User manual
68 en | Maintenance – walktest Panel Controller
F.01U.076.969 | 6.0 | 2010.04 Operation guide Bosch Sicherheitssysteme GmbH
15 Maintenance – walktest
This chapter contains information about the following points:
– Section 15.1 Walktest groups, page 68
– Section 15.2 Starting and ending walktest, page 70
– Section 15.3 Ending walktest for all elements, page 71
– Section 15.4 Displaying tested or untested elements, page 71
– Section 15.5 Assigning tested elements to a walktest group, page 72
A walktest is indicated by a yellow LED display on the panel.
15.1 Walktest groups
The following options are available for switching elements to walktest:
– Select individual elements from lists and/or
– Select previously defined walktest groups consisting of at least one element.
There are 12 pre-defined walktest groups. The number of possible walktest groups is
predefined: January to December.
Example:
Detectors which are to be tested in May, can be grouped together in a group called May.
New elements can be added to a group, and elements that have already been added can be
removed.
CAUTION!
Alarm or fault messages from detectors switched to walktest are not forwarded to
transmission devices or extinguishers.
NOTICE!
If a signaling device is activated during a walktest, it emits a different signal tone to the one it
emits in the alarm state.
NOTICE!
Even if the elements in a group (e.g. January) have been completely deleted, this group will
still be displayed in the list.