D7212GV3 Operation and Installation Guide EN Control Panel
D7212GV3 | Operation and Installation Guide | Trademarks Part 68 Trademarks Molex is a registered trademark of Molex Incorporated. Certifications and Approvals The D7212GV3 Literature Pack includes the D7212GV3 Approved Applications Compliance Guide (P/N: F01U143080). Refer to this guide for additional guidelines on installing the control panels in Underwriters Laboratories Inc. (UL) and fire-specific applications. Fire UL Underwriters Laboratories, Inc.
D7212GV3 | Operation and Installation Guide | Contents . Contents 1.0 2.0 2.1 2.2 3.0 3.1 3.1.1 3.1.2 3.2 3.3 3.3.1 3.3.2 3.3.3 3.3.4 3.3.5 3.3.6 3.3.7 3.3.8 3.3.9 3.3.10 3.3.11 3.3.12 3.3.14 3.3.15 3.3.16 4.0 4.1 4.2 4.3 4.4 4.5 4.5.1 4.5.2 4.5.3 4.5.4 4.5.5 4.6 4.6.1 4.6.2 4.6.3 4.6.4 4.6.5 4.7 4.8 Introduction ......................................................6 Lightning Strikes..............................................7 Effects ..................................................................
D7212GV3 | Operation and Installation Guide | Contents 9.0 9.1 9.1.1 9.1.2 9.1.3 9.1.4 9.1.5 9.2 9.3 9.3.1 9.3.2 9.3.3 9.3.4 9.3.5 9.3.6 9.3.7 9.3.8 9.4 9.4.1 9.4.2 9.4.3 9.4.4 9.4.5 9.4.6 9.4.7 9.5 10.0 10.1 10.1.1 10.1.1 10.1.2 10.1.3 11.0 11.1 11.2 11.2.1 11.2.2 11.3 11.4 11.4.1 11.4.2 11.4.3 11.4.4 4 Off-Board Points.............................................32 Point (Zonex) Bus: D7212GV3 Terminals ....32 POPIT Modules ...............................................32 POPEX Modules..................
D7212GV3 | Operation and Installation Guide | Figures . Figures Figure 1: Figure 2: Figure 3: Figure 4: Figure 5: Figure 6: Figure 7: Figure 8: Figure 9: System Configuration .................................8 Enclosure Mounting..................................14 Ground Fault Detect (S4) .........................15 Reset Pin ....................................................16 Service Walk Test Flow Chart .................19 Battery Terminals .....................................
D7212GV3 | Operation and Installation Guide | 1.0 Introduction 1.0 Introduction This manual addresses the operation and installation of the D7212GV3 Control Panel only. Throughout this guide, the words “control panel” refer to the D7212GV3 Control Panel. To obtain any of the documents in Table 1, contact Bosch Security Systems, Inc. Customer Service at (800) 289-0096 and request the documentation by its corresponding part number.
D7212GV3 | Operation and Installation Guide | 2.0 Lightning Strikes . 2.0 Lightning Strikes The control panel is designed to significantly reduce electromagnetic interference and malfunction generally caused by lightning. 2.1 Effects Any electronic system can be struck directly by lightning or be adversely affected by a lightning strike near the system.
D7212GV3 | Operation and Installation Guide | 3.0 Overview 3.0 Overview 3.1 Configuration and Parts Figure 1: System Configuration Each D8128D OctoPOPIT combines eight POPIT points in one module. D8129 OctoRelay provides alarm and auxilliary relay output. (Other functions available.) Control Panel D8125, ISW-D8125CW-V2, or D8125MUX Interface used for point expansion. DX4020 or ITS-DX4020-G allows communication over a Local or Wide Area network (LAN/WAN).
D7212GV3 | Operation and Installation Guide | 3.0 . 3.1.1 Overview Parts List The D7212GV3 Control Panel is shipped preassembled from the factory with the following parts: Literature Pack • D7212GV3 Program Record Sheet (P/N: F01U170810) • 7000/9000 Series Point Chart Label (P/N: 79-06660-000) Assembly • PC board • Faceplate shield • Mounting skirt • One #6 x 1/4-in. screw 3.1.2 Parts Available by Separate Order Order the following components separately to complete a basic 8-point installation.
