68 en | Maintenance – walktest Panel Controller
F.01U.076.969 | 6.0 | 2010.04 Operation guide Bosch Sicherheitssysteme GmbH
15 Maintenance – walktest
This chapter contains information about the following points:
Section 15.1 Walktest groups, page 68
Section 15.2 Starting and ending walktest, page 70
Section 15.3 Ending walktest for all elements, page 71
Section 15.4 Displaying tested or untested elements, page 71
Section 15.5 Assigning tested elements to a walktest group, page 72
A walktest is indicated by a yellow LED display on the panel.
15.1 Walktest groups
The following options are available for switching elements to walktest:
Select individual elements from lists and/or
Select previously defined walktest groups consisting of at least one element.
There are 12 pre-defined walktest groups. The number of possible walktest groups is
predefined: January to December.
Example:
Detectors which are to be tested in May, can be grouped together in a group called May.
New elements can be added to a group, and elements that have already been added can be
removed.
CAUTION!
Alarm or fault messages from detectors switched to walktest are not forwarded to
transmission devices or extinguishers.
NOTICE!
If a signaling device is activated during a walktest, it emits a different signal tone to the one it
emits in the alarm state.
NOTICE!
Even if the elements in a group (e.g. January) have been completely deleted, this group will
still be displayed in the list.