Installation guide

Notice!
Note that the maximum line resistance for conventional zones is
22.5 Ohm.
The voltage of the zones is 20 VDC ±1 V.
The maximum current of the zones is 100 mA ±5 mA.
Notice!
Observe local regulations for the maximum number of detectors
in a zone.
When using the FLM-320-EOL4W Module, use the battery
calculator included on the CD.
Notice!
The last zone of the fire panel supports the use of 4-wire
detectors.
The fire panel does not support dual-detector dependency with
4-wire detectors.
Please use permissible external power supply units depending
on power consumption.
Notice!
Activating a manual call point in a zone programmed as "No
Delay" triggers an immediate alarm.
Notice!
Only use manual call points in zones which are programmed as
No Delay.
22 en | Installation Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH