D9412GV3/D7412GV3 v8.
D9412GV3/D7412GV3 | Program Entry Guide | EN | 2 Documentation Conventions Type Styles Used in this Manual To help identify important items in the text, the following type styles are used: Prompt A thick border is used to indicate a main programming entry as seen in the Remote Programmer’s Display. It is used as a section heading and screen example. Shaded boxes indicate programmer prompts that are only available when Custom or View events are selected.
D9412GV3/D7412GV3 | Program Entry Guide | Table of Contents 1.0 1.1 1.2 1.2.1 1.3 Introduction................................................. 5 Using this Program Entry Guide................... 5 Guide to Programming Options.................... 6 Local Keypad Programming......................... 7 Guide to UL 864 Programming Requirements 9 2.0 Panel and Area Wide Parameters ........... 12 2.1 Phone ........................................................
D9412GV3/D7412GV3 | Program Entry Guide | 6.1 Door Profile .............................................. 140 6.2 Strike Profile............................................. 143 6.3 Event Profile............................................. 145 7.0 SIA CP-01 Quick Reference ................... 147 Programming Prompts Directory....................... 148 Figures Figure 1: EN | 4 Table 25: Table 26: Table 27: Table 28: Table 29: Table 30: D1255 Keypad Programming Menu and Page References...................
D9412GV3/D7412GV3 | Program Entry Guide | 1.0 Using this Program Entry Guide This guide is only for programming the D9412GV3 and D7412GV3 Control Panels. Although this guide specifically refers to the D9412GV3 Control Panels, it can be used for programming the D7412GV3 Control Panels. Differences between the D9412GV3 and D7412GV3 are shown in Table 1 on page 5.
D9412GV3/D7412GV3 | Program Entry Guide | 1.0 1.2 Introduction EN | 6 Guide to Programming Options Full configuration of the control panel is only achieved through use of the Remote Programming Software (RPS). A limited keypad programmer’s mode is available to modify some of the more commonly changed parameters. This guide is set up in a specific order. Related program entries are grouped together in modules as they appear in RPS. This guide shows the programming options for each programming prompt.
D9412GV3/D7412GV3 | Program Entry Guide | 1.0 1.2.1 Introduction EN | 7 Local Keypad Programming GV3 now offers a Local Keypad Programming menu with the Service Passcode only. It includes all custom options. For a list of program items you can set using Keypad Programming, refer to Figure 1 on page 7 and Figure 2 on page 8. To access the Keypad Programming menu, the Keypad Programming option must be set to P (refer to Section 2.10.
D9412GV3/D7412GV3 | Program Entry Guide | 1.0 Introduction EN | 8 Figure 2: D1260 Keypad Programming Menu and Page References Refer to Phone # on page 12. Refer to Phone # Format on page 13. Refer to Enhanced Comm on pages 130 to 132. Refer to R# Primary Device on page 18 and R# Backup Device on page 19. Refer to RPS Passcode on page 32. Refer to RPS Phone # on page 34. Refer to RPS IP Address # on page 129. Refer to RPS Port Number on page 129.
D9412GV3/D7412GV3 | Program Entry Guide | 1.0 1.3 Introduction EN | 9 Guide to UL 864 Programming Requirements This section identifies the programming requirements you must make in order to comply with UL 864 Commercial Fire applications. NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES This product incorporates field-programmable software.
D9412GV3/D7412GV3 | Program Entry Guide | 1.
D9412GV3/D7412GV3 | Program Entry Guide | 1.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 2.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 If you program the primary phone number with a sequence to temporarily disable Call Waiting (typically *70 pause, but verify with the phone service provider) followed by the phone number, you should program the backup phone number without the Call Waiting cancel sequence. If the subscriber cancels Call Waiting without notifying their alarm installing company, the control panel can still send reports using the backup number.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 2.2 Phone Parameters The program items in this category describe panelwide characteristics for telephone dialing, receiver format, and supervision.
D9412GV3/D7412GV3 | Program Entry Guide | 2.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Phone Supv Time Panel and Area Wide Parameters EN | 16 Buzz on Fail Default: 0 Default: No Selection: 0, 10 to 240 Selection: Yes or No 0 No phone line supervision. Yes 10 to 240 Enter the number of seconds (in 10 sec increments) you wish to wait before indicating trouble. After a faulted phone line restores, it takes the same amount of time to start restoral responses.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Expand Test Report Default: No Selection: Yes or No Yes Off-normal events listed in Routing Group Test Reports are reported to the central station. No Off-normal conditions for the events listed in the Routing Group Test Reports at test time are not reported. Use this program item to add system event information to scheduled Test Reports. Refer to Section 4.2 Schedules (Skeds) on page 114.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 2.3.3 Programming Primary and Backup Destinations Each route number has an R# Primary Device and an R# Backup Device. For example, if two phone numbers are programmed, the R# Primary Device destination is the phone number that the route group attempts to dial first. If the R# Primary Device destination does not connect to the central station receiver after two dialing attempts, the control panel dials the R# Backup Device destination.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 There are four Route Groups which contain a selection of event categorizes and individual events. Each group has a primary and a backup device. The primary device is the first (most important) destination used to reach the programmed route within this group. The backup device is used if the primary device fails. R# Primary Device Default: No Device Selection: No Device, Phone 1..4, SDI ## Path 1..4 Phone 1 Phone 1 is this group’s primary destination.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 R# Backup Device Default: No Device Selection: No Device, Phone 1..4, SDI ## Path 1..4 Phone 1 Phone 1 is this group’s backup destination if the primary destination fails. Phone 2 Phone 2 is this group’s backup destination if the primary destination fails. Phone 3 Phone 3 is this group’s backup destination if the primary destination fails. Phone 4 Phone 4 is this group’s backup destination if the primary destination fails.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 2.3.9 Panel and Area Wide Parameters Route Group Categories Fire Reports To meet UL 864 requirements for Central Station and Remote Station applications, enable Fire Reports. Selecting Yes enables a report to be sent when the event occurs.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Selecting Yes enables a report to be sent when the event occurs.
D9412GV3/D7412GV3 | Program Entry Guide | 2.
