Installation guide

FPC-500
‑2
FPC-500
‑4
FPC-500
-8
Zones
Voltage
Max. output current
Max. line resistance
20 VDC ±1VDC
100 mA ±5 mA
22.5 Ohm
AUX
Voltage
Max. output current
Max. line resistance
Fuse
21 VDC to 29 VDC
500 mA ±10%
22.5 Ohm
0.75 A @ 60 V
Notification appliance outputs
Voltage
Max. output current
Max. line resistance
Fuse
21 VDC to 29 VDC
500 mA ±10% per output
22.5 Ohm
0.75 A @ 60 V
Relay outputs
Breaking capacity
Max. line resistance
1 A @ 30 VDC
22.5 Ohm
Transistor outputs
Breaking capacity
Max. line resistance
No inductive loads
20 mA @ 24 VDC
22.5 Ohm
Recommended cable type Unshielded cable, 0.8-mm
cable diameter, cable cross
section up to 1.5 mm
2
Batteries
Max. inner resistance
Max. current consumption
Fuse
800 mOhm
2.3 A
5 A @ 60 V
End-point voltage 21.4 V
60 en | Technical Data Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH