Zones
– Voltage
– Max. output current
– Max. line resistance
20 VDC ±1VDC
100 mA ±5 mA
22.5 Ohm
AUX
– Voltage
– Max. output current
– Max. line resistance
– Fuse
21 VDC to 29 VDC
500 mA ±10%
22.5 Ohm
0.75 A @ 60 V
Notification appliance outputs
– Voltage
– Max. output current
– Max. line resistance
– Fuse
21 VDC to 29 VDC
500 mA ±10% per output
22.5 Ohm
0.75 A @ 60 V
Relay outputs
– Breaking capacity
– Max. line resistance
1 A @ 30 VDC
22.5 Ohm
Transistor outputs
– Breaking capacity
– Max. line resistance
No inductive loads
20 mA @ 24 VDC
22.5 Ohm
Recommended cable type Unshielded cable, 0.8-mm
cable diameter, cable cross
section up to 1.5 mm
2
Batteries
– Max. inner resistance
– Max. current consumption
– Fuse
800 mOhm
2.3 A
5 A @ 60 V
End-point voltage 21.4 V