Data Sheet

Fire Alarm Systems | FPE‑1000‑NE Networking Card 3‑Ethernet
FPE‑1000‑NE Networking Card 3‑Ethernet
www.boschsecurity.com
u Provides three Ethernet ports using CAT 5 or better
cable
u Uses simple plug-in connection to the FPA‑1000‑V2
u Connects as either Class A or Class B
u Uses standard RJ45 connections
u Provides second power input port for normal
network operation during maintenance
The FPE‑1000‑NE Ethernet Networking Card provides
two Ethernet ports for in/out peer‑to‑peer
communication and one additional Ethernet port for
communication with the fiber optic and wired cards,
for IP reporting, or for browser-based panel/network
programming.
Functions
Auxiliary Power
The networking card typically receives power from the
FPA‑1000‑V2 mainboard. The networking card can,
however, be powered by an auxiliary power supply
(nominal 24 VDC with 2-pin connector). When both
power sources are connected to the networking card,
only one source supplies power to the card without
interference by or with the other supply. This allows
the network to continue to function when
maintenance requires the networking card be
disconnected from the mainboard.
Certifications and approvals
Region Certification
USA UL FSZI: Emergency Alarm System Control
Units (ANSI/UL 2017) and UOJZ: Con-
trol Units, System (ANSI/UL 864)
CSFM see our website
FDNY-
CoA
#6101
Installation/configuration notes
Mounting
Mount the networking card along the bottom of the
keypad on the mainboard. Copper leads on the
networking card slide into terminals on the mainboard
and a the mounting bracket on the networking card
snaps into place onto the keypad base.
Connections
All Ethernet connections are made with a minimum of
CAT 5 cable at a maximum length of 328 ft (100 m).

Summary of content (2 pages)