D7212GV3 | Operation and Installation Guide | 3.0 3.2 Overview Accessories Refer to the Bosch Security Systems, Inc. Product Catalog for additional information.
D7212GV3 | Operation and Installation Guide | 3.0 Overview . 3.3 Features in the D7212GV3 3.3.1 SDI Molex Connector Use the SDI Molex Connector to easily connect an SDI device with the SDI bus. Possible applications include: • Connecting a DX4010i to program the control panel with Remote Programming Software (RPS) at the premises • Connecting a keypad to test the control panel. Do not connect the D5200 Programmer to the SDI Molex connector. Control panel firmware v8.
D7212GV3 | Operation and Installation Guide | 3.0 Table 4: Compatible Keypads Model D1255/ D1255B/ D1255RB D1256/ D1256RB D1257/ D1257RB D1260/ D1260B D720/ D720B Display 16-character alphanumeric Application Fire/Burglary/Access 16-character alphanumeric 16-character alphanumeric 4-line by 20character 8 LED Fire 3.3.8 3.3.
D7212GV3 | Operation and Installation Guide | 4.0 . 3.3.15 Other Features The D7212GV3 Control Panel has many programmable features. Some of the features are listed below. Complete details on all features are in the D7212GV3 Program Entry Guide (P/N: F01U170808).
D7212GV3 | Operation and Installation Guide | 4.0 Figure 2: Installation Enclosure Mounting 3 1 2 2 4 7 8 3 5 9 6 12345- 14 Point chart label Mounting skirt hooks (2) Module mounting holes (12) Tamper switch mounting holes (5) Skirt mounting hole (1) 6789- Enclosure mounting holes (5) Mounting skirt hook holes (2) Back of D7212GV3 Control Panel Lock down tab Bosch Security Systems, Inc.
D7212GV3 | Operation and Installation Guide | 4.0 Installation . 4.4 Installing the Control Panel 1. Place the control panel over the inside back of the enclosure, aligning the large rectangular openings of the mounting skirt with the mounting hooks of the enclosure. Slide the control panel down so that it hangs on the hooks. Refer to Figure 2, Item 2 on page 14. 4.5.3 To enable the Ground Fault Detect Enable feature, lock (close) the S4 Ground Fault Detect Pin on the control panel (Figure 3).
D7212GV3 | Operation and Installation Guide | 4.0 Releasing the reset pin from the closed position resets the control panel. The control panel resets all its timers, counters, indexes, and buffers. Any points that restore after a reset do not generate Restoral Reports. If the reset pin is placed in the disable position when all areas are armed, there must be an entry in the Answer Armed program item. Refer to RPS Parameters in the D7212GV3 Program Entry Guide (P/N: F01U170808).
D7212GV3 | Operation and Installation Guide | 4.0 . 4.6.5 Powering Up Reconnect the battery, then plug in the transformer. The buzzer sounds for two sec when the control panel is powered up. Leave the reset pin in the locked position. 4.9 Installation Testing the System After installing and programming the control panel, test the system completely. Test the control panel and all devices for proper operation.
D7212GV3 | Operation and Installation Guide | 4.0 Service Walk Test Procedure Refer to Figure 5 on page 19 for Service Walk Test options. Refer to the Walk Test procedures in the GV3 Series Owner’s Manual Supplement (P/N: F01U143082) when using a D1260 or D1260B Keypad. 1. Choose a keypad to conduct the test. Ensure that the display shows the idle disarmed text. 2. Press the [MENU] key to enter the Function List. Press [NEXT] repeatedly until the SERVICE WALK ? prompt appears. 3. Press [ENT].
D7212GV3 | Operation and Installation Guide | 4.0 Installation . Figure 5: Service Walk Test Flow Chart SERVICE WALK? ENT 40 PTS TO TEST Test a device ESC POINT TEXT (Text displays for 60 seconds) 39 PTS TO TEST ESC Test a device POINT TEXT (Text displays for 60 seconds) 38 PTS TO TEST ESC Test a device POINT TEXT 1 PTS TO TEST ESC Test a device 0 PTS TO TEST IDLE TEXT ESC VIEW UNTESTED? ENT # PTS UNTESTED NEXT ESC ESC POINT TEXT Bosch Security Systems, Inc.