D9412GV3/D7412GV3 | Program Entry Guide | 2.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 When activating an on-board relay using remote automation software, the D9412GV3 and D7412GV3 Control Panels log and print the resulting event as: Relay 250 (Relay A) Relay 251 (Relay B) Relay 252 (Relay C) Auto Function Reports The following prompts support customized routing of Auto Function Reports. Selecting Yes enables a report to be sent when the event occurs.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters User Chng Reports Point Reports Selecting Yes enables a report to be sent when the event occurs. Report Selections R# Service Start Yes, No R# Service End Yes, No R# Fire Walk St Yes, No R# Fire Walk End Yes, No R# Walk Test St Yes, No Yes, No R# Extra Point Yes, No R# Send Point 1 Text R# RF Low Bat Yes, No R# RF Low Bat Res Yes, No 1 Yes, No Selecting Yes enables a report to be sent when the event occurs.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Access Reports Selecting Yes enables a report to be sent when the event occurs. Access Granted, No Entry, Request to Enter (RTE) and Request to Exit (REX) Events can be enabled or disabled by each D9210B.
D9412GV3/D7412GV3 | Program Entry Guide | 2.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 2.4 Panel and Area Wide Parameters Power Supervision For the following items to be true, AC Fail/Restoral Report must be programmed as Yes and AC Tag Along must be programmed as No. AC Fail Time Default: 1:00 Selection: 0:01 to 90:00 Program the amount of time that AC power must be off before the control panel responds to the AC failure. The response to restoral of AC power is delayed for the same amount of time. The control panel always monitors AC.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 AC Tag Along is required for NFPA and UL 864 Commercial Fire systems. Be sure to program AC Fail/Restoral Report as No if AC Tag Along is programmed Yes. AC/Battery Buzz No Selection: Yes or No Yes Initiates panel-wide trouble tone at all keypads. No Does not initiate panel-wide trouble tone at keypads Initiates a panel-wide trouble tone at keypads when AC fails or battery is low or missing.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 P## Scope Panel and Area Wide Parameters EN | 31 P## Fire Events Default: No Printer Default: Refer to the program record sheet Selection: No Printer, Area, Account, Panel Wide, Custom Selection: Yes or No Yes Panel Wide Printer prints all designated events that occur panel-wide. A panel-wide printer can cross account boundaries. All events in this group print at assigned printer. No No events in this group print at assigned printer.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 P## Point Event Default: Refer to the program record sheet Selection: Yes or No P## Usr Chng Evt Default: Refer to the program record sheet Selection: Yes or No 2.6 RPS Parameters Use these program items to enable remote programming software (RPS) functions in the control panel using the on-board phone connection or a Network Interface Module. Refer to Section 5.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Keypad Programming of RPS Passcode D1255 1. Refer to Figure 1 on page 7 to access Keypad Programming and navigate to the RPS PASSCODE option. The keypad shows the currently configured passcode. 2. Press [ENT] to change the passcode. An invisible editing cursor is enabled. 3. The [PREV] button acts as a [Backspace] key. The [COMMAND] key allows you to cycle though the special passcode characters (A, B, C, D, E, F); the [NEXT] key selects the passcode character.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters RPS Call Back Default: No Selection: Yes or No Yes When the control panel hears the correct RPS passcode, it hangs up the phone, seizes the phone line, then dials the programmed RPS phone number (refer to the RPS Ph prompt on page 35). This ensures that the control panel only communicates with RPS units connected to the programmed phone number. If the call is answered manually, the call back must be initiated manually.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 RPS Phone # Default: Blank Selection: Blank or up to 24 characters Blank Control panel does not dial a phone number for RPS. 1 to 24 characters Enter up to 24 characters to define dialing characteristics. This is the phone number the control panel dials to contact RPS. Refer to Section 2.6.1 on page 32 for instructions on configuring special phone number digits to detect dial-tone detect and to pause dialing.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 2.7 Miscellaneous Duress Type Panel and Area Wide Parameters EN | 36 Cancel Report Default: No Default: 0 Selection: Yes or No Selection: 0, 1, 2, or 3 Yes Send Cancel and Fire Cancel Reports according to routing. No Do not send Cancel and Fire Cancel Reports. 0 1 Do not send a duress event with any passcode. Increase the last digit by 1 to generate an alarm. For example, if the passcode is 6123, 6124 activates a duress alarm.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Area 1 must be enabled: System events such as power and phone supervision do not send a report correctly if Area 1 is disabled. When programmed No, points assigned to this area do not generate events, show at the keypad when arming and disarming, or send status reports. All user authority in this area is turned off while the area is disabled. To meet UL 864 requirements, set A# Area On to Yes.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Refer to the prompts P## Force Arm Returnable and P## Bypass Returnable in Section 3.2 Point Responses on page 91 for returning a point to the system when the point returns to normal or when the area is disarmed. Users can bypass more points than the number entered here during the disarmed state. It is only when the user attempts to Bypass Arm an area (or areas) that this restriction is enforced.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 When the detector senses smoke or fire, the area’s sensor reset relay interrupts power to points connected to it for the time in Verify Time. Panel and Area Wide Parameters EN | 39 When power restores to the points, the 60-sec confirmation window starts. If any detector, reset during the verification time, experiences another alarm during the confirmation window, an alarm occurs.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 40 A# Area Type Default: Regular Selection: Regular, Master, Associate, or Shared Regular Arms or disarms as an independent area. Master Does not allow arming for this area unless all associate areas with the same A# account number are master exit delay armed or master armed. CHK AREA displays if the associate areas are not armed.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 2.8.2 Shared-Area Characteristics Arming a Shared Area A shared area arms automatically when all associate areas are armed. As soon as the last associate area is armed, the shared area automatically begins its arming sequence. Passcode, key switch, subcontrols, or RPS cannot arm shared areas. To display faulted points at associate areas, the shared and associate areas must have the same account number.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters Select the bell pattern this area uses to signal an alarm on a Fire point. A# Fire Time Default: 6 min Selection: 1 min to 90 min Enter the number of minutes the bell rings for Fire Alarm points. The relay activated for this time is programmed in A# Fire Bell in Area Relays. The bell output begins as soon as the fire alarm occurs. It shuts off the bell when the programmed number of minutes expires.