Panel Controller Isolate | en 57
Bosch Sicherheitssysteme GmbH Operation guide F.01U.076.969 | 6.0 | 2010.04
12 Isolate
This chapter contains information about the following points:
Section 12.2 Isolating and de-isolating elements, page 57
Section 12.3 Displaying list of all isolated elements, page 58
12.1 Menu overview
12.2 Isolating and de-isolating elements
Select the element you require in the submenu.
Example:
To isolate a detector, select the following in the start menu:
1. Bypass Block
2. Block
3. Detector
Various selection criteria are displayed. See also Section 5.6 Working with lists, page 27.
4. Select a selection criterion, e.g. By description.
A list of the detectors is displayed. Refer to Section 5.6.1 Scrolling through lists, page 28
for information on how to scroll forward and backward through the list.
5. Select the required list fields.
The list fields are marked.
6. Select Block.
The selected elements are isolated.
To de-isolate the elements again, repeat all previous steps, but select Un-block in step 6.
A C after a detector means that this detector is part of a closed group and cannot be isolated
individually. In order to isolate a detector marked in this way, please select Logical zone in
step 3.
CAUTION!
Bypassed detectors: Alarm messages from bypassed detectors are no longer displayed, only
faults.
Isolated detectors: Isolated detectors are not analyzed.
Bypass
Block
-> Bypass Show blocked devices Select by
number
Block Group Printer
Block -> Sounder Strobe HVAC Doorholder
Transmission device Detector Extinguishing
system
Annunciator
Logical zone More... -> Control
element
Interface
module
C