D7212GV3 | Operation and Installation Guide | 5.0 5.0 Power Supply 5.1 Primary Power Terminals 1 and 2 5.1.1 Primary (AC) Power Circuit The primary source is a 16.5 VAC, 40 VA, internallyfused transformer (Bosch Security Systems, Inc. Model D1640). The control panel draws 200 mA when idle and 500 mA when in an alarm state. The total available auxiliary current is 1.4 A. Transient suppressors and spark gaps protect the circuit from power surges.
D7212GV3 | Operation and Installation Guide | 5.0 . 5.2.2 Installing the Battery 1. Place the battery upright in the base of the enclosure. 2. Locate the red and black leads supplied in the literature pack. 3. Connect the black battery lead to Terminal 4, and then to the negative (-) side of the battery. 4. Connect the red battery lead to Terminal 5, and then to the positive (+) side of the battery. Warning: High current arcs are possible.
D7212GV3 | Operation and Installation Guide | 5.0 Figure 7: Charging and Battery LEDs L EDs Off When No rmal 10.2 VD C - Battery Load Sh ed YELLOW - Ch arg ing Statu s RED - Low Battery - 12.1 VDC Investigate Low Battery reports immediately: If primary (AC) power is off and the discharge continues, the control panel becomes inoperative when the battery voltage drops below 10.2 VDC. 5.2.5 Power Supply When the battery voltage drops below 10.0 VDC, the control panel shuts down.
D7212GV3 | Operation and Installation Guide | 5.0 Power Supply . Table 7: Charging Status and Low Battery LEDs Type Charging Status LED Low Battery LED LED Color Yellow State Yellow Off Yellow On Yellow Flash once per minute Red Red Red Off On Red Flash (same as green LED) Action Shows the changing status of the battery. Refer to Figure 7 on page 22 for location. Battery is fully charged.
D7212GV3 | Operation and Installation Guide | 6.0 6.0 Power Outputs 6.1 Circuit Protection Three self-resetting circuit breakers protect the control panel from short circuits on the continuous and programmable power outputs. If the control panel is programmed for power supervision and a short circuit occurs on one of the power outputs, the control panel sends BATTERY LOW and BATTERY MISSING when using Bosch Security Systems, Inc. Modem IIIa2 communicator format.
D7212GV3 | Operation and Installation Guide | 7.0 . Voltage Output at Terminals 6, 7, and 8 If Terminals 6, 7, and 8 do not provide the expected output, check: • Programming for Relays A, B, and C in the relays section of the program. • Bell Parameters section of the program to confirm that the Alarm and Fire Bell responses are programmed for the expected duration and pattern. • Point Assignments section to confirm that each point is programmed for the expected local response. 6.4.
D7212GV3 | Operation and Installation Guide | 7.0 7.3 Telephone Connections Location 7.4 To prevent jamming of signals, wire the RJ31X or RJ38X jack before the in-house telephone system to support line seizure (Figure 8). Install the jack on the street side of the telephone switch, wired ahead of any PBX equipment. Line seizure temporarily interrupts normal telephone usage while the control panel sends data.
D7212GV3 | Operation and Installation Guide | 7.0 Telephone Connections . 7.5 Phone LED (Red) The red Phone LED illuminates when the control panel seizes the telephone line and remains illuminated until the control panel returns the telephone line. Refer to Figure 9 on page 26 for the location of the red LED. 7.6 Operation Monitor LED (Green) The green Operation Monitor LED indicates the operation of the central processing unit (CPU). When the CPU is operating normally, the LED flashes 0.
D7212GV3 | Operation and Installation Guide | 8.0 8.0 On-Board Points 8.1 Terminals 11 to 22 Description The control panel provides eight on-board points. Each point functions independently and does not interfere with the operation of the others. The control panel monitors the sensor loops for normal, shorted, or open conditions between an input terminal (11, 13, 14, 16, 17, 19, 20, or 22) and any of the point common terminals (12, 15, 18, and 21).
D7212GV3 | Operation and Installation Guide | 8.0 On-Board Points . 8.4 Point Response Time The control panel scans on-board and off-board point sensor loops every 300 ms. The Debounce program item in the Point Assignment section of the software determines point response time by setting the number of times the control panel scans a point before generating an alarm. The debounce count can range from 2 to 15; therefore, point response time ranges from 600 ms to 4.5 sec. The Bosch Security Systems, Inc.
D7212GV3 | Operation and Installation Guide | 8.0 On-Board Points Figure 11: Rothenbuhler 5110/4001-42 High Security Bell Wiring Configuration 2 1 3 1 6 0.64 mm (1/4 in.
D7212GV3 | Operation and Installation Guide | 8.0 On-Board Points . Figure 12: Wiring the Rothenbuhler 5110/4001-42 High Security Bell to the D7212GV3 Control Panel 4 1 9 1 7 9 2 13 5 6 6 2 3 3 RE D ORG WHT BL K 7 4 12 8 9 1 2 3 3 6 11 9 N/O 1 10 COMM 1 N/C 1 X1 X1+ 1234567∗ 5110 Logic Board 4001-42 External Line Balancing Module D7212GV3 Control Panel Alarm output Alternate alarm Common +12.
D7212GV3 | Operation and Installation Guide | 9.0 Off-Board Points 9.1.3 9.0 Off-Board Points 9.1 Point (Zonex) Bus: D7212GV3 Terminals 9.1.1 POPIT Modules The D7212GV3 can use point of protection input transponder (POPIT) modules to provide a maximum of 32 off-board points, bringing the total number of points the D7212GV3 can monitor to 40. Each offboard point requires a POPIT Module.
D7212GV3 | Operation and Installation Guide | 9.0 Off-Board Points .
D7212GV3 | Operation and Installation Guide | 9.0 Off-Board Points Figure 13: Connecting the D8125 POPEX to the D7212GV3 Control Panel 1234- D8125 POPEX Module Switch block D9127 Sensor Loop 33 kΩ EOL resistor (P/N: P106F, package of eight) 5 - Zonex expansion loop 6 - Up to 32 POPITs 7 - Off-board points Do not loop wiring around any terminal. 34 Bosch Security Systems, Inc.
D7212GV3 | Operation and Installation Guide | 9.0 Off-Board Points . 9.3 Installing the D8125 POPEX Module For information on the Multiplex Bus Interface, refer to the D8125 Multiplex Bus Interface Operation and Installation Guide (P/N: F01U034973). Save the POPIT Label Sheets: The D8125 is packaged with two sets of POPIT label sheets. One set is marked “Bank 1” for use with the D7412GV3 and D7212GV3. The other set is marked “Bank 2” for use with the D9412GV3 and D9112.
D7212GV3 | Operation and Installation Guide | 9.0 9.3.4 Wiring Data Expansion Loops to POPEX Modules Each POPEX Module has two positive (+) and two negative (-) data expansion loop terminals. Up to 32 POPITs can be connected to one D8125 on the D7212GV3 (refer to Figure 13 on page 34). To connect the data expansion loops to the D8125 POPEX Module: Off-Board Points 9.3.6 Six switches on each POPIT assign the module to a point number.
D7212GV3 | Operation and Installation Guide | 9.0 Off-Board Points . Figure 14: Program Record Sheet 9.3.8 POPIT Labels 9.4 D7212GV3 off-board points are numbered 9 to 40. Two sheets of peel-off POPIT labels are supplied with the D8125 POPEX Module. Use the sheet marked “Bank1” for Points 9 to 40. Each label has two parts. Place the smaller part, with only the point number, on the chip. Place the larger part, with the switch settings, on the base of the POPIT. Set the switches and cover the POPIT.
D7212GV3 | Operation and Installation Guide | 9.0 The D8128D is also suitable for fire supervisory applications, such as indicating circuit supervision (using the D192G Bell Circuit Supervision Module), sprinkler supervision, and valve tamper protection. Use the D125B for two-wire smoke detectors. The D129 is usually used for water-flow switches. Off-Board Points 9.4.3 Installation For the most effective installation, use the following four-step process: 1. Set the OctoPOPIT switches. Refer to Section 9.
