Installation guide
Communication parameters
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
Notification appliances
Standby
– A-
– B+
Alarm state
– A-
– B+
10 V to 15 V
0 V to 0.5 V
0 V to 1 V
21 V to 29 V
Inputs
– Alarm resistor 820 ohm ±5%
– EOL Resistor 3900 ohm ±1%
Zones (with resistance combination)
– Alarm resistor 820 ohm ±5%
910 ohm ±5%
No 2-Det Depend: 680 ohm
±5%
– EOL Resistor 3900 ohm ±1%
Zones (with EOL modules)
– Alarm resistor 820 ohm ±5%
910 ohm ±5%
No 2-Det Depend: 680 ohm
±5%
6.1.1
Conventional Fire Panel Technical Data | en 61
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980