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 A# Single Ring Default: No Selection: Yes or No Yes One bell output per arming period. After one alarm, alarms on any Nonfire points in the same area cannot restart the bell until the armed state changes. An alarm on a different point in same area restarts bell output. No Restart bell output with each alarm event.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 To suppress reports: Use Opening/Closing Windows to suppress reports for a specified period of time and then automatically turn them on again. Use the Restricted O/C options. A Closing Report is sent if the user is force arming, sending duress, or bypass arming. An Opening Report is sent if the user is disarming during an alarm condition or unbypasses points when disarming. If the system is normal, no Opening or Closing Report is sent.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 A# Area O/C Default: Yes Selection: Yes or No Yes No Include the Area # and generate Opening and Closing Reports for this area when it is armed. Do not include the Area # or generate Opening and Closing Reports for this area. Determines if the area number and the account number are reported at arming and disarming. As long as Account O/C is No, the account number sends a report when arming this area individually.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 A# Fail to Close Panel and Area Wide Parameters EN | 46 A# Restrictd O/C Default: No Default: No Selection: Yes or No Selection: Yes or No Yes Fail to Close Report is sent for this area if the area is not armed when the Closing Window stop time occurs. Yes Restrict Opening and Closing Reports for this area. A# Area O/C must be programmed Yes to generate Restricted Opening and Closing Reports. Note: Program an exit delay time in Exit Dly Time.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 A# Perimeter O/C Default: No Selection: Yes or No Yes This area can send Perimeter Opening and Closing Reports. No This area cannot send Perimeter Opening and Closing Reports. This item determines if this area can send Perimeter Instant and Perimeter Delay Closing Reports and normal Opening Reports to the central station. Opening and Closing Windows do not suppress this event. Refer to the L## Perimeter O/C prompt on page 75.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Parameter Setup Requirement: Two Man Rule can be completed only by entering two valid unique passcodes with L## Passcode Disarm authority. Panel and Area Wide Parameters EN | 48 When the first digit of the second code is pressed, the following message appears. As each digit is pressed, an additional asterisk appears.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters Parameter Setup Requirement: To avoid the possibility of false alarms in Associate areas, do not use the A# Exit Restart feature in areas with A# Area Type set to Shared. The Early Ambush timer can be started and stopped only by passcodes with the L## Passcode Disarm authority.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters 2.9 A# Entry Warning EN | 50 Keypad (Command Center) This programming module contains three programming categories: Cmd Cntr Assignment, Area Text, and Custom Function. Default: Yes Selection: Yes or No Yes Pulse the alarm output for the last 10 sec of the Entry Delay time. No Do not pulse the Alarm Bell output during the Entry Delay time.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 CC# Supervised Default: Refer to the program record sheet Selection: Yes or No Yes Only one keypad can be installed for this CC SDI address. No More than one keypad can be installed using this CC SDI address with the same address DIP switch setting. Supervise this SDI address and generate Trouble SDI Reports and local trouble annunciation if a problem occurs with this keypad or the SDI bus.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 52 CC# A1 [through A#] in Scope CC# Scope Default: Refer to the program record sheet Default: Selection: Panel Wide, Custom, No Keypad, Area, and Account Refer to the preceding important note Selection: Yes or No Panel Wide A panel-wide keypad can view information and perform Arming and Disarming functions for all areas in the control panel. A panel-wide keypad can cross account boundaries.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters CC# Enter Key Relay Default: 0 Selection: 0 to 128, A, B, C (0 to 64, A, B, C for the D7412GV3) 0 The [ENTER] key is not used to activate a relay. 1 to 128 (64), A, B, C Assign the relay number that activates when [ENTER] is pressed at this keypad after the user enters a valid passcode. The service passcode cannot be used for the CC# Enter Key Cycle Door application.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 If a door is not programmed for this prompt and a door is not assigned to the area using the D# Entry Area in the Access Control section, 9210 NOT READY appears at this keypad when you attempt to add a user. The message indicates that the control panel cannot start the Add User Mode until a door is assigned to this keypad. Assigning a door to a keypad is not necessary for the user to control the door(s) using the Door Control function.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 For SIA CP-01 Compliance CC# Exit Tone can be set to Yes or No. CC# Arm Now Warning Default: No Selection: Yes or No Yes This keypad activates a tone and displays PLEASE CLOSE NOW. No This keypad does not activate the tone or display PLEASE CLOSE NOW. Panel and Area Wide Parameters CC# Passcode Follows Scope Default: Yes Selection: Yes or No Yes Master Arming allows a user to change the armed state of the areas within the scope of this keypad.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 CC# Scroll Lock Panel and Area Wide Parameters EN | 56 CC# Abort Display Default: No Default: Yes Selection: Yes or No Selection: Yes or No Yes Prevents the idle system status text from scrolling automatically. Requires user intervention to advance. Yes This keypad shows the Alarm Aborted message for all aborted alarms within its scope.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 57 D1260 Series Keypad Area# Is On Default: Refer to the program record sheet Selection: Sixteen alphanumeric characters Enter the text for this area that appears when the area is master armed or master instant armed and other areas sharing the same account number are not yet master armed. This display does not appear when the area is perimeter armed.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters Custom Function Default: 128 Selection: 128 to 143 EN | 58 Figure 3: Softkey Locations on the D1260 Keypad Enter the Custom Function number you want to program. You can program up to sixteen Custom Functions, which are numbered 128 to 143. 1 5 2 6 CF### Text 3 7 4 8 Default: Refer to the program record sheet Selection: Sixteen alphanumeric characters. See Section 2.9.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters 128 to 143 Enable Custom Function 128 through 143 (Menu Function only): This function determines if a passcode is needed to access a Custom Function from the menu list. ENTER PASSCODE (or Enter Passcode + Enter Key on the D1260) appears when this function is passcode protected. If a command within the Custom Function is passcode protected, ENTER PASSCODE appears at the keypad.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 2.10.1 Commands Similar to command initiation used in other Bosch Security Systems, Inc. products, the Commands method provides continuity in the arming commands across product lines and makes an easy transition for dealers using other Bosch Security Systems, Inc. products. With commands, the end user presses [COMMAND] and then the numeral of the command to initiate. For example, [COMMAND][2] arms the perimeter of the area.