Installation Guide

D9412GV4/D7412GV4/D7212GV4 | Installation and Operation Guide | 9.0 Off-Board Points
Bosch Security Systems, Inc. | 3/12 | F01U266054-01 47
Figure 16: D8128D OctoPOPIT Layout
23451 678
P O I N T S
1
2
3
4
1 - Interconnect wiring connectors
2 - Address DIP switches
3 - Terminal strip
4 - Point DIP switches
9.4.3 Installation
For the most effective installation, use the
following four-step process:
1. Set the OctoPOPIT switches. Refer to Section
9.4.4 Setting the OctoPOPIT Switches.
2. Physically mount the OctoPOPIT in the
enclosure. Refer to Section 9.4.5 Mounting
OctoPOPITs, page 48.
3. Wire the OctoPOPIT. Refer to Section 9.4.6
Wiring OctoPOPITs on page 48.
4. Wire the OctoPOPIT sensor loops. Refer to
Section OctoPOPIT Sensor Loops on page 53.
9.4.4 Setting the OctoPOPIT Switches
The D8128D OctoPOPIT has two sets of DIP
switches (Figure 16 on page 47). Use the DIP
switches on the top of the unit (with the terminal
strip along the left edge) to set the address for
the OctoPOPIT. Use the DIP switches at the
bottom of the unit to enable or disable individual
points connected to the OctoPOPIT.
Address Switches
The switches on the D8128D OctoPOPIT set
point assignments and line termination. These
switches are easier to set before mounting the
D8128D in the enclosure.
Switches 1, 2, 3, and 4 assign the OctoPOPIT
sensor loops to point numbers on the control
panel. Table 12 shows the OctoPOPIT switch
settings for point assignments.
Switch 5 sets line termination. Refer to
Error!
Reference source not found..
Table 12: D8128D OctoPOPIT Switch Settings
ZONEX 1 D8128D Address Switches ZONEX 2
Points 9 to
127 1 2 3 4 5
Points 129
to 247
9 to 16 ON ON ON ON * 129 to 136
17 to 24 ON ON ON OFF * 137 to 144
25 to 32 ON ON OFF ON * 145 to 152
33 to 40 ON ON OFF OFF * 153 to 160
41 to 48 ON OFF ON ON * 161 to 168
49 to 56 ON OFF ON OFF * 169 to 176
57 to 64 ON OFF OFF ON * 177 to 184
65 to 72 ON OFF OFF OFF * 185 to 192
73 to 80 OFF ON ON ON * 193 to 200
81 to 88 OFF ON ON OFF * 201 to 208
89 to 96 OFF ON OFF ON * 209 to 216
97 to 104 OFF ON OFF OFF * 217 to 224
105 to 112 OFF OFF ON ON * 225 to 232
113 to 120 OFF OFF ON OFF * 233 to 240
121 to 127 OFF OFF OFF ON * 241 to 247
* Line Termination Switch
For the D8128D OctoPOPITs assigned to
Points 121 to 127, 241, and 247, set Point
Input Switch 8 to the OPEN position.
D9412GV4 uses Points 9 to 127 on Zonex
1 and Points 129 to 247 on Zonex 2.
D7412GV4 uses Points 9 to 75 on Zonex 1
only.
D7212GV4 uses Points 9 to 40 on Zonex 1
only.