D7212GV3 | Operation and Installation Guide | 9.0 Off-Board Points . Table 14: Switch 5 Settings for Line Termination Is a D8125 POPEX Module connected? No Yes Switch 5 Setting(s) on D8128D OctoPOPIT(s) Set Switch 5 of only one D8128D to ON Set Switch 5 of all D8128Ds to OFF Point DIP Switches Each point connected to the D8128D is enabled by closing the respective DIP switch, or disabled by opening the DIP switch.
D7212GV3 | Operation and Installation Guide | 9.0 Off-Board Points Figure 16: Connecting D8128D OctoPOPITs to the D7212GV3 1 - Zonex 1 address 2 - Sensor loops Refer to Address Switches in Section 9.4.4 Setting the OctoPOPIT Switches on page 38 for information about making these switch settings. Refer to Table 14 on page 39 for information about setting Switch 5. Do not loop wiring around any terminal. 40 Bosch Security Systems, Inc.
D7212GV3 | Operation and Installation Guide | 9.0 Off-Board Points . Using Molex Connectors Each D8128D Module is supplied with a 30 cm (12 in.) female-to-female Molex cable assembly. P1 and P2 are Molex connectors that parallel the COM, IN, OUT, and +12.0 VDC terminals on the terminal strip.
D7212GV3 | Operation and Installation Guide | 9.0 9.4.7 OctoPOPIT Sensor Loops Off-Board Points Figure 18: D8128D OctoPOPIT Sensor Loops Only the resistance on the loop limits the number of normally-open or normally-closed detection devices each sensor loop can supervise. Resistance on each sensor loop must be less than 100 Ω with the detection devices connected. 1 Certain UL and NFPA applications can limit the number of detection devices. Consult the appropriate UL or NFPA standards.
D7212GV3 | Operation and Installation Guide | 10.0 Off-Board Relays . 10.0 Off-Board Relays 10.1 D8129 OctoRelay Use the D8129 OctoRelay to add relay outputs to the system in groups of eight. The D7212GV3 allows up to 24 relay outputs. Review Section 6.0 Power Outputs on page 24 to ensure that enough power is provided for the OctoRelays and other powered devices that are connected to the system. OctoRelays for relay numbers 1 to 24 connect to Zonex 1, Terminal 28. Refer to Figure 19 on this page.
D7212GV3 | Operation and Installation Guide | 11.0 10.1.1 Relay Outputs Relay outputs can activate when you are setting the OctoRelay switches or programming the control panel. Disconnect equipment connected to relay outputs when you perform these functions. Each OctoRelay output provides a Form C dry contact rated for 1.0 A at 12.0 VDC. Normally-open, common, and normally-closed terminals are available for each relay output.
D7212GV3 | Operation and Installation Guide | 11.0 . 11.2.1 Assigning an Address for the Keypad 11.2.2 Installation Switches on the keypad assign an address (1 to 8). The address determines if the keypad is supervised, the scope of the keypad, and to what area the keypad is assigned. Refer to Keypad Assignment in the D7212GV3 Program Entry Guide (P/N: F01U170808) for a complete description of addresses. Refer to the keypad installation manuals for installation and mounting instructions.
D7212GV3 | Operation and Installation Guide | 11.0 The control panel and the D8132 (or other power supply) must share Arming Devices COMMON. Figure 20 shows the common form of the D8132 Module connected to the common on the keypad and the common on the control panel. Any stand-alone power supply, powering any device connected to the control panel, must also be connected to a common terminal on the control panel.
D7212GV3 | Operation and Installation Guide | 11.0 Arming Devices . 11.3 D279A Independent Zone Control Any on-board or OctoPOPIT point can be programmed so that the D279A Independent Zone Control operates as independent point control (arming and disarming the point). Refer to Point Assignments in the D7212GV3 Program Entry Guide (P/N: F01U170808) for programming information. Refer to the D279A Operation and Installation Instructions (P/N: 46458) for wiring and operation instructions. 11.