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Instant arms all perimeter points with point response that starts an instant alarm (refer to P## Pt Response in Section 3.2 Point Responses on page 91) in the area where the keypad is assigned. Entry and exit delays are not provided with this arming function. This function causes a Perimeter Delay point to act as a Perimeter Instant point.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 View Memory Panel and Area Wide Parameters Send Report Default: E Default: P Selection: -, E, or P Selection: -, E, or P Function No. 13 Function Name Function No. 9 EN | 62 Function Name View Event Memory Alternate Keystroke [COMMAND][4][0] Use this function to view prior alarm, trouble, and supervisory activity occurring since the last time the system armed. Event memory is not cleared until the area re-arms.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Change Display Panel and Area Wide Parameters Add User Default: E Default: P Selection: -, E, or P Selection: -, E, or P Function Name Function No. 15 Change Display EN | 63 Alternate Keystroke [COMMAND][4][9] Function Name Function No. 18 Add User Alternate Keystroke [COMMAND][5][6] Use this function to select either a bright or dim display with loud or soft keypad warning tones. You can also choose the time and date display.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 View Log Panel and Area Wide Parameters User Cmd 9 Default: E Default: P Selection: -, E, or P Selection: -, E, or P Function No. 21 Function Name View Log Alternate Keystroke (Menu function only) Use this function to view all of the system events, their time stamps, User IDs, or point numbers. User Name and Point Text are not stored in the event log, but they appear when the control panel matches them with the User ID ### and the Point ###.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Reset Sensors Panel and Area Wide Parameters Move to Area Default: E Default: P Selection: -, E, or P Selection: -, E, or P Function No. 27 Function Name Reset Sensors EN | 65 Alternate Keystroke [COMMAND][4][7] Use this function to activate the Reset Sensors function for Fire or Intrusion points programmed as P## Resettable in Section 3.1 Point Index on page 100. Points within the scope of the keypad where the function is entered reset.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 66 2.10.4 Custom Functions Default Text Default: P Selection: -, E, or P Function No. 34 Function Name Default Text C Function 128 [through 143] Alternate Keystroke [COMMAND][5][7] Determining the armed state of an area using the programmed custom text might be difficult. Use this function to switch temporarily to the control panel default text, shown on the program record sheet.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters Keypad Programming of the Keypad Programming Option D1255 1. Refer to Figure 1 on page 7 to access Keypad Programming and navigate to the DISABLE KP PROG option. Press [ENT]. 2. The current keypad programming configuration shows (for example, ALLOWED: YES). 3. Press [ENT] to change the configuration. The keypad reads PRG ALLOWED: followed by YES or NO. 4.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 68 L## Perimeter Delay L## Master Arm Delay Default: Refer to the program record sheet Default: Refer to the program record sheet Selection: - or E Selection: - or E Function No. 2 Function Name Function No. 5 Function Name Master Arm Delay Alternate Keystroke [COMMAND][1] Perimeter Delay Arm Alternate Keystroke [COMMAND][3] Master arms areas based on the CC# Scope of the keypad using an exit delay time.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 L## View Memory Default: Refer to the program record sheet Selection: - or E Function No. 9 Function Name View Event Memory Panel and Area Wide Parameters To Walk Test a Door point connected to a D9210B Access Interface Module, open the door without activating the door sequence or allowing it to time out past the extended shunt time. L## Fire Test L## View Point Status Default: Refer to the program record sheet Selection: - or E Function No.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 70 L## Cycle Door L## Send Report Default: Refer to the program record sheet Default: Refer to the program record sheet Selection: - or E Selection: - or E Function No. 13 Function Name Send Report Alternate Keystroke [COMMAND][4][1] or [COMMAND][4][2] Send a Test Report from any keypad assigned to an area where the user has authority.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Table 26: L## Secure Door-Door Mode Definitions Door State Lock Door Secure Door Unlock Door Cycle Door Definition Normal Door: When a door is in the Lock Door state, one can initiate the door sequence using Skeds, CYCLE DOOR?, keypad functions, door requests, and valid token or card requests. No Access Allowed: When a door is in the Secure Door state, no access is allowed through the door until it is returned to the Lock Door state.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 L## Add User Panel and Area Wide Parameters EN | 72 L## View Log Default: Refer to the program record sheet Default: Refer to the program record sheet Selection: - or E Selection: - or E Function No. 18 Function Name Function No. 21 Function Name Add User Alternate Keystroke [COMMAND][5][6] Add or change users, add or change authority levels, add or change tokens or cards.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 L## Bypass a Point Refer to the program record sheet Selection: - or E Function Name Bypass a Point Alternate Keystroke [COMMAND][0] Bypass points with this authority level. L## Unbypass a Point Default: Refer to the program record sheet Selection: - or E Function Name Function No. 26 Unbypass a Point EN | 73 L## Move to Area Default: Function No.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 74 Events print locally without alarm annunciation or reporting to the central station receiver. D1255 Keypad displays a sequential count and the text for the point after each point is activated and restored. Default: Refer to the program record sheet Selection: -, or E The D1255 Keypad displays ALL PNTS TESTED.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Custom Functions Default: Refer to the program record sheet Selection: - or E Function Name Enable Custom Function 128 through 143 EN | 75 L## Send Duress L## C Function 128 [through 143] Function No. 128 through 143 Panel and Area Wide Parameters Alternate Keystroke (Menu function only) Default: Refer to the program record sheet Selection: - or E Generates a Duress Report if the area where this authority level is assigned sends duress.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 L## Disarm Level Default: Refer to the program record sheet Selection: I, D, or - I Users change the Master Armed state and Perimeter Armed state to Perimeter Instant. The armed state does not change in other areas, and the armed state does not change if the area is already in the perimeter instant or disarmed state. User needs access level for Master Armed (M) state.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 77 2.10.8 SIA Duress Passcode Options 2.11 USER INTERFACE Authority Levels L## Disarm The Function List is accessed when the user presses [MENU] (or the key corresponding to menu on the D1260) while the keypad shows the idle text. Program as many as 32 M### Function(s).
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 M## CC Address 1 [through 16] Default: Refer to the program record sheet Selection: Yes or No Yes This menu item appears at this keypad address. No This menu item does not appear at this keypad address. Panel and Area Wide Parameters The others report as 001 to 128. The Relay Report is RELAY SET RELAY # rrr when the relay is turned on and RELAY RESET RELAY # rrr when the relay is turned off.
D9412GV3/D7412GV3 | Program Entry Guide | 2.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 80 When sharing one relay to reset sensors in two or more areas, you must program the following. Failure to do so causes TROUBLE PT ### for all point types programmed as P## Resettable. A# Watch Mode CC # Scope must include all areas that share the relay. L## Reset Sensors authority must be assigned to the passcode that activates the COMMAND 47 or Reset Sensor function.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 A# Duress Relay Default: 0 Selection: 0, 1 to 128 for D9412GV3, 1 to 64 for D7412GV3, A, B, or C Activates when a Duress alarm is generated from a keypad assigned to the specified area. Burg Time needs a bell period programmed and A# Duress Enable must be Yes. This relay activates when the Burg Bell starts and deactivates when the Burg Bell time ends. The Burg Bell pattern has no effect on this relay function. Panel and Area Wide Parameters 2.12.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 82 Summary Fire Trouble Comm Fail Default: 0 Default: 0 Selection: 0, 1 to 128 for D9412GV3, 1 to 64 for D7412GV3, A, B, or C Selection: 0, 1 to 128 for D9412GV3, 1 to 64 for D7412GV3, A, B, or C Activates when a control panel cannot communicate a report after making ten attempts to each routing destination. At the same time, COMM FAIL RG displays at the keypad.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 2.1.1 Panel and Area Wide Parameters User Groups When using the Add/Change User function at the keypad, the authority levels and the changes made affect the master user’s passcode and the entire group’s token or cards. For the D9412GV3, there are 249 groups (99 groups for the D7412GV3) consisting of one user with a passcode and token (master) and three users with tokens or cards but not a passcode (sub-user).
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 2.1.6 Panel and Area Wide Parameters EN | 84 Reporting and Logging Phone # Format must be ModemIIIa2 for the following reports sent to the central station. Regardless of the reporting format, they log and print at the local printer as shown in Figure 4. Each sub-user is identified by the master user’s three-digit number plus an extension of 0, 1, 2, or 3. These numbers are called Sub-user ID Codes. shows all the users for User Group 122 as they would appear.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 85 U### User Group User ### Default: 001 Default: 0 Selection: 000 or 001 to 249 (001 to 099 for the D7412GV3) Selection: 0, 1 to 8 Enter the User number you are programming. User 000 is the Service Authority Level (Level 15). You cannot change the programming for user 000. Only the Service Authority Level (User 000) can delete User 000.
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters U### Name Default: Refer to the program record sheet Selection: Sixteen alphanumeric characters Converting hexadecimal to decimal: If your card label contains letters as well as numbers, the number is hexadecimal.* Convert the hexadecimal number to decimal using your calculator. If you cannot convert in this way, use the reader and the Add/Chg User? Function to add the tokens or cards.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 3.0 Points 3.1 Point Index Use the point indexes to construct personality types for points used in the system. The Index numbers are used in Point Assignments. Each unique point index number determines the control panel’s responses to specific conditions occurring on the Protective points. Points EN | 87 Point Index Default: 1 Selection: 1 to 31 The number of the point personality you are programming. You can define up to 31 individual personalities.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 88 P ## Type Description 2 Interior: Interior points are armed only by master arming the area. They are not armed when using Perimeter Arming functions. These points are typically used to monitor interior detection devices such as interior doors, motion detectors, photoelectric beams, and carpet mats. Instant Interior Points: Interior points are usually programmed for an instant alarm (refer to Section 3.2 Point Responses on page 91).
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 89 P ## Type Description 4* Keyswitch Maintained: Program P## Pt Response as 1. Do not connect initiating devices to a Keyswitch point. Normal: The area is disarmed. Short: A short is a trouble when the area is disarmed. A short is an alarm when the area is armed. When this point changes from shorted to normal or open, it restores. Open: When this point changes from normal to open, the area arms.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 90 P ## Type Selection Description 7* D279 (O/C Non-Priority): The D279 provides point arming and disarming independent of the area arm state. A non-priority D279 point arm state does not affect the area arm state. Point Response must be programmed 1. Local bells are silenced through the keypad. For bell control at the D279, use P## Type 8. Open the W1 jumper on the D279 to send Point Opening and Point Closing Reports.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 3.2 Point Responses 3.2.1 Applications for Point Responses 9, D, and E: Combine Point Responses 9, D, and E with Perimeter point types to create more flexible 24-hour protection. Unlike 24-hour points, a faulted Perimeter point with a Point Response of D and E displays at the keypad when arming. Like a 24-hour point, a point programmed this way can generate alarms whether the area is armed or disarmed.
D9412GV3/D7412GV3 | Program Entry Guide | 3.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points If you want this point to ring the bell because the message failed to reach the central station receiver, program P## Audible After 2 Failures as Yes. P## Entry Tone Off Default: No Selection: Yes or No Yes Disables the entry delay tone when this perimeter point is faulted. No EN | 93 P## Ring Until Restored This is intended for use with points set to P## Type 1 (Perimeter).
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 When a point programmed for P## Silent Bell is faulted, the timer for the A# Burg Time starts, even though the bell is not yet ringing. As much as 3 min can elapse before the second attempt fails. Ensure that A# Burg Time is programmed to provide the amount of bell time you need, minus the additional 3 min that might elapse before the bell actually begins to ring.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 95 P## Buzz On Fault Default: 0 Selection: 0 to 3 Selection Operation for Controlled Points (Point Types 1, 2, and 3) Operation for 24-hour, Fire and Aux AC Supervision Points (Point Types 0 and 11) 0 The point buzzes at the keypad only if it enters into the trouble condition indicated in the P## Point Response.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points Do not use the Change Relays? function to toggle relays reserved for special functions. Special function relays are Area and Panel Wide Relay functions as well as relays assigned to CC## Enter Key Relay and P## Relay Response Type. P## Watch Point Default: Refer to the program record sheet Selection: Yes or No Yes Activates Watch Mode responses if the point is faulted while the control panel is in Watch Mode.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points Local While Disarmed suppresses all reports from 24-hour points. Do not use P## Type 0 for this prompt. Remember that this option works only for Disarmed points, and a Type 0 is a 24-hour Always Armed point. Instead, choose any type other than 0, and use a point response that reports an alarm, whether or not the point is armed. For instance, P## Type 1 and P## Response 9 reports an alarm on an open or a short (I) whether the area is armed or not.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 P## Bypass Returnable Default: No Selection: Yes or No Yes This point automatically returns to the system when the area is disarmed. Points Bypassing a 24-hour point: When a 24-hour point or 24-hour Supervisory point is bypassed, 24 HOUR BYPASS scrolls continuously at the keypad. Bypassing a Fire Point: FIRE BYPASS scrolls to indicate that a 24-hour Fire point or a Fire Supervisory point is bypassed.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 P## Swinger Bypass Points EN | 99 P## Defer Bypass Report Default: No Default: No Selection: Yes or No Selection: Yes or No Yes Enable Swinger Bypass for this point. Yes No Disable Swinger Bypass for this point. Send a Point Bypass Report with the Closing Report instead of a Command Bypass Report when a user bypasses the point. No Do not defer Bypass Reports. To meet UL requirements, set this parameter to No.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 The Cross Point feature does not activate when a fault occurs on Controlled points (Point Types 1, 2 and 3) in the disarmed, entry delay, or exit delay states. Refer to Section 5.9 Cross Point Parameters on page 139 for additional programming requirements to program the Cross Point Timer. Points EN | 100 P## Alarm Verify Default: Refer to the program record sheet Selection: Yes or No Yes Enable alarm verification on this point.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points When a sensor reset occurs, the control panel does not accept alarms from any points with P## Resettable programmed as Yes. During the 5-sec reset time, alarms from these points are ignored. 3.3 Do not mix fire and intrusion devices on the same powered loop.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Keypad Programming of P### Point Index D1255 1. Refer to Figure 1 on page 7 to access Keypad Programming and navigate to the POINT PARAMETERS option. The PT NUM 1 - ### option shows. 2. Enter the point number you wish to configure and press [ENT]. 3. The keypad shows the point number and the index number (for example, INDEX: 3). 4. Press [ENT]. An invisable editing cursor is enabled for point index number. 5. The [PREV] button acts as a [Backspace] key.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 103 P### Point Text P### Relay Default: Refer to the program record sheet Default: Refer to the program record sheet Selection: 0 to 8 Selection: Up to sixteen alphanumeric characters Use this option to activate a relay when the point is faulted. Refer to Table 28. Relays do not activate for Fire Supervisory or Non-Fire Supervisory points.
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 3.4 COMMAND 7 and COMMAND 9 These entries assign point indexes, associated relays that activate, and the text for the COMMAND 7 and COMMAND 9 keypad functions. CMD7 Point Index Default: 31 Selection: 0 to 31 Points CMD9 Point Index Default: 31 Selection: 0 to 31 This entry selects one of the 31 P## Index codes that define how the control panel reacts when a COMMAND 9 is initiated.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 4.0 Schedules (Skeds) 4.1 Windows Use this programming module to define the windows for Opening and Closing and User Access. 4.1.1 Opening and Closing Use these windows to set a schedule for disarming and arming. The disarming and arming schedules have several independent features: Suppress normal Opening or Closing Reports when A# Disable O/C in Windows is programmed as Yes.
D9412GV3/D7412GV3 | Program Entry Guide | 4.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) W# Open Window Start EN | 107 Make time entries using a 24-hour clock. For example: Default: 00: 00 Selection: HH:MM (hours and minutes) Midnight is entered as 00:00 7:00 AM is entered as 07:00 2:45 PM is entered as 14:45 11:59 PM is entered as 23:59 Enter the time you want the control panel to start the Opening Window. The window goes into effect at the beginning of the minute.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 108 Table 30: Programming for Two Same Day Opening Windows (refer to Figure 5) Open W# 1 2 Day of Week S M T W T F S S M T W T F S Close Early Begin Start Stop 06: 00 13 : 00 07 : 00 14 : 00 08: 00 15 : 00 Early Begin Start Stop eXcept On Holiday Yes / No Yes / No Holiday Index 1 2 3 4 1 2 3 4 Area(s) 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Do not program a single window to cross the midnight boundary.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 If the window must activate on the same day as it is programmed, reboot the control panel to activate the window immediately. W# Close Window Start Default: 00: 00 Selection: HH:MM (hours and minutes) Schedules (Skeds) EN | 109 W# Close Window Stop Default: 00: 00 Selection: HH:MM (hours and minutes) Enter the time that you want the control panel to end the Closing Window. The window stops at the end of the minute.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 W# Xept Holiday Schedules (Skeds) EN | 110 W# Holiday 1 Default: No Default: No Selection: Yes or No Selection: Yes or No Yes Do not activate this window on holidays. Yes Use Holiday Index 1 with this window. To use this selection, the window must be programmed to activate on at least one day of the week and a Holiday Index must be enabled. No Do not use Holiday Index 1 with this window.
D9412GV3/D7412GV3 | Program Entry Guide | 4.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 112 Table 36: Delivery Schedule* Open W# 3 Day of Week S M T W T F S Early Begin 02 : 30 Program at least one day Yes. * Close Start Stop Early Begin 02 : 45 03 : 00 03 : 05 Start Stop 03: 15 00 : 00 Day(s) of the week, but not on holidays 03: 30 01 : 00 eXcept On Holiday Yes No Yes No Yes Holiday Index 1 2 3 4 1 2 3 4 Select at least one index Area(s) 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Program at least one area Yes.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 UW# Sunday Schedules (Skeds) EN | 113 UW# Group Enable Default: No Default: 00:00 Selection: Yes or No Selection: HH:MM (hours and minutes) This prompt, and the next six day of the week prompts, select the days of the week that the User Group Window is active. Refer to the W# Sunday prompt in Section 4.1.1 Opening and Closing on page 105 for more information about programming this prompt.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 4.1.3 Schedules (Skeds) Holiday Indexes for User Group Windows You can enable up to four Holiday Indexes to use with User Group Windows. Enable at least one Holiday Index if UW# Xept Holiday is programmed as Yes for this user window, or if you want this window to activate only on specific dates. Holidays are programmed in Holiday Indexes. Refer to Section 4.3 Holiday Indexes on page 124 for programming information.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Default: 0 Selection: 0 to 24, 28, 29 1 2 3 4 Arm Area: This function simulates the Master Arm Delay keypad function. Entries in the S## Area # prompts define the area(s) this sked arms. The sked can arm multiple areas. If any point is faulted when the sked executes, it is force armed regardless of the A# Force Arm Bypass Max setting. Disarm Area: This function emulates the DISARM #? or DISARM ALL? keypad function list options.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Default: 0 Selection: 0 to 24, 28, 29 5 6 Unbypass All Points: This function is not available as a keypad function. The entry in the S## Area # prompt defines the area(s) where the sked unbypasses all points. The sked unbypasses all points in the area, regardless of how they were bypassed. This sked can unbypass all points in multiple areas. Relay On: This function emulates the Change Relay keypad function to turn relays on.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Default: 0 Selection: 0 to 24, 28, 29 9 Test Report: This function emulates the Test Report? sub-function of the Send Report? keypad function ([COMMAND][4][1]). This function generates a Test Report only from Area 1 but contains panel-wide status information. The report is sent to the phone(s) programmed for Test and Status Reports in Section 2.3.8 Communication Attempts on page 18.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Default: 0 Selection: 0 to 24, 28, 29 11 Execute Custom Func: This function emulates any of the custom functions assigned to the keypad that can be executed by a user from the keypad. When a sked executes a custom function, it is subject to the scope of the selected keypad. Cmd Center and Custom Func prompts appear after entering Function Code 11. Both entries are required.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Default: 0 Selection: 0 to 24, 28, 29 13 Schedules (Skeds) EN | 119 Adjust Time Forward One Hour: This sked function is used to make adjustments to the control panel’s clock. A typical application is to program this to go into effect at 2:00 AM on the date that Daylight Saving Time begins (during the springtime). No Time Change Report is sent or logged, but the new time appears in the next report logged. No other parameters require input for this option.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Default: 0 Selection: 0 to 24, 28, 29 17 18 Access Control Level Off: This function emulates the ACCESS CMD LEVEL command that determines whether a user’s token or card level is disabled. This function allows access to be turned off for the levels programmed. Unlock Door: This function emulates the UNLOCK? 12345678 keypad function for unlocking a door. Schedules (Skeds) S## Access Ctl Level # EN | 120 Yes Turn off access for level #.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Default: 0 Selection: 0 to 24, 28, 29 22 23 24 28 Access Authority Events Off: The control panel can log Access Granted Events when a valid token, RTE, REX, or Unlock Door Event is detected for a specific door. These events can be directed to print at a local printer or send a report remotely through phone routing. This sked disables Access Granted Events to be reported for Door #.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 29 Schedules (Skeds) EN | 122 Non-Expanded Off-Normal Test Report: Non-Expanded Off-Normal Test Report Events are only sent when any point is in the off-normal state from any area, but only sends the Off Normal Test Report Event. Any system trouble that is active also generates a Non-Expanded Off-Normal Test Report. The Event Log only shows a Test Report Event.
D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 123 S## Monday S## Time Default: 00:00 Default: No Selection: HH:MM (hours and minutes) Selection: Yes or No Enter the time that the sked executes. Make entries using a 24-hour clock (for example, 7:00 AM is entered as 07:00, 2:45 PM is entered as 14:45). Disabled skeds can have their time set to Disabled; however, to ensure that a sked is fully disabled, enter [COMMAND][5][2] (Change Skeds function) and select DISABLE?.
D9412GV3/D7412GV3 | Program Entry Guide | S## Holiday # Default: None Selection: Yes or No Yes Use Holiday Index 1 with this sked. No Do not use Holiday Index 1 with this sked. EN | 124 4.3 Holiday Indexes This programming module has two sections: Add/Change/Delete and View Holidays. Use the Add/Change/Delete section to program the Holiday Indexes. The View Holidays section is a view-only section provided for your convenience.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 5.0 AUXPARM 5.1 Introduction The programming prompts in this section are primarily used for programming enhanced communication capabilities for the GV3 Series Control Panels. AUXPARM 5.3 EN | 125 SDI Automation SDI automation defines the characteristics of a serial interface module (SIM) when used with home or business automation software.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 Status Rate AUXPARM 5.4 Default: 0 Selection: 0 to 255 0 Status information is sent only when requested. 1 to 255 Status information is sent at the interval programmed. If the Status Rate is set to a value less than 10, and 1 to 6 SDI devices are connected to the system, the fastest the control panel can send the status information is in approximately 1 sec.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 5.4.1 Configuration for RPS Over Network COMMAND 43 (Remote Programming) can establish communication with RPS over the phone or over the network. Figure 6 on page 128 and Figure 7 on page 129 show the structure of COMMAND 43. AUXPARM RPS Address Verification Default: No Selection: Yes or No Yes Verifies that the incoming RPS IP address matches the address entered in RPS IP Address. No Do not verify the RPS IP address.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 128 Figure 6: COMMAND 43 Flow Chart (D1255) Command 43, Remote Program idle text (Area Name) (area text) Command key pressed *System Command* 43 pressed Enter choice: RPS via Phone> RPS via Network> RPS via Network Allow Answer (or ringing) RPS via phone Enter choice: Use port 7700> Enter Port Number> RPS connecting...
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 129 Figure 7: COMMAND 43 Flow Chart (D1265) Idle text COMMAND 43 RPS VIA PHONE ? NEXT NEXT ESC RPS VIA NETWORK? NEXT ENT ENT ALLOW ANSWER ? USE PORT ##### ? ENT (or ringing) NEXT NEXT ENTER PORT NUM ? ENT ENT RPS CONNECTING ENTER PORT ##### ESC ##### ENT RPS CONNECTING Idle text Bosch Security Systems, Inc.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 RPS IP Address # Default: 0.0.0.0 Selection: 0.0.0.0 to 255.255.255.255 0 to 255 There are four numbers for an IP address. Leading zeros are not required. This prompt contains the IP address for RPS. An IP address has four fields. Each field has a range of 0 to 255. For example, an IP address is expressed as 110.227.64.190. Contact your network administrator to determine the IP address to which the RPS computer is connected.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 5.5 Programming Path Numbers and IP Addresses for Enhanced Communications Enhanced communications is the ability to communicate by some means other than the standard digital dialer. In this section, programmable parameters allow you to define up to four separate enhanced communication paths to which events can be routed.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 Refer to Keypad Programming of Path # IP Address, Path # Port Number, and Path # Poll Rate on page 132. Path # Poll Rate Default: 0 Selection: 0, 5 to 65535 sec 0 Disables the heartbeat poll (not recommended, refer to the first Important Note that follows). 5 to 65534 Enables the poll rate for the amount of time programmed here. 65535 The maximum number of 65535 sets the poll rate to once every 24 hr.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 8. The keypad shows the currently configured IP address. Press [NEXT]. The currently configured port number shows. 9. Press [ENT] to change the port number. 10. The [PREV] button acts as a [Backspace] key. Press [PREV] to delete the characters of the port number and then enter the new port number. 11. Press [ENT] to save the changes. When the keypad reads PARAMETER SAVED, your selection is configured. 12. Press [NEXT].
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 134 When the control panel first powers up, the first Heartbeat Poll for Path 1 is sent and is acknowledged in 1 sec. 120 sec after the first Heartbeat Poll is sent, the second Heartbeat Poll for Path 1 is generated and sent to the central station receiver.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 Example of Retry Count: An acknowledgment of the heartbeat was not received within 10 sec. The control panel sends the next Heartbeat Poll after the first 10-sec ACK wait period expires. If the central station does not acknowledge this Heartbeat Poll, the control panel continues to re-send. When the resend count is reached, the control panel declares this path as failed (and generates the Comm Trouble ## Event).
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 This item determines whether the NIM is supervised. If the NIM is supervised, disconnecting it from the control panel creates a Trouble SDI 88 Event and the keypad annunciates a trouble tone and displays SERVC SDI 88.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 137 Default: No If a second passcode is not entered within the programmed time, a Duress event is generated based on the first user code. Duress reports must be enabled in Routing in order to be sent to a central station. Selection: Yes or No Yes Forces the Summary Fire relay output to remain on after the Alarm Silence command.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 For SIA CP-01 Compliance: Abort Window is a required parameter. To meet UL requirements, the combined Entry Delay time and Abort Window time must not exceed 60 sec. For Entry Delay time programming information, refer to P## Entry Delay in the Point Responses section of your control panel’s program entry guide.
D9412GV3/D7412GV3 | Program Entry Guide | 5.0 Perimeter Relay Default: No Selection: Yes or No Yes Change the function of the area-wide fail-to-close relays to follow the perimeter armed states of their areas. No The area-wide fail-to-close relay operates normally. When set to Yes, the A# Fail to Close relay becomes an area-wide perimeter armed relay. This relay is activated when all areas assigned to the same relay have perimeter points that are armed.
D9412GV3/D7412GV3 | Program Entry Guide | 6.
D9412GV3/D7412GV3 | Program Entry Guide | 6.0 All SDI devices, regardless of area assigned, report to Area 1, Account 1 by default upon SDI failure. If a D9210B becomes disconnected, an SDI Fail ## and a Missing Point ### Event is created. If the D9210B is not programmed with a D# Entry Area, 9210 NOT READY appears at the keypad with this door assigned to it when you press the [ENTER] key.
D9412GV3/D7412GV3 | Program Entry Guide | 6.0 Door points must be programmed as Perimeter points. If a 24-hour point type is required for the Door point, you can use a Perimeter point type with a point response of 9 to C. Also, the debounce count must be set to 4 in Point Assignments. When assigning Points 1 to 8 (control panel zones), the end-of-line (EOL) resistors must be removed from the control panel.
D9412GV3/D7412GV3 | Program Entry Guide | 6.0 This command unlocks the door regardless of the armed state. Each fire alarm that is generated causes a Door Unlocked – Automatic Event. D# Disarm on Open? Default: Yes Selection: Yes or No Yes The area disarms only after the door is opened for a user with a valid disarm level. ACCESS CONTROL 6.2 EN | 143 Strike Profile This programming category is used to create a specific door profile for: Strike and shunt times.
D9412GV3/D7412GV3 | Program Entry Guide | 6.0 D# Buzz Time ACCESS CONTROL EN | 144 D# Deactivate On Open? Default: 2 sec Default: Yes Selection: 0 to 240 sec Selection: Yes or No 0 Buzz Time is not programmed for this door. Yes 1 to 240 The buzzer sounds for the amount of time programmed. Strike deactivates when the door is opened after a valid Access Granted request. No Strike remains activated for the amount of the programmed strike time whether door is opened or closed.
D9412GV3/D7412GV3 | Program Entry Guide | 6.0 D# REXShunt Only? ACCESS CONTROL EN | 145 D# Access Granted? Default: No Default: No Selection: Yes or No Selection: Yes or No Yes Programmed shunt time activates so the door can be manually opened. Yes Access Events from this door controller are sent to the control panel for processing. No REX automatically activates the programmed strike and shunt time.
D9412GV3/D7412GV3 | Program Entry Guide | 6.0 D# Enter Request? Default: No Selection: Yes or No Yes A Door RTE Event from this door controller is sent to the control panel for processing. No A Door RTE Event from this door controller is not sent to the control panel for processing. This program item determines if RTE Events are sent to the control panel for processing memory, printing, and remote reporting. RTE Events require D# Access Granted to be programmed as Yes.
D9412GV3/D7412GV3 | Program Entry Guide | 7.0 SIA CP-01 Quick Reference EN | 147 7.
D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory EN | 148 Programming Prompts Directory Panel and Area Wide Parameters ................ 12 P## Burglar Event .............................. 31 Phone ....................................................... 12 P## Access Event .............................. 31 Phone # ............................................ 12 P## User Event .................................. 31 Phone Parameters...................................
D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory EN | 149 Open/Close Options .............................. 43 Custom Function ................................ 58 A# Account O/C ................................. 44 CF### Text ........................................ 58 A# Area O/C ...................................... 45 CF### Key Strokes ............................ 58 A# Disable O/C in Window................. 45 User Interface...........................................
D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory EN | 150 Authority Level ................................... 67 L## Area O/C ..................................... 75 L## Disarm ........................................ 67 L## Restricted O/C............................. 75 L## Master Arm Delay ....................... 68 L## Perimeter O/C ............................. 75 L## Master Arm Instant L## Send Duress................................ 75 L## Perimeter Instant............
D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory EN | 151 U### User Group............................... 85 P### Point Text................................ 103 U### Area 1 [through Area #] Auth .... 85 COMMAND 7 and COMMAND 9............ 104 U### Name........................................ 86 CMD7 Point Index ............................ 104 U### Mstr Site ................................... 86 CMD7 Relay..................................... 104 U### Mstr Crd Data .........
D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory UW# Xept Holiday............................ 114 EN | 152 Supervise SDI 80 ............................. 125 UW# Holiday 1 [through 4] ............... 114 Schedules (Skeds) ................................ 114 Status Rate ...................................... 126 Sked Number................................... 114 SDI RPS Parameters............................. 126 S## TimeEdit ...................................
D9412GV3/D7412GV3 | Program Entry Guide | Programming Prompts Directory Strike Profile .......................................... 143 Door # .............................................. 143 D# Strike Time ................................. 143 D# Shunt Time ................................. 143 D# Buzz Time .................................. 144 D# Extend Time ............................... 144 D# Deactivate On Open? ................. 144 D# RTE Shunt Only? ....................... 144 D# REXShunt Only? ..
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY, 14450 USA www.boschsecurity.com © Bosch Security Systems, Inc.