User manual
Panel Controller Fault message | en 53
Bosch Sicherheitssysteme GmbH Operation guide F.01U.076.969 | 6.0 | 2010.04
10.2.8 Signals
Optical signals
An internal buzzer sounds on the panel and the "fault" signal light turns yellow.
Depending on the type of fault, an additional yellow signal light lights up (see also
Section 4.2 Display elements, page 21):
– Fault System
– Fault Transmission Device
– Fault Signals
Acoustic signal
An internal signal tone sounds on the system.
To temporarily switch off the internal buzzer:
Press the "Signal tone off" key.
The internal signal tone is switched off.
10.3 Resetting malfunction message
Depending on the configuration, three different variants are offered for resetting; see
Section 9.7 Resetting alarm message, page 47.
There are two ways to reset a fault message:
– Select Reset in the message display or
– Select the fault message and then press Reset in the detailed view
The selected element/element group is reset.
If a list field is marked with an "R", the process of resetting is not yet complete for this
element.
If an element cannot be reset, it will continue to be displayed in the list.
After the successful resetting of all elements, the standby display is displayed.
10.4 Isolating an element
In order to isolate an element that has caused a fault:
1. Select the fault message you require.
2. Select Block.
CAUTION!
If a message does not have to be reset, it is removed from the display as soon as the fault has
been rectified.
TEXT R
CAUTION!
The system does not transmit any information as to whether it was possible to isolate the
selected element. To monitor the operation, check the element.