Data Sheet

Fire Alarm Systems | FPP‑RNAC‑8A‑4C Remote Notification Appliance Circuit (RNAC) Power Supply
FPP‑RNAC‑8A‑4C Remote Notification
Appliance Circuit (RNAC) Power Supply
www.boschsecurity.com
u 8 A of power
u Fully supervised outputs
u Configurable for NAC output or constant auxiliary
power
u Regulated 24 VDC output (nominal) with
over‑current protection
u Built‑in NAC patterns
Use the FPP‑RNAC‑8A‑4C power supply to add four
additional notification appliance circuits to a fire alarm
control panel (when connected via the option bus), or
as a NAC power supply for fire-protective signaling
systems (when connected directly to the NAC output).
The additional notification appliance circuits can be
NFPA 72, Class B (Style Y) or Class A (Style Z).
This regulated power supply provides up to 8 A of
power that is used to operate both continuous and
intermittent loads. This 8 A of power can be
distributed through the four output circuits and
auxiliary power circuit. The FPP‑RNAC‑8A‑4C power
supply is UL Listed for use in commercial fire alarm
applications.
Functions
Compatible Control Panel Connections
The FPP‑RNAC‑8A‑4C power supply is compatible with
any UL Listed control panel that uses reverse polarity
supervised notification outputs with 12 VDC or 24 VDC
regulated outputs. It is also compatible with the
following Bosch Control Panels:
D7022 Two‑zone Conventional FACP
D8024 and D10024A Analog FACPs
For the D7022 conventional panel and the D8024
and D10024A analog panels, the FPP‑RNAC‑8A‑4C
connects through a NAC circuit. No option bus
connection is necessary.
D7024 Four‑zone Addressable FACP
DS9400i Four‑zone FACP
DS9400M AddressiFire FACP
Connect up to two FPP‑RNAC‑8A‑4C power
supplies to a D7024, DS9400i, or DS9400M
Control Panel. The control panel can individually
control each of the four NAC outputs for each
power supply. Only the four NAC outputs of a
single power supply will be synchronized.
FPD‑7024 or FPA‑1000 Analog Addressable Fire
Panels
Connect up to four FPP‑RNAC‑8A‑4C power
supplies to an FPD‑7024 or an FPA‑1000 control
panel. Each RNAC’s four NAC outputs will be
synchronized and can be individually controlled
for a total of 16 synchronized circuits.
NAC Output Patterns
The NAC circuits can be set to produce the following
output patterns:
Steady
Temporal Code 3