D1256/D1257 Installation Instructions Fire Command Center/ Fire Alarm Annunciator
74-06925-000-B D1256/D1257 Installation Instructions Page 2 © 2000 Radionics
D1256/D1257 Contents 1.0 Introduction...................................................................................... 5 1.1 1.2 Before You Begin ............................................................................................... 5 Type Styles Used Here....................................................................................... 5 Tips, Notes, Cautions and Warnings ........................................................................................................5 1.
D1256/D1257 Contents Figures Figure 1: D1256/D1257 Internal Arrangement ......................................................................................................................7 Figure 2: Example 1 – Area Text.........................................................................................................................................10 Figure 3: Example 2 – Custom Function ...............................................................................................................
D1256/D1257 Introduction 1.0 Introduction 1.1 Before You Begin Before installing the D1256 or D1257, you should be familiar with the Operation and Installation manual and Program Entry Guide for the control/communicator you are using. When using the D1256 or D1257 with the D9112B, the software must be Revision 2.1 or higher. 1.2 Type Styles Used Here We use special type styles to help you identify the objects that we are describing in this guide.
D1256/D1257 Introduction Caution These caution the operator that physical damage to the program and/or equipment may occur. 1.3 Organization and Layout These installation instructions consists of 3 chapters and an appendix. The table below provides a brief description of each section. Chapter 1 Introduction This is the chapter you are reading. Chapter 2 Overview Description of the different parts of the D1256 & D1257.
D1256/D1257 Overview 2.0 Overview 2.1 D1256/D1257 Differences 2.1.1 D1256 The D1256 Fire Command Center is a four-wire serial device used with the following Radionics Control/Communicators: • D7212B • D9112B • D7212 • D7412 • D9112 • D9412 • D9124 (that uses the D9112LTB), and • D9124 (that uses the D9112LTB-EX) Each panel listed here supervise up to eight command centers. You can connect a total of 32 command centers to the system.
D1256/D1257 Overview 2.2.1 Display Both the D1256 and D1257 feature a 16-character English language display, with custom programmable text. The custom text is provided through programming the control/communicator. See Figure 1: D1256/D1257 Internal Arrangement. Both display the latest status conditions of the fire system using words, numbers, and symbols. When an alarm occurs, it is displayed until the user acknowledges the event at a command center.
D1256/D1257 Installation 3.0 Installation 3.1 Mounting the D1256 and D1257 The annunciators are low profile, surface-mounted units molded in durable red plastic. They can be mounted using the following optional packages: • • • 3.1.1 D56 Command Center Keypad Conduit Box (Protected surface or flush mount) D54B Command Center Flushmount Kit (Brass) D54C Command Center Flushmount Kit (Stainless Steel) Mounting Locations Do not mount annunciators in a location where they are exposed to direct sunlight.
D1256/D1257 Installation 3.3 Programming the Control/Communicator The Command Center, User Interface, Command Menu (for D7212B, D9112B) or Function List (D7212, D7412, D9112, D9412), and Passcode Worksheet sections of the control/communicator program determine the annunciator displays and functions available from the D1256. Key points to consider are described below. 3.3.1 3.3.2 Command Center Assignments 1. Command Center Text.
D1256/D1257 Installation CF 129 – TROUBLE SILENCE ? Key Stroke: A4CC. This custom function will be programmed as the second item in the Menu and will be executed whenever the TROUBLE SILENCE key is pressed on the D1256. This entry is equivalent to the execution of a Command 4 at the D1256. CF 130 – DETECTOR RESET ? Key Stroke: A47. This custom function will be programmed as the third Menu item and will be executed when the DETECTOR RESET key is pressed on the D1256.
D1256/D1257 Installation Menu Item and Function Radionics recommends that you program the first ten menu items as indicated below. The first four menu items must be programmed as indicated below for the D1256 to function properly. The first four keys on the D1256 annunciator execute the first four menu items turned on at the command center address. Menu items five through ten are optional features that you may or may not want to program into the D1256 system.
D1256/D1257 Installation 3.3.
D1256/D1257 Installation User Interface # 1 2 3 4 5 6 7 8 9 10 11 12 13 14 37 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 32 33 34 35 # 128 129 130 131 132 133 134 135 136 137 Functions* Disarm ? Master Arm Delay ? Master Arm Instant? Perimeter Instant ? Perimeter Delay ? Watch Mode ? Perimeter Part ? View Area Status ? View Memory ? View Pt Status ? Walk Test ? Fire Test ? Send Report ? ♦Door Control ? ♦Cycle Door ? ♦Unlock Door ? ♦Secure Door ? ♦Access Control Level? Change Display ? Change Time/Dat
D1256/D1257 Installation User Interface # 138 139 140 141 142 143 Custom Functions* Custom Function 138 Custom Function 139 Custom Function 140 Custom Function 141 Custom Function 142 Custom Function 143 Report Levels Force Arm ? Area O/C ? Restricted O/C ? Perimeter O/C ? Send Duress ? Passcode Arm ? Passcode Disarm ? E/P E E E E E E 1 2 3 4 5 Authority Levels 6 7 8 9 P P P P P P P E E E E E E E E E E E E E E E E E E E E E E E E E M I M D P D P D P D D E E E 10 11 12 13
D1256/D1257 Installation Further customization may be required if the D1256 is located in an unsecured area, or if D1255 Command Centers are installed in the system. The factory loaded program for the D9124 makes these functions available without requiring a passcode entry.