will be presented for the reader to keep in mind. These appear different from the rest of the text as follows; Important Notes - should be heeded for successful operation and programming. Also tips and shortcuts may be included here. Caution - These caution the operator that physical damage to the program and/or equipment may occur.
D9210B D9210B Overview 2.0 D9210B Overview 2.1 System Description 2.1.1 Operational Primer The D9210B is a fully supervised, addressable SDI bus device that allows access control integration for the D9412 (8 doors) and D7412 (2 doors) panels. Each D9210B can store up to 986 user tokens (300 tokens for D7412), each with a different access level for each door.
D9210B D9210B Overview When the door is held open past the normal door sequence time, an extended door sequence time is initiated. This extended time extends the shunt and re-activates the buzzer. If programmed, CLOSE DOOR # will display at the control center assigned to the door. The normal door sequence will not activate if the interlock point is in an off normal (open or short) condition. The Interlock Point can be assigned to multiple door controllers.
D9210B D9210B Overview 2.2 Physical Overview • • • • • Terminal Blocks. The D9210B comes with three banks of terminal blocks for connecting the D9210B to its power source, the panel and associated readers and relays. Relay. A removable (model D136) relay provides a dry contact single pull, double throw output. Dipswitch. The D9210B dipswitch has six on-off switch settings. Setting these switches allows each unique D9210B to be programmed for a specific address.
D9210B D9210B Overview 2.3.2 2.4 • Four door states: Locked, Unlocked, Secured, Fire Unlock. • Disarm states using a token • Pre-warn for holding door open too long • Disarm system before or after a door opens • Automatic Unlock door on disarm, Locked Door when armed • Optional Deactivate strike when the door opened • Interlock point assignment to prevent access until interlock point is normal.
D9210B D9210B Overview 2.5 Ordered Separately The D9210B Door Controller can be used with the Bosch Security Systems D7412 (supports 2 doors) or D9412 (supports 8 doors) Control/Communicator security panels and associated control keypads and access control readers. Following are the available options. • D9210BLC: The D9210BLC (up to 4) can be installed in the same enclosure as the control panel using the mounting screws and fasteners. Two additional modules can be mounted using the D136 brackets.
D9210B D9210B Overview 2.6 Listings and Approval Information 2.6.1 Underwriters Laboratories (UL) The D9210B, when used with the D7412 or D9412 panels, is listed by UL for use as part of an Access Control System; Local, Police-Connect, Central Station, or Proprietary Burglar Alarm System; and a Commercial Fire Alarm System. In addition to the manual, refer to the D7412/D9412 installation documentation regarding Burglar Alarm Grades and Fire Alarm services supported.
D9210B Installation 3.0 Installation Thank you for choosing our product. We have made an effort to identify the key steps for installing the D9210B successfully. To ensure that your installation goes smoothly, follow the installation steps in the order presented. 3.1 System Planning Before proceeding, draw your system layout on a sheet of graph paper. Also, review the architect and engineering drawings (if available). This will help you set addresses, mark the units, and route/tag wires.
D9210B Installation 3.2.2 Pulling and Marking the Wires Running wire. Use Table 4 to estimate the wire bundle size for your knockouts and where to mount the D9210B. Tag your wire runs to prevent confusion during installation and troubleshooting. Figure 2 shows the wiring for a typical D9210B installation. Purpose Power/SDI data Suggested Wire Tag Tag A Approximate Diameter 0.25 in. (6.4 mm) Recommended Wire Type 4/22 AWG quad (2500 ft. / 762 m) 4/18 AWG quad (5000 ft.
D9210B Installation Strike and D9210B CAUTION 12 VDC AUX Power Supply UL Listed for Fire DO NOT power the D9210B Module with 24 VDC.
D9210B Installation 3.2.3 Mounting Do not install or replace a D9210B while it is connected to live power circuits. The D9210B should be powered down until it is ready to be tested. 3.2.3.1 D9210BLC 1. Mount the D8103, D8109 or D8108A enclosure on a flat service. 2. Install another D9210LC to the mounting skirt (optional) prior to step 3. 3. Hang the mounting skirt in the enclosure by aligning the rectangular tabs of the enclosure with the rectangular knockouts on the mounting skirt. 4.
