User manual
Panel Controller Further functions | en 87
Bosch Sicherheitssysteme GmbH Operation guide F.01U.076.969 | 6.0 | 2010.04
4. Select Call back to restore the connection with the Remote Access center.
Active is displayed when a connection has been made to the Teleservice.
To disconnect the connection, select Stop RAM.
19.5 Change password
1. Select Further functions in the start menu
2. Change password
A list of all operators is displayed.
Refer to Section 5.6.1 Scrolling through lists, page 28 for information on how to navigate
through a list.
3. Select the list field you require.
4. Enter the password.
On the display, each digit of the password is indicated with an asterisk so that nobody
else can see the password.
5. Enter a new password and repeat the entry in the bottom field again.
6. Select OK to confirm the entry or Cancel to cancel the operation.
19.6 Performing a fire drill
During a drill, all signaling devices are activated.
To start a drill:
1. Select Further functions in the start menu
2. Drill
3. Confirm Start drill with OK
The drill is started.
To end the drill, select Stop drill.
During the fire drill, fire alarms, fault messages and supervisory alarms are displayed.
To switch between the fire drill display and the message display in question, select Return to
message screen or Return to drill screen on the status bar.
If an alarm or a fault/supervisory alarm is sounded during a fire drill, the panel controller
reacts as described in the table below:
NOTICE!
If all operators with the same access authorization have the same password, this function
cannot be used.
CAUTION!
If a genuine alarm is reported during a fire drill, the fire drill is abandoned. The fire drill can
only be restarted when the alarm is ended.
Fire alarm Fault/
supervisory alarm
The drill signaling devices are
switched off.
Yes No
The drill is automatically
terminated.
Yes No