Installation guide
Information as per EN 54‑4, chapter 7.1
a) This is a power supply unit that is installed in the FPC‑500
Fire Panel. It provides power to the device and the connected
peripherals and is used to charge the two connectable batteries.
b) Technical data
1) Recommended power
output
61 W
2) Power supply 230 VAC +10%/-15%, 50–60 Hz
Operating voltage 26 VDC to 29 VDC
3) Communication
parameters
None
4) Fuse values 3.15 A/250 V
5) Batteries 2 x 7.0–7.2 Ah (max.) lead gel
battery
6) Max. current
consumption
2.3 A
7) Max. battery inner
resistance
800 mOhm
8) I
min
70 mA
I
max, a
0.7 A
I
max, b
2.3 A
9) Cable parameters
Battery Cable enclosed
Board power supply Wired ex works
230-V power supply 1.5-mm
2
standard cable
6.4
Conventional Fire Panel Technical Data | en 63
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980