Installation guide

System Configuration
To be able to perform the actions in operating level 3, you will
need a code you can enter with the zone keys.
Notice!
The following codes are programmed in delivery status:
Operating level 2: 1234
Operating level 3: 3333
The basic settings can be found in Default Settings, page 74.
Calling up operating level 3
Press the "Code input" key.
You will be prompted to enter a code.
C O D E /
Enter the code with zone keys 1 to 8.
You are in the programming menu of the system.
!
Caution!
In operating level 3, the fire panel is not operational. None of
the inputs and outputs are monitored.
Automatic exit of level 3
If you are in level 3 and no key has been pressed for 10 minutes,
the system will exit level 3 automatically.
One minute before exiting level 3, a pulse tone of the internal
buzzer indicates the time. The time up to the automatic exit of
level 3 is displayed in the LCD display.
4
Conventional Fire Panel System Configuration | en 31