Table Of Contents
DSA E-Series (E2800 12-bay) Maintenance | en 35
Bosch Sicherheitssysteme GmbH Installaton manual 2018.02 | V1 | DOC
2. If the Recovery Guru in SANtricity System Manager still shows an issue, select Recheck to
ensure the problem has been resolved.
3. If the Recovery Guru indicates that drive reconstruction did not start automatically, start
reconstruction manually, as follows:
Note: Perform this operation only when instructed to do so by technical support or the
Recovery Guru.
Select Hardware.
Click the drive that you replaced.
From the drive's context menu, select Reconstruct.
Confirm that you want to perform this operation.
When the drive reconstruction completes, the volume group is in an optimal state.
4. As required, reinstall the bezel on the front of the unit.
5. Return the failed part to Bosch, as described in the RMA instructions shipped with the
kit.
8.2 Replacing a power-fan canister
Each 12-bay controller unit or 12-bay expansion unit includes 2power supplies with integrated
fans. These are referred to as power-fan canisters in SANtricity System Manager. If a power-
fan canister fails, you must replace it as soon as possible to ensure that the unit has a
redundant power source and adequate cooling.
Before you begin
You have a replacement power-fan canister (power supply) that is supported for your 12-
bay controller unit or 12-bay expansion unit.
You have an ESD wristband, or you have taken other antistatic precautions.
About this procedure
Use this procedure to replace a power-fan canister in the following shelves:
12-bay controller unit
12-bay expansion unit
12-bay dual controller unit - rear view
1
1 Power-fan canisters
12-bay expansion unit - rear view
1