Testing your System (continued)
Fire Walk Test
This test is used to confirm that Smoke detectors will report alarms to the keypads. The Fire Walk Test tests all fire zones, including verified
fire and waterflow.
This test requires you to manually alarm each zone.
At the start of the Fire Walk Test a Fire Walk Test report, if programmed, is sent to the central station. Fire alarm reports are not sent to the
central station during the Fire Walk Test. A Fire Walk Test restoral is sent upon completion of the Fire Walk Test.
The Fire Walk Test is enabled for 20 minutes once it is started. The test time is extended to 20 minutes every time another zone is tested.
When a fire zone is tested, any output programmed to follow that zone will activate for 5 seconds.
A Fire Walk Test will prevent the system from sending any Fire Reports during the test.
Type of Test Command
Sequence
What Will Happen What To Do
Fire Walk
Test
[PIN[ + [#] [9] [1]
“Fire Test” will display followed by the zone number of any
zones that have not been tested.*
The zone LEDs of any untested zones will flash.**
“Fire Testing” will display followed by the zone number of
the zone that is currently being tested.*
The zone LED for the zone currently being tested will run
on steady.**
As each zone is tested, the display returns to “Fire Test”
and indicates the remaining untested zones.*
As each zone is tested, its LED turns off.**
Test each zone as
instructed by your
installaing company.
Exit the Zone Test
using [PIN] + [#]
*DS7447/
DS7447E only
**DS7445/
DS7445i only