D7212GV3 | Operation and Installation Guide | 12.0 Table 20 shows the correct switch setting for Address 17. 12.0 SDI Devices 12.1 Table 20: Description The D7212GV3 Control Panel can support a number of accessory devices from the SDI Bus using Terminals 29 through 32. Some devices include the D1255RB and D1255 Keypads (refer to Section 11.0 Arming Devices on page 44), D9131A Parallel Printer Interface Module, ITS-DX4020-G GPRS/GSM Communicator, and DX4020 Network Interface Module. 12.
D7212GV3 | Operation and Installation Guide | 13.0 . The ITS-DX4020-G GPRS/GSM IP Communicator has two modes; GPRS uses Modem IIIa2; and GSM uses Contact ID. For programming information refer to the ITS-DX4020-G GPRS/GSM IP Communicator Installation and Operation Guide (P/N: F01U163066). Figure 22: DX4020 DIP Switch Settings Programmer Connections If supervised and the module does not respond to control panel supervision polls, SERVC SDI 88 or SERVC SDI 92 appears at the keypad.
D7212GV3 | Operation and Installation Guide | 13.0 13.2 Installer Keypad and Local Programmers Mode While installing or maintaining a D7212GV3 control panel, it is sometimes necessary to change the configuration. To do so, a local keypad programming menu is available in the Service Menu. You can access the Service Menu when the control panel is in stand-by mode or while it is operating. Refer to the D7212GV3 Control Panel Program Entry Guide (P/N: F01U170808) for an explanation of the programming menu.
D7212GV3 | Operation and Installation Guide | 14.0 D7212GV3 Faceplate . 14.0 D7212GV3 Faceplate Figure 24: D7212GV3 Faceplate 1234567- Charging status LED (yellow) Low battery LED (red) Color-coded battery leads Ground fault detect enable Phone LED (red) Tip Telephone cord connector Bosch Security Systems, Inc. | 10/10 | F01U143079-03 8 - Ring 9 - S3, Point 8 EOL selection 10 - Operation monitor LED (green) 11 - Accessory connector 12 - Programming connector Do not use with firmware version 8.
D7212GV3 | Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A Appendix A: System Wiring Diagrams, Issue A Figure 25: D7212GV3, Power Supply Side System Wiring 1 - If required by local AHJ, connect the D113 Battery Lead Supervision Module. 2 - Batteries 3 - D122 Dual Battery Harness, as required. 4 - D1640 Transformer and D8004 Transformer Enclosure required for NFPA applications. 5 - D8132 Dual Battery Charger with two batteries (Batteries are not supervised.
D7212GV3 | Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A . Figure 26: D7212GV3, Input Points and Peripheral Devices System Wiring CLASS 2 TRANSFORMER 16.5 VAC 40 VA 60 Hz Model D1640 Internally Fused - Do not short Requires Unswitched Outlet Do not share with other equipment D7212GV3 + AUX POWER BATTERY NEGATIVE ONLY CAUTION: Avoid damage to Panel. Do not connect 24 V to terminals. Maximum charging current 1.
D7212GV3 | Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A Use zero retard for the D129, except for water-flow devices. All external connections except Terminal 5 (battery positive) are power limited. The D7212GV3 control panel is not UL listed for commercial faire applications.
D7212GV3 | Operation and Installation Guide | Appendix B: Point Address Chart . Appendix B: Point Address Chart Place the labels on the base of the POPIT. Do not attach labels to the POPIT cover. A bullet (•) in the switch column indicates that the switch is set to ON. Use D9127 POPITs for Points 9 to 40. D9127 POPITs have DIP switches 0 to 6.
D7212GV3 | Operation and Installation Guide | Specifications Specifications Table 22: Specifications Voltage Input (Power Supply) Current Requirements Power Outputs* Minimum Operating Voltage SDI Bus Telephone Connections Battery Discharge/ Recharge Schedule Primary: Terminals 1 and 2 16.5 VAC 40 VA class 2 plug-in transformer (D1640) Secondary: Terminals 4 and 5 Sealed lead-acid rechargeable battery (12.0 VDC, 7 Ah or 12.0 VDC, 17.2 or 18 Ah). The control panel supports up to two 12.
D7212GV3 | Operation and Installation Guide | Notes . Notes . Bosch Security Systems, Inc.
© Bosch Security Systems, Inc.