D9210B Installation 3.2.5 Door Lock, Terminals 2, 3 and 4 Description. A removable relay (model D136) provides a dry contact single pull double throw output. Some strikes require a closed circuit to unlock the door while others require an open circuit to unlock the door. The relay will support 12 VDC @ 2A or 24 VDC @ 2.5 A or 12/24 VAC @ 40 A (See Table 6). State Common Input (3) Lock N/C (2) Lock N/O (4) Description For 12/24 VDC strikes, provide the input power here from the power supply.
D9210B Installation 3.2.9 Connecting the Card Reader, Terminals 12, 14, 15, 16, 17, and 18 Description. These terminals provide connection for a standard 26-bit Wiegand reader. Compatible Readers: Table 7 specifies the UL listed Wiegand readers and associated tokens that are compatible with the D9210B. Bosch Security Systems guarantees only these readers will function properly and only the readers noted below can be used in UL certified systems.
D9210B Installation 3.2.10 Setting the Dipswitch and Tagging the Unit The D9412 panel supports up to eight door controllers using all eight address settings. The D7412 supports up to two door controllers using the first two address settings. Each D9210B uses one of eight addresses. Addresses can not be duplicated. Because the D9210B is always supervised, two D9210B modules having the same address will not function and SDI failures will occur. Fill out the Program Record Sheet.
D9210B Installation 3.2.11 Connecting Power and SDI, Terminals 1, 3, 5, 6, and 7 Do not connect 24 VDC or non-isolated [from the strike] 12/24 VAC of the D9210B. Reference Figure 5 for the following connections. Terminal 1, Pwr +12 VDC IN. The red wire provides power to the D9210B, 12 VDC readers and buzzers. Terminal 3, LCKCOM. For 12/24 VDC strikes provide the input power here from the power supply. Terminal 5, Common. The black conductor provides electrical common between the D9210B and the power source.
D9210B Installation To activate the D9210B, follow the instructions in the D9210B Program Entry Guide (P/N:32207). Use the ACCESS Program Record Sheet to match the door to the proper address and to ensure that the door is assigned to the proper area. 3.2.13 Step 13: Testing the D9210B Description. The D9210B comes shipped with a default program that will let you run a quick test upon installing the unit. Go through the following items to verify the D9210B is functioning properly.
D9210B Installation Notes: D9210B Operation and Installation Guide 32206G Page 22 © 2002 Bosch Security Systems
D9210B Operation 4.0 Operation 4.1 Door Release Application The D9210B can be used for door release functions. When used in this configuration, the strike relay contacts must be supervised. This can be accomplished with the use of an end-of-line relay commonly used for smoke detectors. Connecting the D9210B for this application is shown in Figure 6. Program Point Index in the POINTS handler as Supervisory with Point Response as [A] Supervisory on Open and Trouble on Short.
D9210B Operation Notes: D9210B Operation and Installation Guide 32206G Page 24 © 2002 Bosch Security Systems
D9210B Troubleshooting 5.0 Troubleshooting 5.1 LED Troubleshooting Use the following reader and D9210B LED patterns to troubleshoot the D9210B. It is important to use the Door Control function to validate actual door states when troubleshooting.
D9210B Troubleshooting Notes: D9210B Operation and Installation Guide 32206G Page 26 © 2002 Bosch Security Systems
D9210B Appendix A: D9210B Terminal Quick Reference and Electrical Specifications Appendix A: D9210B Terminal Quick Reference and Electrical Specifications Terminal 1 PWR + Description 12 VDC power input 2 LCK N/C Continuity with LCK COM when relay is off. • 12/24 V @ 2.0 A max (30 VDC max) 3 LCK COM 4 LCK N/O Input to feed LCK N/C (T2) and Lock N/O (T3) Continuity with LCK COM when relay is on. • 12/24 V @ 2.
© 2002 Bosch Security Systems 130 Perinton Parkway, Fairport, NY 14450-9199 USA Customer Service: (800) 538-5807; Technical Support: (888) 886-6189 32206G Operation and Installation Guide 10/02 D9210B Page 28 of 28