Installation guide

There is a groove on the top of the extensions. Make sure that
the board has been correctly installed.
Notice!
A maximum of two extensions can be connected:
FPC-500‑2: No extension can be connected
FPC-500‑4: One extension can be connected
FPC-500‑8: Two extensions can be connected
Wiring
External components such as zones, notification appliances,
inputs, etc. are wired to screw terminals attached to the upper
side of the board.
No
.
Meaning FPC‑500
-2
FPC‑500
-4
FPC‑500
-8
1 Inputs 1 1 2
2 Zones 2 4 8
3 Aux power supply 1
4 Notification appliance 2
5 Alarm and fault relay 1/1
3.3
Conventional Fire Panel Installation | en 19